Table 28. Effective occupancy output
nviOccManCmd
nviOccSchedule
Occupancy Sensor
Arbitration Result
Bypass Timer
nvoEffectOccup
Occupied
Does not matter
Does not matter
Does not matter
Occupied
Unoccupied
Does not matter
Does not matter
Zero
Unoccupied
Not zero
Bypass
(a)
(a) Occupied bypass is initiated by either a communicated request (nviOccManCmd = bypass) or a local input (zone sensor timed override ON button).
Bypass
2
Occupied
Does not matter
Does not matter
(b)
(b) Whenever an update of nviOccManCmd is received indicating Bypass, the bypass timer is set to the nviBypassTime and the countdown starts.
Occupied
Unoccupied
Does not matter
Zero
Unoccupied
Not zero
Bypass
Standby
Does not matter
Zero
Standby
Not zero
Bypass
Not valid
Occupied
Does not matter
Occupied
Unoccupied
Zero
Unoccupied
Not zero
Bypass
Standby
Does not matter
Does not matter
Zero
Standby
Not zero
Bypass
Not valid
Occupied
Occupied
Does not matter
Occupied
Unoccupied
Zero
Standby
(c)
(c) If nviOccManCmd and nviOccSensor are not valid, nviOccSchedule is occupied, the bypass timer is zero, and the binary input is occupancy. Then, the
occupancy binary input can switch the control between occupied and occupied standby.
Not zero
Bypass
Unoccupied
Does not matter
Zero
Unoccupied
Not zero
Bypass
Standby
Does not matter
Zero
Standby
Not zero
Bypass
Not valid
Occupied
Does not matter
Occupied
Unoccupied
Zero
Unoccupied
Not zero
Bypass
CNT-SVX08F-EN
55
Troubleshooting