General Data

Minimum/Maximum Evaporator Flow Rates (Gallons/Minute )

Two Pass

Three Pass

Four Pass

Evaporator

Nominal

Nominal

Nominal

Code

Min

Max

Conn Size (In.)

Min

Max Conn Size (In.)

Min

Max

Conn Size (In.)

B1

253

1104

8

168

736

6

—-

—-

—-

B2

288

1266

8

192

844

6

—-

—-

—-

C1

320

1412

8

213

941

6

—-

—-

—-

C2

347

1531

8

232

1022

6

—-

—-

—-

D1

415

1812

8

275

1206

8

—-

—-

—-

D2

450

1980

8

300

1320

8

—-

—-

—-

D3

486

2131

8

324

1417

8

—-

—-

—-

D4

351

1542

8

234

1028

8

—-

—-

—-

D5

351

1542

8

234

1028

8

—-

—-

—-

D6

293

1287

8

196

860

8

—-

—-

—-

E1

450

1980

8

300

1320

8

—-

—-

—-

F1

563

2478

10

376

1655

8

—-

—-

—-

F2

604

2667

10

404

1780

8

—-

—-

—-

G1

—-

—-

—-

505

2218

10

379

1666

8

G2

—-

—-

—-

550

2413

10

411

1807

8

G3

—-

—-

—-

622

2732

10

466

2050

8

Notes:
1.  Minimum flow rates are based on 

water only

.

2.  All water connections are grooved pipe.

Minimum/Maximum Evaporator Flow Rates (Liters/Second)

Two Pass

Three Pass

Four Pass

Evaporator

Nominal

Nominal

Nominal

Code

Min

Max

Conn Size (mm)

Min

Max Conn Size (mm)

Min

Max

Conn Size (mm)

B1

16

70

200

11

46

150

—-

—-

—-

B2

18

80

200

12

53

150

—-

—-

—-

C1

20

89

200

13

59

150

—-

—-

—-

C2

22

97

200

15

65

150

—-

—-

—-

D1

26

114

200

17

76

200

—-

—-

—-

D2

28

125

200

19

83

200

—-

—-

—-

D3

31

134

200

20

89

200

—-

—-

—-

D4

22

97

200

15

65

200

—-

—-

—-

D5

22

97

200

15

65

200

—-

—-

—-

D6

18

81

200

12

54

200

—-

—-

—-

E1

28

125

200

19

83

200

—-

—-

—-

F1

36

156

250

24

104

200

—-

—-

—-

F2

38

168

250

25

112

200

—-

—-

—-

G1

—-

—-

—-

32

140

250

24

105

200

G2

—-

—-

—-

35

152

250

26

114

200

G3

—-

—-

—-

39

172

250

29

129

200

Notes:
1.  Minimum flow rates are based on 

water only

.

2.  All water connections are grooved pipe.

Minimum/Maximum Condenser Flow Rates
(Gallons/Minute)

Two Pass

Condenser

Nominal

Code

Min

Max

Conn Size (In.)

B1

193

850

6

B2

212

935

6

D1

193

850

6

D2

212

935

6

E1

291

1280

8

E2

316

1390

8

E3

325

1420

8

E4

245

1080

8

E5

206

910

8

F1

375

1650

8

F2

355

1560

8

F3

385

1700

8

G1

444

1960

8

G2

535

2360

8

G3

589

2600

8

Notes:
1.  Minimum flow rates are based on 

water only

.

2.  All water connections are grooved pipe.

Minimum/Maximum Condenser Flow Rates
 (Liters/Second)

Two Pass

Condenser

Nominal

Code

Min

Max

Conn Size (mm)

B1

12

54

150

B2

13

59

150

D1

12

54

150

D2

13

59

150

E1

18

81

200

E2

20

88

200

E3

21

90

200

E4

15

68

200

E5

13

57

200

F1

24

104

200

F2

22

98

200

F3

24

107

200

G1

28

124

200

G2

34

149

200

G3

37

164

200

Notes:
1.  Minimum flow rates are based on 

water only

.

2.  All water connections are grooved pipe.

Water Flow Rates

Содержание RTHD

Страница 1: ...SeriesR HelicalRotary LiquidChillers Model RTHD 175 450T ons 60 Hz 125 450T ons 50 Hz Built for Industrial and Commercial Applications RLC PRC020 EN June 2006...

Страница 2: ...n via the LCD touch screen display freedom from interoperability concerns with LonMark communications job specific communication options that allow greater reporting flexibility Improved startup tempe...

Страница 3: ...ures and Benefits Options Controls Application Considerations Selection Procedure Model Nomenclature General Data Electrical Data and Connections Dimensions andWeights Mechanical Specifications Conver...

Страница 4: ...mal Storage Specifiers and operators benefit from dual setpoint control and industry leading temperature efficiency and control capabilities plus outstanding support through partnership with Calmac a...

Страница 5: ...rovides maximum efficiency high reliability and low maintenance requirements Electronic expansion valve with fewer moving parts than alternative valve designs offers highly reliable operation Suction...

