Electrical Data Tables

Compressor motor electrical data is
provided in the data section for each
compressor size. Rated load amperes
(RLA), locked rotor wye amperes (LRA)
and expected inrush for the Wye-delta
and Solid State Starter configurations are
shown.

Although the terms “LRA” and “expected
inrush” are often used interchangeably,
the distinction applied here is that LRA is
the rated inrush for the motor, but
expected inrush is that allowed by the
starter, based on the specific
configuration.

Selecting starters in the Wye-delta or
Solid State configuration lowers
expected inrush vs. the Delta (or “across-
the-line”) configuration. A Solid State
Starter configuration lowers the
expected inrush by approximately 50
percent, while Wye-Delta lowers it by
approximately 66 percent.

The RLA is based on the motor’s
performance when reaching full rated
horsepower. The kW rating of the motor
will equal or exceed the kW requirement
indicated by the Series R computer
selection program at design conditions. If
motor kW draw at design conditions is
less than the kW rating of the motor, the
RLA at design conditions is determined
by multiplying the motor RLA (at the
desired voltage) by this ratio: design kW/
motor kW rating. This calculation is
performed within the Series R chiller
computer selection program, making
RLA available as part of the design
predictions. Predicted values include
power factor variation from point to point.

A voltage utilization range is tabulated for
each voltage listed. Series R chillers are
designed to operate satisfactorily over a
utilization range of ±10 percent of the
standard design voltages: (a) 200 V, 230 V,
380 V, 460 V, and 575 V for 60 Hertz, 3-
phase, and (b) 380 V, 400 V,
415 V for 50 Hertz, 3-phase.

Selection
Procedure

Unit Performance with Fluid Media
Other Than Water

Series R chillers can be provided with a
wide variety of fluid media other than
water, including ethylene glycol and
propylene glycol— in the evaporator,
condenser or both. Chillers using media
other than water are excluded from the
ARI 550/590-2003 Certification Program,
but are rated in accordance with ARI
Standard 550/590-2003. Trane factory
performance tests are only performed
with water as the cooling and heat-
rejection media. When considering
selection of media other than water,
contact the local Trane sales office for
chiller selections and factory
performance testing information.

Fluid media other than water lowers the
heat transfer coefficient, and therefore
reduces chiller performance. In general, it
is good practice to hold the percent glycol
added to within the minimum allowed by
the Trane selection program, based on
either (a) unit operating temperatures, or
(b) the operating temperatures the
evaporator or condenser water will
experience under its full range of
conditions. Adding more glycol than
required for the specific application is
equivalent to selecting a less efficient
chiller. Lower-viscosity glycols such as
ethylene will have less adverse impact
on chiller performance than higher-
viscosity glycols such as propylene.

Evaporator and Condenser Pressure
Drop

Pressure drop data is determined by the
Series R chiller computer selection
program available through local Trane
sales offices.

Dimensional Drawings

Dimensional drawings provided for
selection purposes illustrate overall
measurements of the unit. The
recommended service clearances are
those required to easily service the
Series R chiller.

All catalog dimensional drawings are
subject to change, and current submittal
drawings should be referenced for more
detailed dimensional information.
Dimensional drawings are also available
from the selection program. Contact the
local Trane sales office for submittal
information.

Содержание RTHD

Страница 1: ...SeriesR HelicalRotary LiquidChillers Model RTHD 175 450T ons 60 Hz 125 450T ons 50 Hz Built for Industrial and Commercial Applications RLC PRC020 EN June 2006...

Страница 2: ...n via the LCD touch screen display freedom from interoperability concerns with LonMark communications job specific communication options that allow greater reporting flexibility Improved startup tempe...

Страница 3: ...ures and Benefits Options Controls Application Considerations Selection Procedure Model Nomenclature General Data Electrical Data and Connections Dimensions andWeights Mechanical Specifications Conver...

Страница 4: ...mal Storage Specifiers and operators benefit from dual setpoint control and industry leading temperature efficiency and control capabilities plus outstanding support through partnership with Calmac a...

Страница 5: ...rovides maximum efficiency high reliability and low maintenance requirements Electronic expansion valve with fewer moving parts than alternative valve designs offers highly reliable operation Suction...

Страница 6: ...2 4 and 203 2 mm sizes Nitrogen Charge Unit is shipped with a nitrogen holding charge in lieu of refrigerant Seal Kit for Reassembly Ideal for situations when the bolt together construction of the RTH...

Страница 7: ...ice making and daytime comfort cooling Options Programmable Relays Default set factory installed programmable relays allow the operator to select four relay outputs from a list of eight Available rel...

Страница 8: ...on including normal cooling and icemaking Water temperatures and setpoints Loading and limiting status and setpoints Average line current Outdoor air temperature Start stop differential timers Auto Ma...

Страница 9: ...ng In the event of a problem the operator receives an alarm notification and diagnostic message to aid in quick and accurate troubleshooting A snapshot report showing system status just prior to an em...

Страница 10: ...to obtain and maintain this differential at startup but for continuous operation a design should maintain a 25 F 13 9 C differential from evaporator leaving water temperature to condenser leaving wat...

Страница 11: ...s This ideal balance of design integrity with installation and operating cost considerations can also be obtained by consulting aTrane representative and applying theTrane System Analyzer program Wate...

Страница 12: ...developed using the most current standard fouling factors Part Load Performance Actual air conditioning system loads are frequently less than full load design conditions Depending on the number of ch...

Страница 13: ...Performance with Fluid Media OtherThanWater Series R chillers can be provided with a wide variety of fluid media other than water including ethylene glycol and propylene glycol in the evaporator conde...

Страница 14: ...C UL Digit 13 Pressure Vessel Code A ASME L Chinese Pressure Vessel Code Digit 14 Evaporator Frame B B Frame C C Frame D D Frame E E Frame F F Frame G G Frame Digit 15 Evaporator Capacity 1 Tube coun...

Страница 15: ...igit 43 Power Line Connection Type A Terminal Blocks B Mechanical Disconnect Switch D Circuit Breaker F High Interrupt Circuit Breaker H Ground Fault Circuit Breaker J Ground Fault High Interrupt Circ...

Страница 16: ...B2 B2 B2 45 170 29 110 HFC 134a 410 186 B2 C2 D2 58 220 34 129 HFC 134a 490 222 C1 D6 E5 45 170 29 110 HFC 134a 490 222 C1 D5 E4 52 197 32 121 HFC 134a 490 222 C1 E1 F1 82 310 60 226 HFC 134a 525 238...

Страница 17: ...114 200 17 76 200 D2 28 125 200 19 83 200 D3 31 134 200 20 89 200 D4 22 97 200 15 65 200 D5 22 97 200 15 65 200 D6 18 81 200 12 54 200 E1 28 125 200 19 83 200 F1 36 156 250 24 104 200 F2 38 168 250 2...

Страница 18: ...200 21 76 200 D2 34 125 200 23 83 200 D3 37 134 200 25 89 200 D4 27 97 200 18 65 200 D5 27 97 200 18 65 200 D6 22 81 200 15 54 200 E1 28 125 200 23 83 200 F1 43 156 250 29 104 200 F2 46 168 250 31 11...

Страница 19: ...ta 50 Hertz NominalVoltage 380 400 415 Compressor Voltage 342 360 374 Code Utilization Range 418 440 457 Max kW 139 145 148 B1 B2 RLA Max kW 233 233 233 LRA Y 391 412 428 LRAD 1229 1296 1348 Max kW 20...

Страница 20: ...RLC PRC020 EN 20 Electrical Data and Connections...

Страница 21: ...21 RLC PRC020 EN Electrical Data and Connections...

Страница 22: ...3 17 560 7 965 16 168 7 334 D1 D1 E1 15 385 6 978 14 443 6 551 D1 F1 F2 17 537 7 955 16 187 7 342 D1 G1 G1 20 500 9 299 18 600 8 437 D1 G2 G2 21 065 9 555 19 107 8 667 D2 D3 D2 E2 15 570 7 062 14 562...

Страница 23: ...erEnd 36 914 mm OtherEnd 108 2743 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 24: ...erEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 25: ...EitherEnd 36 914 mm OtherEnd 108 2743 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact conf...

Страница 26: ...erEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 27: ...EitherEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact conf...

Страница 28: ...therEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact config...