Installation Mechanical
22
RTAF-SVX001K-EN
Figure 10.
Mounting point locations
(a)
(a) Quantity of mounting points and isolators varies with unit.
See submittal for actual number required for specific unit size.
Control panel 2 is only present on 280 to 520 ton units.
1
3
5
7
2
4
6
8
Control P
anel 1
9
11
10
12
Control P
anel 2
Table 10. Isolator locations, I-P units (in)
(a)
Unit Size
(tons)
Location
1
2
3
4
5
6
7
8
9
10
11
12
115
22.8
22.8
100.4
100.4
198.8
198.8
-
-
-
-
-
-
130
22.8
22.8
100.4
100.4
198.8
198.8
-
-
-
-
-
-
150
22.8
22.8
138.9
138.9
243.1
243.1
-
-
-
-
-
-
170
22.8
22.8
138.9
138.9
243.1
243.1
-
-
-
-
-
-
180
22.8
22.8
138.9
138.9
243.1
243.1
-
-
-
-
-
-
200
22.8
22.8
105.4
105.4
204.7
204.7
287.5
287.5
-
-
-
-
215
22.8
22.8
105.4
105.4
204.7
204.7
287.5
287.5
-
-
-
-
230
22.8
22.8
105.4
105.4
204.7
204.7
287.4
287.4
-
-
-
-
250/270
22.8
22.8
105.4
105.4
204.7
204.7
287.4
287.4
-
-
-
-
280
18.8
18.8
129.1
129.1
269.6
269.6
379.8
379.8
-
-
-
-
310
18.8
18.8
129.1
129.1
239.3
239.3
313.9
313.9
424.1
424.1
-
-
350/390
18.8
18.8
129.1
129.1
239.3
239.3
313.9
313.9
424.1
424.1
-
-
410
18.8
18.8
129.1
129.1
239.3
239.3
402.6
402.6
512.8
512.8
-
-
450
60.2
40.1
142.1
129.1
223.6
239.3
334.6
323.9
442.0
445.8
540.4
548.1
500/520
60.2
40.1
142.1
129.1
223.6
239.3
334.6
323.9
442.0
445.8
540.4
548.1
(a) Dimensions are referenced from end of the unit on the circuit 1 control panel side (not including control panel itself).
Table 11. Isolator locations, SI units (mm)
(a)
Unit Size
(tons)
Location
1
2
3
4
5
6
7
8
9
10
11
12
115
578
578
2550
2550
5050
5050
-
-
-
-
-
-
130
578
578
2550
2550
5050
5050
-
-
-
-
-
-
150
578
578
3528
3528
6174
6174
-
-
-
-
-
-
170
578
578
3528
3528
6174
6174
-
-
-
-
-
-
180
578
578
3528
3528
6174
6174
-
-
-
-
-
-
200
578
578
2678
2678
5199
5199
7302
7302
-
-
-
-
215
578
578
2678
2678
5199
5199
7302
7302
-
-
-
-
230
578
578
2678
2678
5199
5199
7299
7299
-
-
-
-
250/270
578
578
2678
2678
5199
5199
7299
7299
-
-
-
-
280
478
478
3278
3278
6848
6848
9648
9648
-
-
-
-
310
478
478
3278
3278
6078
6078
7973
7973
10773
10773
-
-
350/390
478
478
3278
3278
6078
6078
7973
7973
10773
10773
-
-
410
478
478
3278
3278
6078
6078
10225
10225
13025
13025
-
-
450
1529
1018
3609
3278
5679
6078
8500
8228
11226
11324
13726
13923
500/520
1529
1018
3609
3278
5679
6078
8500
8228
11226
11324
13726
13923
(a) Dimensions are referenced from end of the unit on the circuit 1 control panel side (not including control panel itself).