General Information

8

 RT-SVX39B-EN

Supply Fan Failure Input (Optional)

The Fan Failure Switch can be connected to sense indoor 
fan operation:

FFS (Fan Failure Switch) If air flow through the unit is not 
proven by the differential pressure switch connected to the 
RTRM (factory set point 0.07 “w.c.) within 40 seconds 
nominally, the RTRM will shut off all mechanical 
operations, lock the system out, send a diagnostic to ICS, 
and the SERVICE output will flash. The system will remain 
locked out until a reset is initiated either manually or 
through ICS.

Clogged Filter Switch (Optional)

The unit mounted clogged filter switch monitors the 
pressure differential across the return air filters. It is 
mounted in the filter section and is connected to the 
RTOM. A diagnostic SERVICE signal is sent to the remote 
panel if the pressure differential across the filters is at least 
0.5" w.c. The contacts will automatically open when the 
pressure differential across the filters decreases to 
approximately 0.4" w.c. The clogged filter output is 
energized when the supply fan is operating and the 
clogged filter switch has been closed for at least 2 minutes. 
The system will continue to operate regardless of the 
status of the filter switch.

Note:

On units equipped with factory installed MERV 13 
filters, a clogged filter switch with different 
pressure settings will be installed. This switch will 
close when the differential pressure is 
approximately 0.8' w.c. and open when the 
differential falls to 0.7" w.c.

Condensate Drain Pan Overflow Switch 
(Optional)

ReliaTel Option

This input incorporates the Condensate Overflow Switch 
(COF) mounted on the drain pan and the ReliaTel Options 
Module (RTOM). When the condensate level reaches the 
trip point for 6 continuous seconds, the RTOM will shut 
down all unit functions until the overflow condition has 
cleared. The unit will return to normal operation after 6 
continuous seconds with the COF in a non-tripped 
condition. If the condensate level causes unit shutdown 
more than 2 times in a 3 days period, the unit will be 
locked-out of operation requiring manual reset of 
diagnostic system through Zone Sensor or Building 
Automation System (BAS). Cycling unit power will also 
clear the fault.

Compressor Disable (CPR1/2)

This input incorporates the low pressure control (LPC) of 
each refrigeration circuit and can be activated by opening 
a field supplied contact installed on the LTB. 

If this circuit is open before the compressor is started, the 
compressor will not be allowed to operate. Anytime this 
circuit is opened for 1 continuous second during 
compressor operation, the compressor for that circuit is 

immediately turned “Off”. The compressor will not be 
allowed to restart for a minimum of 3 minutes should the 
contacts close.

If four consecutive open conditions occur during the first 
three minutes of operation, the compressor for that circuit 
will be locked out, a diagnostic communicated to the 
remote panel (if installed), and a manual reset will be 
required to restart the compressor.

Low Pressure Control

When the LPC is opened for 1 continuous second, the 
compressor for that circuit is turned off immediately. The 
compressor will not be allowed to restart for a minimum 
of 3 minutes.

If four consecutive open conditions occur during an active 
call for cooling, the compressor will be locked out, a 
diagnostic communicated to ICS™, if applicable, and a 
manual reset required to restart the compressor. On dual 
compressor units only the affected compressor circuit is 
locked out.

High Pressure Control 

The high pressure controls are wired in series between the 
compressor outputs on the RTRM and the compressor 
contactor coils. If the high pressure control switch opens, 
the RTRM senses a lack of current while calling for cooling 
and locks the compressor out.

If four consecutive open conditions occur during an active 
call for cooling, the compressor will be locked out, a 
diagnostic communicated to ICS™, if applicable, and a 
manual reset required to restart the compressor. On dual 
compressor units only the affected compressor circuit is 
locked out.

Lead/Lag Control (Dual Circuit Only)

Lead/Lag is a selectable input located on the RTRM. The 
RTRM is configured from the factory with the Lead/Lag 
control disabled. To activate the Lead/Lag function, simply 
cut the wire connected to J3-8 at the RTRM. When it is 
activated, each time the designated lead compressor is 
shut off due to the load being satisfied, the lead 
compressor or refrigeration circuit switches. When the 
RTRM is powered up, i.e. after a power failure, the control 
will default to the number one circuit compressor.

Zone Sensor Module (ZSM) (BAYSENS107*)

This electronic sensor features three system switch 
settings (Heat, Cool, and Off) and two fan settings (On and 
Auto). It is a manual changeover control with single 
setpoint. (Cooling Setpoint Only)

Zone Sensor Module (ZSM) (BAYSENS109*)

This electronic sensor features four system switch settings 
(Heat, Cool, Auto, and Off) and two fan settings (On and 
Auto). It is a manual or auto changeover control with dual 
setpoint capability. It can be used with a remote zone 
temperature sensor BAYSENS077*.

Содержание Precedent WSC060ED

Страница 1: ...ining Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...responsible management of refrigerants Know the applicable laws and follow them Revision Summary RT SVX39B EN 11 September 2012 MERV 8 filter with filter removal tool Stainless steel drain pan condens...

Страница 3: ...nstalled Power Wiring 22 Main Unit Power Standard Wiring 22 Field Installed Control Wiring 22 Controls using 24 VAC 23 Controls using DC Analog Input Outputs Standard Low Voltage Multiconductor Wire 2...

Страница 4: ...Digital Zone Sensor Test 39 Unit Economizer Control ECA Trouble shooting ReliaTel Control 40 Wiring Diagrams 41 Limited Warranty 42 Heat Pump WCC WCD WCH WCM and WSC Parts Only 42 Heat Pump WCZ WCY W...

Страница 5: ...connect6 2 Unit Mounted Circuit Breaker6 Digit 20 Convenience Outlet 0 No Convenience Outlet A Unpowered Convenience Outlet B Powered Convenience Outlet three phase only 7 Digit 21 Communications Opti...

Страница 6: ...rcuit breaker options 7 Requires use of Disconnect or Circuit Breaker 8 Standard metering devices are TXVs 9 The return air smoke detector may notfit upor workproperly on the Precedent units when used...

Страница 7: ...the unit It is capable of delivering up to 25 inch pounds of torque and is powered by 24 VAC RTCI ReliaTel Trane Communication Interface Optional This module is used when the application calls for an...

Страница 8: ...ed the compressor will not be allowed to operate Anytime this circuit is opened for 1 continuous second during compressor operation the compressor for that circuit is immediately turned Off The compre...

Страница 9: ...to a BAYSENS119 remote panel wiring must be 18 AWG shielded twisted pair Belden 8760 or equivalent Refer to the specific remote panel for wiring details Wireless Zone Sensor BAYSENS050 This electronic...

Страница 10: ...10 RT SVX39B EN Unit Clearances Figure 1 Typical installation clearances for single multiple unit applications WSC060E unit WSC072 120E units...

Страница 11: ...es RT SVX39B EN 11 Figure 2 Heat pump 5 ton Note All dimensions are in inches millimeters Figure 3 Heat pump 5 ton unit clearance and roof opening Note All dimensions are in inches millimeters CLEARAN...

Страница 12: ...Unit Clearances 12 RT SVX39B EN Figure 4 Heat pump 5 ton roof curb Note All dimensions are in inches millimeters Figure 5 Heat pumps 6 7 tons Note All dimensions are in inches millimeters...

Страница 13: ...Clearances RT SVX39B EN 13 Figure 6 Heat pump 10 ton Note All dimensions are in inches millimeters Figure 7 Heat pump 6 10 ton unit clearance and roof opening Note All dimensions are in inches millime...

Страница 14: ...Unit Clearances 14 RT SVX39B EN Figure 8 Heat pump 6 10 ton roof curb Note All dimensions are in inches millimeters 2130 MM 356 MM...

Страница 15: ...he consignee Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur after delivery No...

Страница 16: ...f gravity dimensions in mm Tons Unit Model No Maximum Model Weights a lbs kgs Corner Weights b Center of Gravity in mm Shipping Net A B C D Length Width 5 WSC060ED 667 304 562 256 169 77 140 64 96 44...

Страница 17: ...air openings as viewed form the rear of the unit Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence andto reduce static pressure When attaching the ductwor...

Страница 18: ...rb ductwork must be fabricated and installed by the installing contractor before the unit is set into place Note For sound consideration cut only the holes in the roof deck for the ductwork penetratio...

Страница 19: ...the unit for shipping damage and material shortage file a freight claim and notify appropriate sales representative Verify correct model options and voltage from unit nameplate Verify that the install...

Страница 20: ...he outward edge of each duct cover with 2 screws 5 Slide RETURN DUCT COVER insulation side up into supply opening until inward edge of duct cover engages with the 2 retaining clips on the duct flange...

Страница 21: ...ccess panel and supply air access panels 2 Remove the support panel that the condensate drain pan exits through 3 Slide the condensate drain pan out of the unit 4 Place on a level surface in the posit...

Страница 22: ...dard Wiring 1 Location of the applicable electrical service entrance is illustrated in Unit Clearances p 10 Complete the unit s power wiring connections at Compressor Contactor 1 CC1 inside the unit c...

Страница 23: ...etween the unit and components utilizing a DC analog input output signal refer to Unit Clearances p 10 for the electrical access locations provided on the unit 1 Table 4 lists the conductor sizing gui...

Страница 24: ...Installation 24 RT SVX39B EN Figure 24 ReliaTel refrigeration module Figure 25 Customer control low voltage routing...

Страница 25: ...rature averaging Example 1 illustrates two series circuits with two sensors in each circuit wired in parallel The square of any number of remote sensors is required Example 2 illustratesthreesensorssq...

Страница 26: ...27 Typical field wiring diagrams for optional controls BAYSENS119 ASYSTAT777 Zone Sensor BAYSENS077 ASYSTAT111 BAYSENS107 BAYSENS073 Zone Sensor BAYSENS077 ASYSTAT111 BAYSENS109 BAYSENS074 Zone Sensor...

Страница 27: ...ing that deviates the farthest from the average voltage Example If the voltage readings of the supply power measured 221 230 and 227 the average volts would be VD reading farthest from average 221 The...

Страница 28: ...Upon power initialization the RTRM performs self diagnostic checks to insure that all internal controls are functional It also checks the configuration parameters against the components connected to...

Страница 29: ...t will automatically revert to the applied System control method For unit test steps test modes and step resistance values to cycle the various components refer to Table 6 p 30 ReliaTel Controls Upon...

Страница 30: ...y adjustment set screw and turn sheave clockwise To decrease fan RPM loosen the pulley adjustment set screw and turn sheave counterclockwise If the required CFM is too high external static pressure is...

Страница 31: ...nded period 15 to 30 minutes the motor winding can overheat and cause the motor winding thermostat to open 3 After the compressor and condenser fan have started and operated for approximately 30 minut...

Страница 32: ...e amount of belt deflection that corresponds to the proper belt tension 2 Set the large O ring on the belt tension gauge at the deflection value determined in Step 1b 3 Set the small O ring at zero on...

Страница 33: ...all P D Range Super Gripbelts Gripnotch Steel Cable Gripbelts Min Max Min Max Min Max A 3 0 3 6 3 4 1 2 3 7 8 5 1 2 3 1 4 4 3 8 4 8 3 1 2 5 4 1 2 6 1 4 3 3 4 4 3 4 5 0 7 0 4 5 1 2 5 6 7 8 4 1 4 5 1 4...

Отзывы: