Specifications

General

Exposed metal surfaces are painted with
air-dry beige, direct-to-metal, single-
component paint. Each unit ships with full
operating charges of refrigerant and oil.
Molded neoprene isolation pads are
supplied for placement under all support
points. Startup and operator instruction
by factory-trained service personnel are
included.

Compressor and Motor

The unit is equipped with a semi-
hermetic, direct-drive, 3600-rpm (3000
rpm @ 50 Hz) rotary compressor that
includes a capacity control slide valve, oil
sump heater, and differential pressure
refrigerant oil flow system. Four
pressure-lubricated, rolling-element
bearing groups support the rotating
assembly.

The motor is a suction gas-cooled,
hermetically sealed, two-pole, squirrel
cage induction-type.

Unit-Mounted Starter

The unit is supplied with a NEMA 1 type
enclosure with top power-wiring access
and three-phase, solid state overload
protection. The starter is available in a
Wye-Delta configuration, factory-
mounted and fully pre-wired to the
compressor motor and control panel. A
factory-installed, factory-wired 600VA
control power transformer provides all
unit control power (120 VAC secondary)
and CH530 module power (24 VAC
secondary). Optional starter features
include circuit breakers, ground fault
circuit breakers, and mechanical, non-
fused disconnects.

Evaporator and Condenser

Shells are carbon steel plate. The
evaporator and condenser are designed,
tested, and stamped in accordance with
ASME Code for refrigerant-side/
working-side pressure of 200 psig.

All tube sheets are made of carbon steel;
tubes are mechanically expanded into
tube sheets and mechanically fastened to
tube supports. Evaporator tubes are 1.0-
inch (25.4 mm) diameter and condenser
tubes are 0.75-inch
(19.05 mm) diameter. Both types can be
individually replaced. Standard tubes are
externally finned, internally enhanced
seamless copper with lands at all tube
sheets.

All water pass arrangements are
available with grooved connections (150
or 300 psig waterside). All connections
may be either right- or left-handed.
Waterside shall be hydrostatically tested
at 1.5X design working pressure.

Refrigerant Circuit

An electronically controlled expansion
valve is provided to maintain proper
refrigerant flow.

Unit Controls (CH530)

The microprocessor-based control panel
is factory-installed and factory-tested. The
control system is powered by a control
power transformer, and will load and
unload the chiller through adjustment of
the compressor slide valve.
Microprocessor-based chilled water reset
based on return water is standard.

The CH530 microprocessor automatically
acts to prevent unit shutdown due to
abnormal operating conditions
associated with low evaporator
refrigerant temperature, high condensing
temperature, and/or motor current
overload. If an abnormal operating
condition continues and the protective
limit is reached, the machine should shut
down.

The panel includes machine protection
shutdown requiring 

manual reset for the

following conditions:
• low evaporator refrigerant temperature

and pressure

• high condenser refrigerant pressure
• low oil flow
• critical sensor or detection circuit faults
• motor current overload
• high compressor discharge temperature
• lost communication between modules
• electrical distribution faults: phase loss,

phase imbalance, or phase reversal

• external and local emergency stop
• starter transition failure

The panel also includes machine
protection shutdown with 

automatic

reset for the following correctable
conditions:
• momentary power loss
• under/over voltage
• loss of evaporator or condenser water

flow

When a fault is detected, the control
system conducts more than 100
diagnostic checks and displays results.

The display will identify the fault, indicate
date, time, and operating mode at time of
occurrence, and provide type of reset
required and a help message. The
diagnostic history will display the last ten
diagnostics with their times and dates of
occurrence.

Clear Language Display Panel

Factory-mounted to the control panel
door, the operator interface has an LCD
touch-screen display for operator input
and information output. This interface
provides access to the following
information: evaporator report,
condenser report, compressor report,
ASHRAE Guideline 3 report, operator
settings, service settings, service tests,
and diagnostics. All diagnostics and
messages are displayed in “clear
language.”

Data contained in available reports
includes:
• Water and air temperatures
• Refrigerant levels and temperatures
• Oil pressure
• Flow switch status
• EXV position
• Head pressure control command
• Compressor starts and run-time
• Line phase percent RLA, amps, and

volts

All necessary settings and setpoints are
programmed into the microprocessor-
based controller via the operator
interface. The controller is capable of
receiving signals contemporaneously
from a variety of control sources, in any
combination, and priority order of control
sources can be programmed. The control
source with priority determines active
setpoints via the signal it sends to the
control panel. Control sources may be:
• the local operator interface (standard)
• a hard-wired 4-20 mA or 2-10 VDC

signal from an external source
(interface optional; control source not
supplied)

• Generic BAS (optional points; control

source not supplied)

• LonTalk LCI-C (interface optional; control

source not supplied)

• Trane Tracer  Summit

 system (interface

optional)

Содержание RTHD

Страница 1: ...SeriesR HelicalRotary LiquidChillers Model RTHD 175 450T ons 60 Hz 125 450T ons 50 Hz Built for Industrial and Commercial Applications RLC PRC020 EN June 2006...

Страница 2: ...n via the LCD touch screen display freedom from interoperability concerns with LonMark communications job specific communication options that allow greater reporting flexibility Improved startup tempe...

Страница 3: ...ures and Benefits Options Controls Application Considerations Selection Procedure Model Nomenclature General Data Electrical Data and Connections Dimensions andWeights Mechanical Specifications Conver...

Страница 4: ...mal Storage Specifiers and operators benefit from dual setpoint control and industry leading temperature efficiency and control capabilities plus outstanding support through partnership with Calmac a...

Страница 5: ...rovides maximum efficiency high reliability and low maintenance requirements Electronic expansion valve with fewer moving parts than alternative valve designs offers highly reliable operation Suction...

Страница 6: ...2 4 and 203 2 mm sizes Nitrogen Charge Unit is shipped with a nitrogen holding charge in lieu of refrigerant Seal Kit for Reassembly Ideal for situations when the bolt together construction of the RTH...

Страница 7: ...ice making and daytime comfort cooling Options Programmable Relays Default set factory installed programmable relays allow the operator to select four relay outputs from a list of eight Available rel...

Страница 8: ...on including normal cooling and icemaking Water temperatures and setpoints Loading and limiting status and setpoints Average line current Outdoor air temperature Start stop differential timers Auto Ma...

Страница 9: ...ng In the event of a problem the operator receives an alarm notification and diagnostic message to aid in quick and accurate troubleshooting A snapshot report showing system status just prior to an em...

Страница 10: ...to obtain and maintain this differential at startup but for continuous operation a design should maintain a 25 F 13 9 C differential from evaporator leaving water temperature to condenser leaving wat...

Страница 11: ...s This ideal balance of design integrity with installation and operating cost considerations can also be obtained by consulting aTrane representative and applying theTrane System Analyzer program Wate...

Страница 12: ...developed using the most current standard fouling factors Part Load Performance Actual air conditioning system loads are frequently less than full load design conditions Depending on the number of ch...

Страница 13: ...Performance with Fluid Media OtherThanWater Series R chillers can be provided with a wide variety of fluid media other than water including ethylene glycol and propylene glycol in the evaporator conde...

Страница 14: ...C UL Digit 13 Pressure Vessel Code A ASME L Chinese Pressure Vessel Code Digit 14 Evaporator Frame B B Frame C C Frame D D Frame E E Frame F F Frame G G Frame Digit 15 Evaporator Capacity 1 Tube coun...

Страница 15: ...igit 43 Power Line Connection Type A Terminal Blocks B Mechanical Disconnect Switch D Circuit Breaker F High Interrupt Circuit Breaker H Ground Fault Circuit Breaker J Ground Fault High Interrupt Circ...

Страница 16: ...B2 B2 B2 45 170 29 110 HFC 134a 410 186 B2 C2 D2 58 220 34 129 HFC 134a 490 222 C1 D6 E5 45 170 29 110 HFC 134a 490 222 C1 D5 E4 52 197 32 121 HFC 134a 490 222 C1 E1 F1 82 310 60 226 HFC 134a 525 238...

Страница 17: ...114 200 17 76 200 D2 28 125 200 19 83 200 D3 31 134 200 20 89 200 D4 22 97 200 15 65 200 D5 22 97 200 15 65 200 D6 18 81 200 12 54 200 E1 28 125 200 19 83 200 F1 36 156 250 24 104 200 F2 38 168 250 2...

Страница 18: ...200 21 76 200 D2 34 125 200 23 83 200 D3 37 134 200 25 89 200 D4 27 97 200 18 65 200 D5 27 97 200 18 65 200 D6 22 81 200 15 54 200 E1 28 125 200 23 83 200 F1 43 156 250 29 104 200 F2 46 168 250 31 11...

Страница 19: ...ta 50 Hertz NominalVoltage 380 400 415 Compressor Voltage 342 360 374 Code Utilization Range 418 440 457 Max kW 139 145 148 B1 B2 RLA Max kW 233 233 233 LRA Y 391 412 428 LRAD 1229 1296 1348 Max kW 20...

Страница 20: ...RLC PRC020 EN 20 Electrical Data and Connections...

Страница 21: ...21 RLC PRC020 EN Electrical Data and Connections...

Страница 22: ...3 17 560 7 965 16 168 7 334 D1 D1 E1 15 385 6 978 14 443 6 551 D1 F1 F2 17 537 7 955 16 187 7 342 D1 G1 G1 20 500 9 299 18 600 8 437 D1 G2 G2 21 065 9 555 19 107 8 667 D2 D3 D2 E2 15 570 7 062 14 562...

Страница 23: ...erEnd 36 914 mm OtherEnd 108 2743 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 24: ...erEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 25: ...EitherEnd 36 914 mm OtherEnd 108 2743 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact conf...

Страница 26: ...erEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 27: ...EitherEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact conf...

Страница 28: ...therEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact config...

Страница 29: ...530 microprocessor automatically acts to prevent unit shutdown due to abnormal operating conditions associated with low evaporator refrigerant temperature high condensing temperature and or motor curr...

Страница 30: ...RLC PRC020 EN 30 ConversionTable...

Страница 31: ...31 RLC PRC020 EN...

Страница 32: ...specifications without notice Literature Order Number File Number Supersedes Stocking Location Trane A business ofAmerican Standard Companies www trane com For more information contact your local sal...

Отзывы: