69-1592–1

10

MULTISTAGE ELECTRONIC THERMOSTAT

Pub. No. 18-HD28D1-1

TROUBLESHOOTING GUIDE (continued)

Symptom

Possible Cause

Action

Cooling will not
come on.

No power to the thermostat.

Check that B terminal is connected to the system
transformer.

Check for 24 Vac between B and R or R and Y terminals.

If missing 24 Vac:

Check if the circuit breaker is tripped—reset the
circuit breaker.

Check if the system fuse is blown—replace the fuse.

Check if the system switch at the equipment is in the
Off position—set to the On position.

Check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is
activated.

Wait up to five minutes for the system to respond.

Enter Installer Setup mode number 33. Reconfigure
minimum off time (if required).

System selection is not set to
Cool.

Set system selection to Cool.

Cooling setpoint is above room
temperature.

Check cooling setpoint. Set cooling setpoint to desired
temperature.

Heating or cooling
comes on
momentarily and
shuts off.

Heat or cool circuit is opening
up or becoming high
impedance.

Add resistor in parallel with load or install interface relay.

System On
indicator is lit, but
no heat is being
delivered.

Fan operation set for 00
(conventional heat) when it
should be set for 01 (electric
heat).

Enter Installer Setup mode number 02 and reconfigure the fan
operation.

Conventional heating   
equipment turns on the fan
when the furnace has  
warmed up to a setpoint.

Wait a minute after seeing the On indicator and then check the
registers.

Heating equipment is not
operating.

Verify operation of heating equipment in system test.

Outdoor
temperature   
not displayed

a

.

Option not activated.

Enter Installer Setup mode number 24 and set to 01.

Thermostat must have OT terminals and a TAYSENS100A
installed.

Outdoor
temperature   

Outdoor sensor is connected
incorrectly.

Refer to TAYSENS100A installation instructions and check
wiring between the thermostat and sensor.

display is incorrect

a

Incorrect sensor.

Replace sensor with TAYSENS100A  Sensor.

Содержание TAYSTAT 375

Страница 1: ...e product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTIO...

Страница 2: ...the mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 for typical hookups A letter code is located near each terminal for identification CAUTION E...

Страница 3: ...NFORMATION KEY i DECREASE TEMPERATURE SETTING INCREASE TEMPERATURE SETTING Fig 6 Thermostat key locations and descriptions SETTINGS System and Fan Settings System settings control the thermostat opera...

Страница 4: ...ded off periods by providing air circulation to prevent stagnation and improved moisture removal due to increased run time Cooling Droop is most effective in mild weather conditions and during nightti...

Страница 5: ...e 2 cooling cycle rate 10 03 3 3 cph recommended 2 or 5 cph not recommended 02 or 05 02 2 cph 05 5 cph System setting adjustment 12 00 Automatic changeover 01 or 02 01 Manual changeover 02 Auto Only D...

Страница 6: ...4 85 Highest heating sepoint setting 55 to 85 Temperature range 1 F increments of heating stpoint setting Temperature range stops in cooling 35 65 Lowest cooling sepoint setting 65 to 99 Temperature r...

Страница 7: ...cool turns off 30 Stage one cool and system fan turn off Fan Equipment System Test i 40 Change from cooling to fan equipment system test 41 Fan comes on 40 Fan turns off Key Operation System Test IMP...

Страница 8: ...here Applicable Allow the outdoor temperature sensor to absorb the outdoor air for a minimum of five minutes before taking a reading With an accurate thermometer 1 F 0 5 C measure the temperature at t...

Страница 9: ...ings will not change Example Cannot set the The upper or lower temperature limits were reached Check the temperature setpoints Heating limits are 55 to 85 F 13 to 29 C Cooling limits are 65 to 99 F 18...

Страница 10: ...e room temperature Check cooling setpoint Set cooling setpoint to desired temperature Heating or cooling comes on momentarily and shuts off Heat or cool circuit is opening up or becoming high impedanc...

Страница 11: ......

Страница 12: ...Tyler TX 75711 9010 CUSTOMERASSISTANCE If after reading this guide you have any questions concerning the operation of your thermostat please call the Thermostat Customer Assistance Helpline at 1 877 8...

Отзывы: