BAS-SVX084A-EN
23
Wiring Installation
The three values are joined together to form the BACnet device ID for the unit controller as shown
in the following table.
Device ID Assignment for BACnet/IP Devices
For devices connecting over BACnet/IP, Tracer SC+ calculates the device ID with the following:
•
The BACnet network number for the BACnet/IP link. (This number can be changed by the user).
•
The unit controller rotary switch value. (The Tracer SC+ rotary address is not used to calculate
BACnet/IP device IDs).
The following table shows this process using a Tracer UC600 unit controller.
Table 8.
Calculating the BACnet/IP Device ID
For BACnet MS/TP Network numbers higher than 4190,TTrraacceerr SSCC++ will not be able follow
this scheme and will not propose a Device ID for the unit controller. The controller can be installed
with the Device ID number previously assigned to it.
Note:
It is very important to avoid duplication of BACnet network numbers or device IDs.
Application Wiring
This section provides information about pre-configured wiring for the following applications:
•
•
“Duct Temperature Sensor Wiring,” p. 25
•
Note:
For more details about mounting, wiring, and configuring wireless zone sensors, refer to the
section,
.
Zone Sensor Wiring
Zone Sensor Hard Wired Option
Depending on the zone sensor options used, a maximum of seven (7) wires may be required to run
from the Symbio
210 controller to the zone sensor. The zone sensor options are:
•
Zone sensor (temperature only);
Part Number X1351152801
.
•
Zone sensor with timed override (TOV) on/cancel button;
Part Number X1351153001
.
•
Zone sensor with adjustable setpoint thumbwheel,
Part Number X1351152901
.
•
Zone sensor with adjustable setpoint thumbwheel, timed override (TOV) on/cancel button;
Part Number X1351152701
.
•
Zone sensor with digital display;
Part Number X1379088601
.
Note:
Display sensor has factory mounted communication module.
•
Communications module;
Part Number X1365146702, one (1) box of 12
.
Table 7.
Calculating the BACnet Device ID
Tracer SC+ rotary switch value (21)
0
2
1
Tracer SC+ BACnet MS/TP link number (1)
1
Unit controller rotary switch value (38)
0
3
8
BACnet Device ID 211038
0
2
1
1
0
3
8
BACnet network number Eth port 1 (1)
1
Unit controller rotary switch value (42)
0
4
2
BACnet/IP Device ID: 0142
0
1
0
4
2