Diagnostics
90
RTAF-SVX001K-EN
Pumpdown Terminated By Time
Circuit
Info
Latch
Service
Pumpdown
Service Pumpdown cycle for this circuit
was terminated abnormally due to
excessive time (RTAF max Service
Pumpdown = 4 min.).
Local
Restart Inhibit Invoked - xy
Restart Inhibit xy
Cprsr
Info
Latch
All
When restart inhibit warning is enabled,
the warning exists when unit has been
inhibited from starting and is cleared when
a start of a compressor is possible (Start-
to-Start Timer expires)
Remote
Software Error 1001: Call Trane Service
SW Error 1001-Call Trane
All
functions
Immediate Latch
All
A high level software watchdog has
detected a condition in which there was a
continuous 1 minute period of compressor
operation, with neither Evaporator water
flow nor a” contactor interrupt failure”
diagnostic active. The presence of this
software error message suggests an
internal software problem has been
detected. The events that led up to this
failure, if known, should be recorded and
transmitted to Trane Controls Engineering.
Local
Software Error 1002: Call Trane Service
SW Error 1002-Call Trane
All
functions
Immediate Latch
All
Reported if state chart misalignment in
stopped or inactive state occurred while a
compressor was seen to be operating and
this condition lasted for at least 1 minute
(cmprsr operation due to Service
Pumpdown or with Contactor Interrupt
Failure diagnostic is excluded). The
presence of this software error message
suggests an internal software problem has
been detected. The events that led up to
this failure, if known, should be recorded
and transmitted to Trane Controls
Engineering.
Local
Software Error 1003: Call Trane Service
SW Error 1003-Call Trane
All
functions Immediate Latch
All
Reported if state chart misalignment
occurred inferred from the Capacity
Control, Circuit, or Compressor State
Machines remaining in the Stopping state
for more than 3 minutes. The presence of
this software error message suggests an
internal software problem has been
detected. The events that led up to this
failure, if known, should be recorded and
transmitted to Trane Controls Engineering.
Local
Starts/Hours Modified
Starts/Hours Modified
Cprsr
Info
NonLatch
All
The current value for the cumulative starts
and or hours for the given compressor
have been modified by a write override
from TU.
Remote
Suction Refrigerant Pressure Sensor - xy
Suction Pressure Sensor - xy
Cprsr
Immediate
Latch
All
Bad Sensor or LLID
Remote
Unexpected Starter Shutdown - xy
Unexpected Starter Shtdn - xy
Cprsr
Normal
NonLatch
All Cprsr
Running
modes,
Starting,
Running and
Preparing to
Shutdown
The Starter module status reported back
that it is stopped when the MP thinks it
should be running and no Starter
diagnostic exist. This diagnostic will be
logged in the active buffer and then
automatically cleared. This diagnostic
could be caused by intermittent
communication problems from the Starter
to the MP, or due to mis-binding
Local
Table 33. Main processor diagnostics (continued)
Diagnostic Name
Affects
Target
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level