Страница 6: ...2 4 and 203 2 mm sizes Nitrogen Charge Unit is shipped with a nitrogen holding charge in lieu of refrigerant Seal Kit for Reassembly Ideal for situations when the bolt together construction of the RTH...

Страница 7: ...ice making and daytime comfort cooling Options Programmable Relays Default set factory installed programmable relays allow the operator to select four relay outputs from a list of eight Available rel...

Страница 8: ...on including normal cooling and icemaking Water temperatures and setpoints Loading and limiting status and setpoints Average line current Outdoor air temperature Start stop differential timers Auto Ma...

Страница 9: ...ng In the event of a problem the operator receives an alarm notification and diagnostic message to aid in quick and accurate troubleshooting A snapshot report showing system status just prior to an em...

Страница 10: ...to obtain and maintain this differential at startup but for continuous operation a design should maintain a 25 F 13 9 C differential from evaporator leaving water temperature to condenser leaving wat...

Страница 11: ...s This ideal balance of design integrity with installation and operating cost considerations can also be obtained by consulting aTrane representative and applying theTrane System Analyzer program Wate...

Страница 12: ...developed using the most current standard fouling factors Part Load Performance Actual air conditioning system loads are frequently less than full load design conditions Depending on the number of ch...

Страница 13: ...Performance with Fluid Media OtherThanWater Series R chillers can be provided with a wide variety of fluid media other than water including ethylene glycol and propylene glycol in the evaporator conde...

Страница 14: ...C UL Digit 13 Pressure Vessel Code A ASME L Chinese Pressure Vessel Code Digit 14 Evaporator Frame B B Frame C C Frame D D Frame E E Frame F F Frame G G Frame Digit 15 Evaporator Capacity 1 Tube coun...

Страница 15: ...igit 43 Power Line Connection Type A Terminal Blocks B Mechanical Disconnect Switch D Circuit Breaker F High Interrupt Circuit Breaker H Ground Fault Circuit Breaker J Ground Fault High Interrupt Circ...

Страница 16: ...B2 B2 B2 45 170 29 110 HFC 134a 410 186 B2 C2 D2 58 220 34 129 HFC 134a 490 222 C1 D6 E5 45 170 29 110 HFC 134a 490 222 C1 D5 E4 52 197 32 121 HFC 134a 490 222 C1 E1 F1 82 310 60 226 HFC 134a 525 238...

Страница 17: ...114 200 17 76 200 D2 28 125 200 19 83 200 D3 31 134 200 20 89 200 D4 22 97 200 15 65 200 D5 22 97 200 15 65 200 D6 18 81 200 12 54 200 E1 28 125 200 19 83 200 F1 36 156 250 24 104 200 F2 38 168 250 2...

Страница 18: ...200 21 76 200 D2 34 125 200 23 83 200 D3 37 134 200 25 89 200 D4 27 97 200 18 65 200 D5 27 97 200 18 65 200 D6 22 81 200 15 54 200 E1 28 125 200 23 83 200 F1 43 156 250 29 104 200 F2 46 168 250 31 11...

Страница 19: ...ta 50 Hertz NominalVoltage 380 400 415 Compressor Voltage 342 360 374 Code Utilization Range 418 440 457 Max kW 139 145 148 B1 B2 RLA Max kW 233 233 233 LRA Y 391 412 428 LRAD 1229 1296 1348 Max kW 20...

Страница 20: ...RLC PRC020 EN 20 Electrical Data and Connections...

Страница 21: ...21 RLC PRC020 EN Electrical Data and Connections...

Страница 22: ...3 17 560 7 965 16 168 7 334 D1 D1 E1 15 385 6 978 14 443 6 551 D1 F1 F2 17 537 7 955 16 187 7 342 D1 G1 G1 20 500 9 299 18 600 8 437 D1 G2 G2 21 065 9 555 19 107 8 667 D2 D3 D2 E2 15 570 7 062 14 562...

Страница 23: ...erEnd 36 914 mm OtherEnd 108 2743 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 24: ...erEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 25: ...EitherEnd 36 914 mm OtherEnd 108 2743 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact conf...

Страница 26: ...erEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact configur...

Страница 27: ...EitherEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact conf...

Страница 28: ...therEnd 36 914 mm OtherEnd 126 3200 mm T op 36 914 mm Clearance for tube removal Note 1 Dimensions are based on 3 Pass Evap 2 Pass Cond and LH LH water connections Refer to submittals for exact config...

Страница 29: ...530 microprocessor automatically acts to prevent unit shutdown due to abnormal operating conditions associated with low evaporator refrigerant temperature high condensing temperature and or motor curr...

Страница 30: ...RLC PRC020 EN 30 ConversionTable...

Страница 31: ...31 RLC PRC020 EN...

Страница 32: ...specifications without notice Literature Order Number File Number Supersedes Stocking Location Trane A business ofAmerican Standard Companies www trane com For more information contact your local sal...

Отзывы: