background image

RT-SVX39B-EN

General Information

Unit Nameplate

A Mylar unit nameplate is located on the unit’s corner 
support next to the filter access panel. It includes the unit 
model number, serial number, electrical characteristics, 
refrigerant charge, as well as other pertinent unit data.

Compressor Nameplate

The nameplate for the compressors are located on the side 
of the compressor.

Unit Description

Before shipment, each unit is leak tested, dehydrated, 
charged with refrigerant and compressor oil, and run 
tested for proper control operation.

The condenser coils are aluminum fin, mechanically 
bonded to copper tubing.

Direct-drive, vertical discharge condenser fans are 
provided with built-in thermal overload protection.

The ReliaTel™ Control Module is a microelectronic control 
system that is referred to as “Refrigeration Module” 
(RTRM). The acronym RTRM is used extensively 
throughout this document when referring to the control 
system network.

These modules through Proportional/Integral control 
algorithms perform specific unit functions that governs 
unit operation in response to; zone temperature, supply air 
temperature, and/or humidity conditions depending on 
the application. The stages of capacity control for these 
units is achieved by starting and stopping the 
compressors.

The RTRM is mounted in the control panel and is factory 
wired to the respective internal components. The RTRM 
receives and interpret information from other unit 
modules, sensors, remote panels, and customer binary 
contacts to satisfy the applicable request for cooling.

Economizer Control Actuator (Optional) 

The ECA monitors the mixed air temperature, return air 
temperature, minimum position setpoint (local or 
remote), power exhaust setpoint, CO

2

 setpoint, CO

2

, and 

ambient dry bulb/enthalpy sensor or comparative 
humidity (return air humidity against ambient humidity) 
sensors, if selected, to control dampers to an accuracy of 
+/- 5% of stroke. The actuator is spring returned to the 
closed position any time that power is lost to the unit. It is 
capable of delivering up to 25 inch pounds of torque and 
is powered by 24 VAC.

RTCI - ReliaTel™ Trane Communication 
Interface (Optional)

This module is used when the application calls for an 
ICSTM building management type control system. It 
allows the control and monitoring of the system through 
an ICS panel. The module can be ordered from the factory 
or ordered as a kit to be field installed. Follow the 
installation instruction that ships with each kit when field 
installation is necessary.

RLCI - ReliaTel™ LonTalk Communication 
Interface (Optional)

This module is used when the application calls for an 
ICSTM building management type control system that is 
LonTalk. It allows the control and monitoring of the system 
through an ICS panel. The module can be ordered from the 
factory or ordered as a kit to be field installed. Follow the 
installation instruction that ships with each kit when field 
installation is necessary.

RBCI - ReliaTel BACnet Communications 
Interface (Optional)

This module is used when the application calls for an open 
BACnet protocol. It allows the control and monitoring of 
the system through an ICS panel. The module can be 
ordered from the factory or as a kit to be field installed. 
Follow the installation instructions that ships with each kit 
when field installation is necessary.

RTOM – ReliaTel™ Options Module

The RTOM monitors the supply fan proving, clogged filter, 
supply air temperature, exhaust fan setpoint, supply air 
tempering, Frostat™ and smoke detector. Refer to system 
input devices and functions for operation. 

This module is standard on 10 ton products.

System Input Devices & 
Functions

The RTRM must have a zone sensor or thermostat input in 
order to operate the rooftop unit. The flexibility of having 
several mode capabilities depends upon the type of zone 
sensor thermostat selected to interface with the RTRM. 

The descriptions of the following basic Input Devices used 
within the RTRM network are to acquaint the operator with 
their function as they interface with the various modules. 
Refer to the unit’s electrical schematic for the specific 
module connections.

The following controls are available from the factory for 
field installation.

Содержание Precedent WSC060ED

Страница 1: ...ining Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...responsible management of refrigerants Know the applicable laws and follow them Revision Summary RT SVX39B EN 11 September 2012 MERV 8 filter with filter removal tool Stainless steel drain pan condens...

Страница 3: ...nstalled Power Wiring 22 Main Unit Power Standard Wiring 22 Field Installed Control Wiring 22 Controls using 24 VAC 23 Controls using DC Analog Input Outputs Standard Low Voltage Multiconductor Wire 2...

Страница 4: ...Digital Zone Sensor Test 39 Unit Economizer Control ECA Trouble shooting ReliaTel Control 40 Wiring Diagrams 41 Limited Warranty 42 Heat Pump WCC WCD WCH WCM and WSC Parts Only 42 Heat Pump WCZ WCY W...

Страница 5: ...connect6 2 Unit Mounted Circuit Breaker6 Digit 20 Convenience Outlet 0 No Convenience Outlet A Unpowered Convenience Outlet B Powered Convenience Outlet three phase only 7 Digit 21 Communications Opti...

Страница 6: ...rcuit breaker options 7 Requires use of Disconnect or Circuit Breaker 8 Standard metering devices are TXVs 9 The return air smoke detector may notfit upor workproperly on the Precedent units when used...

Страница 7: ...the unit It is capable of delivering up to 25 inch pounds of torque and is powered by 24 VAC RTCI ReliaTel Trane Communication Interface Optional This module is used when the application calls for an...

Страница 8: ...ed the compressor will not be allowed to operate Anytime this circuit is opened for 1 continuous second during compressor operation the compressor for that circuit is immediately turned Off The compre...

Страница 9: ...to a BAYSENS119 remote panel wiring must be 18 AWG shielded twisted pair Belden 8760 or equivalent Refer to the specific remote panel for wiring details Wireless Zone Sensor BAYSENS050 This electronic...

Страница 10: ...10 RT SVX39B EN Unit Clearances Figure 1 Typical installation clearances for single multiple unit applications WSC060E unit WSC072 120E units...

Страница 11: ...es RT SVX39B EN 11 Figure 2 Heat pump 5 ton Note All dimensions are in inches millimeters Figure 3 Heat pump 5 ton unit clearance and roof opening Note All dimensions are in inches millimeters CLEARAN...

Страница 12: ...Unit Clearances 12 RT SVX39B EN Figure 4 Heat pump 5 ton roof curb Note All dimensions are in inches millimeters Figure 5 Heat pumps 6 7 tons Note All dimensions are in inches millimeters...

Страница 13: ...Clearances RT SVX39B EN 13 Figure 6 Heat pump 10 ton Note All dimensions are in inches millimeters Figure 7 Heat pump 6 10 ton unit clearance and roof opening Note All dimensions are in inches millime...

Страница 14: ...Unit Clearances 14 RT SVX39B EN Figure 8 Heat pump 6 10 ton roof curb Note All dimensions are in inches millimeters 2130 MM 356 MM...

Страница 15: ...he consignee Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur after delivery No...

Страница 16: ...f gravity dimensions in mm Tons Unit Model No Maximum Model Weights a lbs kgs Corner Weights b Center of Gravity in mm Shipping Net A B C D Length Width 5 WSC060ED 667 304 562 256 169 77 140 64 96 44...

Страница 17: ...air openings as viewed form the rear of the unit Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence andto reduce static pressure When attaching the ductwor...

Страница 18: ...rb ductwork must be fabricated and installed by the installing contractor before the unit is set into place Note For sound consideration cut only the holes in the roof deck for the ductwork penetratio...

Страница 19: ...the unit for shipping damage and material shortage file a freight claim and notify appropriate sales representative Verify correct model options and voltage from unit nameplate Verify that the install...

Страница 20: ...he outward edge of each duct cover with 2 screws 5 Slide RETURN DUCT COVER insulation side up into supply opening until inward edge of duct cover engages with the 2 retaining clips on the duct flange...

Страница 21: ...ccess panel and supply air access panels 2 Remove the support panel that the condensate drain pan exits through 3 Slide the condensate drain pan out of the unit 4 Place on a level surface in the posit...

Страница 22: ...dard Wiring 1 Location of the applicable electrical service entrance is illustrated in Unit Clearances p 10 Complete the unit s power wiring connections at Compressor Contactor 1 CC1 inside the unit c...

Страница 23: ...etween the unit and components utilizing a DC analog input output signal refer to Unit Clearances p 10 for the electrical access locations provided on the unit 1 Table 4 lists the conductor sizing gui...

Страница 24: ...Installation 24 RT SVX39B EN Figure 24 ReliaTel refrigeration module Figure 25 Customer control low voltage routing...

Страница 25: ...rature averaging Example 1 illustrates two series circuits with two sensors in each circuit wired in parallel The square of any number of remote sensors is required Example 2 illustratesthreesensorssq...

Страница 26: ...27 Typical field wiring diagrams for optional controls BAYSENS119 ASYSTAT777 Zone Sensor BAYSENS077 ASYSTAT111 BAYSENS107 BAYSENS073 Zone Sensor BAYSENS077 ASYSTAT111 BAYSENS109 BAYSENS074 Zone Sensor...

Страница 27: ...ing that deviates the farthest from the average voltage Example If the voltage readings of the supply power measured 221 230 and 227 the average volts would be VD reading farthest from average 221 The...

Страница 28: ...Upon power initialization the RTRM performs self diagnostic checks to insure that all internal controls are functional It also checks the configuration parameters against the components connected to...

Страница 29: ...t will automatically revert to the applied System control method For unit test steps test modes and step resistance values to cycle the various components refer to Table 6 p 30 ReliaTel Controls Upon...

Страница 30: ...y adjustment set screw and turn sheave clockwise To decrease fan RPM loosen the pulley adjustment set screw and turn sheave counterclockwise If the required CFM is too high external static pressure is...

Страница 31: ...nded period 15 to 30 minutes the motor winding can overheat and cause the motor winding thermostat to open 3 After the compressor and condenser fan have started and operated for approximately 30 minut...

Страница 32: ...e amount of belt deflection that corresponds to the proper belt tension 2 Set the large O ring on the belt tension gauge at the deflection value determined in Step 1b 3 Set the small O ring at zero on...

Страница 33: ...all P D Range Super Gripbelts Gripnotch Steel Cable Gripbelts Min Max Min Max Min Max A 3 0 3 6 3 4 1 2 3 7 8 5 1 2 3 1 4 4 3 8 4 8 3 1 2 5 4 1 2 6 1 4 3 3 4 4 3 4 5 0 7 0 4 5 1 2 5 6 7 8 4 1 4 5 1 4...

Отзывы: