Diagnostics
RTAF-SVX001K-EN
81
Transition Complete Input
Shorted - xy
(Trnsn Compl Input Short xy)
Cprsr
Immediate
Latch
Pre-Start
The Transition Complete input was found to be
shorted before the compressor was started. This
is active for all electromechanical starters.
Local
Under Voltage
Chiller
Normal
NonLatch
Pre-Start and
Any Ckt(s)
Energzd
Nom. trip: 60 seconds at less than 87.5%, ? 2.8%
at 200V ? 1.8% at 575V, Auto Reset at 90% or
greater for 10 cont secs.
Remote
Table 32. Starter diagnostics (continued)
Diagnostic Name and
Source
Affects
Target
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level