RMWH-SVX001C-EN
11
Installation
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify that no power is present
with a voltmeter. To prevent electrical shock, the circuit
board cover must be in place when power is on.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
Receiving, Unpacking, and
Inspecting
1. Upon receipt of the device, inspect the shipping
container for signs of damage. Report any damage to
the carrier and record the information on the delivery
receipt.
2. Carefully remove the device from its shipping
container to avoid causing damage to sensitive
electrical components. If damage has occurred, file the
appropriate claim with the shipping carrier
immediately.
3. Review all contents of the shipping container to make
sure all of the following components are included:
a. Device
b. Instruction manual CD
c. End-of-line filters (quantity determined by number
of ports ordered)
d. Remote horn (if equipped)
e. Protective foam
4. Notify Trane of any shortages immediately.
5. Keep the original packaging in case it is necessary to
return the device for service.
6. Release the two latches on the left side of the device.
7. Open the enclosure.
8. Carefully inspect the internal components and
assemblies for damage or shortages. If damage has
occurred, file the appropriate claim with the shipping
carrier immediately.
9. Before installation and use, keep the device in a dry,
secure place in the original shipping container.
Mounting Guidelines
WARNING
Proper Mounting Location!
Failure to follow instructions below could result in an
explosion which could result in death or serious injury.
DO NOT install the device in areas that contain a
flammable mixture of gas and air.
Do not mount the device directly to chiller, piping, or
piping supports.
Mount the device:
•
In a location that is easy to access and visible to
personnel before they go into the area being
monitored.
•
To a rigid surface that does not have vibration or
mechanical shock.
•
In a vertical position.
•
Approximately 5 ft (1.5 m) above the ground (refer to
and
).
•
With at least 3 in. (7.62 cm) of clearance around all
sides for proper ventilation, calibration, and servicing.
Make sure there is adequate space to connect the
external wiring and sample line piping (refer to
).
•
With the appropriate hardware. Make sure the
hardware is suitable for the mounting surface and can
withstand 70 lb (9 kg) without loosening or causing
damage to the hardware or mounting surface. Use all
four mounting holes provided on the device (refer to
).
•
Away from exposure to direct solar heating and other
excessive heat sources.
•
Away from wet or damp conditions.
•
Away from areas that are dirty or exposed to oils or
chemicals.