Diagnostics
RTAF-SVX001K-EN
89
Low Oil Flow - xy
Cprsr
Immediate
Latch
Cprsr
Energized and
Delta P above
15 Psid
The intermediate oil pressure sensor for
this compressor was out of the acceptable
pressure range for 15 seconds, while the
Delta Pressure was greater than 15 Psid
(172.4 kPa).: Acceptable range is 0.50 >
(PC-PI) / (PC-PE) for the first 2.5 minutes
of operation, and 0.28 > (PC-PI) / (PC-PE)
thereafter.
Local
Low Refrigerant Temperature
Circuit Immediate
Latch
All Ckt Running
Modes
The respective Evaporator Refrigerant Pool
Temperature dropped below the Low
Refrigerant Temperature Cutout Setpoint
for 2250°F-sec (12°F-sec max rate for
early circuit startup period) while the
circuit was running. The minimum LRTC
setpoint is -5°F (18.7 Psia) the point at
which oil separates from the refrigerant.
The integral is held nonvolatile though
power down, is continuously calculated,
and can decay or build during the circuit off
cycle as conditions warrant.
Remote
Low Suction Refrigerant Pressure
Low Suction Rfgt Pressure
Low Suction Rfgt Pressure
Circuit Immediate
Latch
Cprsr Prestart
and Cprsr
Energized
a. The Suction Pressure dropped below 10
Psia just prior to compressor start (after
EXV preposition). b. During Early Startup
Period: the Suction Pressure fell below a
pressure equal to Condenser Pressure ÷ 8
but as limited to not less than 6 or greater
than10 psia. c. After Early Startup Period
expires: The Suction Pressure fell below 16
Psia.
(Note: the Early Startup Period is between
1 and 5 min as an inverse function of the
Cond Temp measured at time of circuit
startup).
Local
Mfr Maintenance Recommended - xy
Maint Recommended xy
Cprsr
Info
Latch
Service
Messages
Enabled
Compressor service recommended as
service interval hours have elapsed.
Remote
MP: Invalid Configuration
Platform Immediate
Latch
All
MP has an invalid configuration based on
the current software installed.
Remote
MP: Reset Has Occurred
None
Info
Latch
All
The main processor has successfully come
out of a reset and built its application. A
reset may have been due to a power up,
installing new software or configuration.
This diagnostic is immediately and
automatically cleared and thus can only be
seen in the Historic Diagnostic List in
Tracer TU.
Remote
No Differential Refrigerant Pressure - xy
No Differential Rfgt Pressure - xy
No Diff Rfgt Press - xy
Cprsr
Immediate
Latch
Compressor
running on
Circuit
The system differential pressure was
below 7.7 Psid (53 kPa) for 6 seconds after
the 11 seconds ignore time relative to
cprsr/circuit startup had expired. In a two
compressor circuit, the lower of the two
suction pressures is used for DP.
Remote
Oil Flow Protection Fault xy
Cprsr
Immediate
Latch
Starter
Contactor
Energized [all
Stop modes]
The Intermediate Oil Pressure Sensor for
this cprsr is reading a pressure either
above its respective circuit’s Condenser
Pressure by 15 Psia or more, or below its
respective Suction Pressure 10 Psia or
more for 30 seconds continuously.
Local
Oil Pressure Sensor - xy
Cprsr
Immediate
Latch
All
Bad Sensor or LLID
Remote
Oil Temperature Sensor - xy
Oil Temp Sensor - xy
Cprsr
Normal
Latch
All
Bad Sensor or LLID
Remote
Outdoor Air Temperature Sensor
Outdoor Air Temp Sensor
Chiller
Normal
Latch
All
Bad Sensor or LLID.
Remote
Table 33. Main processor diagnostics (continued)
Diagnostic Name
Affects
Target
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level