Applications for SCC Mode
AO: Analog Output
The analog output on the MP501 is a 0–10 Vdc output with a maximum current draw of 10 mA from
the connected device.
shows a wiring diagram with the MP501 in this configuration.
Note:
The MP501 will control only one actuator. You cannot have both a 0–10 Vdc actuator and a
tri-state modulating actuator connected to the controller at the same time.
Overriding Outputs
The MP501 includes a manual output test. Use this feature to manually control the outputs in a
defined sequence. Refer to the section,
.
Wiring Diagrams
The following figures show the MP501 outputs wired in three different ways.
the MP501 controlling a tri-state modulating actuator. The MP501 controlling staged outputs is
shown in
shows an application with the MP501 controlling an analog
(0–10 Vdc) actuator.