UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVX051A-GB
6
Unit Description
Sintesis™ Balance
Multi-Pipe CMAF is an Air-to-Water
scroll compressor unit designed for outdoor installation.
The unit can work in different operating modes as below:
1. Heat recovery Mode (H Cooling)
2. Cooling Mode
3. Heat Pump Mode
The units have two independent refrigerant circuits, two
or three compressors per circuit. Units are designed
with a brazed plate exchanger for both chilled/hot water
exchanger and a fin and tube coil exchanger which work
as air evaporator/ condenser
Each unit is completely assembled, hermetic packaged,
refrigerant circuit factory piped, electrical components
wired, leak tested, dehydrated, charged and tested.
The water inlets and outlets openings are covered for
shipment.
Units feature Trane’s exclusive Tracer Symbio™ 800
Control logic and controls. It monitors the control
variables that govern the operation of the unit. Control
logic can correct these variables, when necessary, to
optimize operational efficiencies, avoid unit shut down,
and keep producing chilled or hot water.
These units comes with various options and can be
customized depending on capacity, efficiencies, acoustic
levels, applications requirements at the time of order
placement.
Unit received and its options can be cross-checked with
the serial and model number provided in unit nameplate
and description provided under unit model number
description provided in manual.
Nameplates
The nameplates are applied to the exterior of the control
panel. A compressor nameplate is located on each
compressor.
Unit Nameplate
The unit nameplate provides the following information:
•
Unit model and size description
•
Unit serial number
•
Identifies unit electrical requirements
•
Lists correct operating charges of refrigerant and
refrigerant oil
•
Lists unit service pressures
Compressor Nameplate
The compressor nameplate provides following
information:
•
Compressor model number.
•
Compressor serial number.
•
Compressor electrical characteristics.
•
Utilization range.
•
Refrigerant type(s).
•
Oil type.