Installation
14
RMWH-SVX001C-EN
•
To achieve this connection, install a 10 AWG or larger
copper wire between the grounding lug terminal strip
on the right side of the TruSense™ RMWH Refrigerant
Monitor device and the grounding point (protective
earth). The wire length cannot be longer than 6 ft (2 m).
The TruSense™ RMWH Refrigerant Monitor Wiring
Diagram (
) gives the details of the wiring
requirements for the device.
Figure 11.
TruSense™ RMWH refrigerant monitor wiring diagram