11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
CG-SVX051A-GB
5
Note
:
For unit’s delivered in France, scheduled time for
unit inspection and notifying through registered letter in
case of visible and concealed damage is only 72 hours.
Loose Parts Inventory
Check all the accessories and loose parts that are
shipped with the unit against the shipping list. Included
in these items will be the water vessel drain plugs,
rigging and electrical diagrams, service literature,
which are placed inside the control panel and/or starter
panel for shipment. If optional elastomeric isolators
are ordered with the unit they are shipped mounted on
the horizontal support frame of the unit. The isolators’
location and distribution weight diagram is placed with
the service literature inside the starter/ control panel.
Warranty
Warranty is based on the general terms and conditions
of the manufacturer. The warranty is void if the
equipment is repaired or modified without the written
approval of the manufacturer, if the operating limits are
exceeded or if the control system or the electrical wiring
is modified. Damage due to misuse, lack of maintenance
or failure to comply with the manufacturer’s instructions
or recommendations is not covered by the warranty
obligation. If the user does not conform to the rules of
this manual, it may entail cancellation of warranty and
liabilities by the manufacturer.
Startup MUST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY.
Maintenance contract
It is strongly recommended that you sign a maintenance
contract with your local Service Agency.
This contract provides regular maintenance of your
installation by a specialist in our equipment. Regular
maintenance ensures that any malfunction is detected
and corrected in good time and minimizes the possibility
that serious damage will occur. Finally, regular
maintenance ensures the maximum operating life of
your equipment. We would remind you that failure to
respect these installation and maintenance instructions
may result in immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and
maintaining it in perfect operating condition over a long
period of time, the manufacturer has at your disposal
a refrigeration and air conditioning service school. The
principal aim of this is to give operators and technicians
a better knowledge of the equipment they are using,
or that is under their charge. Emphasis is particularly
given to the importance of periodic checks on the unit
operating parameters as well as on preventive
maintenance, which reduces the cost of owning the unit
by avoiding serious and costly breakdown.
Refrigerant
The refrigerant provided by the manufacturer meets
all the requirements of our units. When using recycled
or reprocessed refrigerant, it is advisable to ensure its
quality is equivalent to that of a new refrigerant. For this,
it is necessary to have a precise analysis made by
a specialized laboratory. If this condition is not respected,
the manufacturer warranty could be cancelled.
General Information