Controls

Trane Chiller Plant Automation

Trane’s depth of experience in chillers and
controls makes us a well-qualified choice
for automation of chiller plants using air-
cooled Series R

®

 chillers

®

. The  chiller  plant

control capabilities of the Trane Tracer
Summit

®

 building automation system are

unequaled in the industry. Our chiller plant
automation software is fully pre-
engineered and tested. It is a standard
software application, not custom
programming which can prove to be
difficult to support, maintain, and modify.

Energy Efficiency

Trane chiller plant automation intelligently
sequences starting of chillers to optimize
the overall chiller plant energy efficiency.
Individual chillers are designated to
operate as base, peak, or swing based on
capacity and efficiency. Sophisticated
software automatically determines which
chiller to run in response to current
conditions. The  software  also
automatically rotates individual chiller
operation to equalize runtime and wear
between chillers.

Trane chiller plant automation enables
unique energy-saving strategies. An
example is controlling pumps, and chillers
from the perspective of overall system
energy consumption. The software
intelligently evaluates and selects the
lowest energy consumption alternative.

Regulatory Compliance Documentation

Comprehensive documentation of
refrigerant management practices is now
a fact of life. Trane chiller plant automation
generates the reports mandated in
ASHRAE Guideline 3.

Keeping Operators Informed

A crucial part of efficiently running a
chiller plant is assuring that the
operations staff is instantly aware of
what is happening in the plant. Graphics
showing schematics of chillers, piping,
pumps, and towers clearly depict the
chiller plant system, enabling building
operators to easily monitor overall
conditions. Status screens display both
current conditions and upcoming
automated control actions to add or
subtract chiller capacity. Series R

 and

other chillers can be monitored and
controlled from a remote location.

Tracer Summit features standard report
templates listing key operating data for
troubleshooting and verifying
performance. Reports for each type of
Trane chiller and three and six-chiller
systems are also standard. Detailed
reports showing chiller runtimes aid in
planning for preventative maintenance.

Swift Emergency Response

We understand the importance of
maintaining chilled water production
while protecting your chillers from costly
damage. If no water flow is detected to a
chiller’s piping, the start sequence is
aborted to protect the chiller. The next
chiller in the sequence is immediately
started to maintain cooling.

In the event of a problem, the operator
receives an alarm notification and
diagnostic message to aid in quick and
accurate troubleshooting. A snapshot
report showing system status just prior to
an emergency shutdown helps operators
determine the cause. If emergency
conditions justify an immediate manual
shutdown, the operator can override the
automatic control.

Integrated Comfort

 Capabilities

When integrated with a Tracer Summit
building management system
performing building control, Trane chiller
plant automation coordinates with Tracer
Summit applications to optimize the total
building operation. With this system
option, the full breadth of Trane’s HVAC
and controls experience are applied to
offer solutions to many facility issues. If
your project calls for an interface to other
systems, Tracer Summit can share data
via BACnet

, the ASHRAE open systems

protocol.

LonTalk Chiller Controls

LonTalk is a communications protocol
developed by the Echelon Corporation.
The LonMark association develops
control profiles using the LonTalk
communication protocol.  LonTalk is a unit
level communications protocol, unlike
BACNet used at the system level.

LonTalk Communications Interface for
Chillers (LCI-C) provides a generic
automation system with the LonMark
chiller profile inputs/outputs. In addition to
the standard points, Trane provides other
commonly used network output variables
for greater interoperability with any
automation system.  The complete
reference list of Trane LonTalk points is
available on the LonMark website.  Trane
controls or another vendor’s system can
use the predefined list of points with ease
to give the operator a complete picture of
how the system is running.

Hardwire Points

Remote devices wired from the control
panel are another reliable method of
providing auxiliary control to a building
automation system.  Inputs and outputs
can be communicated via a typical 4-20
mA electrical signal (or an equivalent Vdc
signal of 0-10 or 2-10) or by utilizing
contact closures.

• External Chilled Water Setpoint

• External Current Limit Setpoint

• Condenser-Regulating Valve Control

• Percent of Full Run Load Amps Output

• Condenser Pressure Output

• Refrigerant Monitor Input

• Programmable Relays
Allows the selection of 4 relay outputs
from a list of eight different default
settings:  Alarm-Latching, Alarm-Auto
Reset, General Alarm, Warning, Chiller
Limit Mode, Compressor Running, Head
Pressure Relief Request, and Tracer
Control.  These contact closures may be
used to trigger jobsite supplied audible or
visual alarms

• Ice Making Control
Provides an interface with ice making
control system and safeties, enabling
both ice making and daytime comfort
cooling

• Chilled Water Temperature Reset
Supplies controls, sensors and safeties to
reset the chilled water temperature
setpoint based upon return water
temperature (standard) or outdoor air
temperature (optional)

Содержание RTHD

Страница 1: ...SeriesR HelicalRotary LiquidChillers Model RTHD 175 450T ons 60 Hz 125 450T ons 50 Hz Built for Industrial and Commercial Applications RLC PRC020 EN June 2006...

Страница 2: ...n via the LCD touch screen display freedom from interoperability concerns with LonMark communications job specific communication options that allow greater reporting flexibility Improved startup tempe...

Страница 3: ...ures and Benefits Options Controls Application Considerations Selection Procedure Model Nomenclature General Data Electrical Data and Connections Dimensions andWeights Mechanical Specifications Conver...

Страница 4: ...mal Storage Specifiers and operators benefit from dual setpoint control and industry leading temperature efficiency and control capabilities plus outstanding support through partnership with Calmac a...

Страница 5: ...rovides maximum efficiency high reliability and low maintenance requirements Electronic expansion valve with fewer moving parts than alternative valve designs offers highly reliable operation Suction...

Страница 6: ...2 4 and 203 2 mm sizes Nitrogen Charge Unit is shipped with a nitrogen holding charge in lieu of refrigerant Seal Kit for Reassembly Ideal for situations when the bolt together construction of the RTH...

Страница 7: ...ice making and daytime comfort cooling Options Programmable Relays Default set factory installed programmable relays allow the operator to select four relay outputs from a list of eight Available rel...

Страница 8: ...on including normal cooling and icemaking Water temperatures and setpoints Loading and limiting status and setpoints Average line current Outdoor air temperature Start stop differential timers Auto Ma...

Страница 9: ...ng In the event of a problem the operator receives an alarm notification and diagnostic message to aid in quick and accurate troubleshooting A snapshot report showing system status just prior to an em...

Страница 10: ...to obtain and maintain this differential at startup but for continuous operation a design should maintain a 25 F 13 9 C differential from evaporator leaving water temperature to condenser leaving wat...

Страница 11: ...s This ideal balance of design integrity with installation and operating cost considerations can also be obtained by consulting aTrane representative and applying theTrane System Analyzer program Wate...

Страница 12: ...developed using the most current standard fouling factors Part Load Performance Actual air conditioning system loads are frequently less than full load design conditions Depending on the number of ch...

Страница 13: ...Performance with Fluid Media OtherThanWater Series R chillers can be provided with a wide variety of fluid media other than water including ethylene glycol and propylene glycol in the evaporator conde...

Страница 14: ...C UL Digit 13 Pressure Vessel Code A ASME L Chinese Pressure Vessel Code Digit 14 Evaporator Frame B B Frame C C Frame D D Frame E E Frame F F Frame G G Frame Digit 15 Evaporator Capacity 1 Tube coun...

Страница 15: ...igit 43 Power Line Connection Type A Terminal Blocks B Mechanical Disconnect Switch D Circuit Breaker F High Interrupt Circuit Breaker H Ground Fault Circuit Breaker J Ground Fault High Interrupt Circ...

Страница 16: ...B2 B2 B2 45 170 29 110 HFC 134a 410 186 B2 C2 D2 58 220 34 129 HFC 134a 490 222 C1 D6 E5 45 170 29 110 HFC 134a 490 222 C1 D5 E4 52 197 32 121 HFC 134a 490 222 C1 E1 F1 82 310 60 226 HFC 134a 525 238...

Страница 17: ...114 200 17 76 200 D2 28 125 200 19 83 200 D3 31 134 200 20 89 200 D4 22 97 200 15 65 200 D5 22 97 200 15 65 200 D6 18 81 200 12 54 200 E1 28 125 200 19 83 200 F1 36 156 250 24 104 200 F2 38 168 250 2...

Страница 18: ...200 21 76 200 D2 34 125 200 23 83 200 D3 37 134 200 25 89 200 D4 27 97 200 18 65 200 D5 27 97 200 18 65 200 D6 22 81 200 15 54 200 E1 28 125 200 23 83 200 F1 43 156 250 29 104 200 F2 46 168 250 31 11...

Страница 19: ...ta 50 Hertz NominalVoltage 380 400 415 Compressor Voltage 342 360 374 Code Utilization Range 418 440 457 Max kW 139 145 148 B1 B2 RLA Max kW 233 233 233 LRA Y 391 412 428 LRAD 1229 1296 1348 Max kW 20...

Страница 20: ...RLC PRC020 EN 20 Electrical Data and Connections...

Страница 21: ...21 RLC PRC020 EN Electrical Data and Connections...

Страница 22: ...3 17 560 7 965 16 168 7 334 D1 D1 E1 15 385 6 978 14 443 6 551 D1 F1 F2 17 537 7 955 16 187 7 342 D1 G1 G1 20 500 9 299 18 600 8 437 D1 G2 G2 21 065 9 555 19 107 8 667 D2 D3 D2 E2 15 570 7 062 14 562...

Страница 23: ...erEnd 36 914 mm OtherEnd 108 2743 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 24: ...erEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 25: ...EitherEnd 36 914 mm OtherEnd 108 2743 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact conf...

Страница 26: ...erEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 27: ...EitherEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact conf...

Страница 28: ...therEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact config...

Страница 29: ...530 microprocessor automatically acts to prevent unit shutdown due to abnormal operating conditions associated with low evaporator refrigerant temperature high condensing temperature and or motor curr...

Страница 30: ...RLC PRC020 EN 30 ConversionTable...

Страница 31: ...31 RLC PRC020 EN...

Страница 32: ...specifications without notice Literature Order Number File Number Supersedes Stocking Location Trane A business ofAmerican Standard Companies www trane com For more information contact your local sal...

Отзывы: