Table 3 . Optional TXV kit part numbers. Some combinations may require a TXV. See AHRI
for system combination ratings.
Table 4.Superheat Charging Chart
95/79
90/75
85/71
80/67
75/63
70/58
115
23
16
7
6
5
5
110
24
17
9
6
5
5
105
26
19
11
6
5
5
100
27
21
13
7
6
5
95
29
23
14
9
6
5
90
30
25
18
12
7
5
85
32
26
20
15
9
6
80
34
28
22
17
11
6
75
35
30
24
19
13
7
70
37
32
26
21
16
10
65
38
34
29
24
19
13
60
40
36
31
27
22
17
55
41
37
34
30
26
21
Superheat (°F)
Indoor Temperature(°F) Dry Bulb/wet Bulb
Outdoor
Temp(°F)
Charge the system by superheat when using a piston. Reference the outdoor unit installation guide
to charge the system by subcooling when using a TXV.