5. AIRFLOW PERFORMANCE (
O
XBOX
AIR HANDLERS ARE SUITABLE FOR MOBILE
HOME APPLICATIONS)
Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size.
External static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat
operation.
AIRFLOW PERFORMANCE DATA
0[0]
0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200]
SCFM
590
544
511
447
404
345
311
273
239
Power/W
49
57
64
70
75
82
91
97
102
Current/A
0.77
0.81
0.84
0.87
0.91
0.94
0.99
1.02
1.11
SCFM
681
633
591
535
490
446
388
354
313
Power/W
63
69
77
83
90
96
103
111
118
Current/A
0.84
0.87
0.93
0.96
0.99
1.03
1.07
1.13
1.16
SCFM
788
736
687
648
597
558
511
473
429
Power/W
86
91
100
108
114
121
128
133
142
Current/A
0.95
0.99
1.11
1.14
1.18
1.21
1.26
1.31
1.37
SCFM
883
842
796
758
717
681
642
599
524
Power/W
121
128
135
144
151
159
165
173
181
Current/A
1.21
1.28
1.32
1.38
1.43
1.47
1.54
1.59
1.64
SCFM
1103
1073
1036
998
967
934
896
855
814
Power/W
233
241
249
258
265
275
281
286
291
Current/A
1.97
2.03
2.09
2.16
2.22
2.29
2.34
2.37
2.41
SCFM
590
544
511
447
404
345
311
273
239
Power/W
49
57
64
70
75
82
91
97
102
Current/A
0.77
0.81
0.84
0.87
0.91
0.94
0.99
1.02
1.11
SCFM
681
633
591
535
490
446
388
354
313
Power/W
63
69
77
83
90
96
103
111
118
Current/A
0.84
0.87
0.93
0.96
0.99
1.03
1.07
1.13
1.16
SCFM
788
736
687
648
597
558
511
473
429
Power/W
86
91
100
108
114
121
128
133
142
Current/A
0.95
0.99
1.11
1.14
1.18
1.21
1.26
1.31
1.37
SCFM
883
842
796
758
717
681
642
599
524
Power/W
121
128
135
144
151
159
165
173
181
Current/A
1.21
1.28
1.32
1.38
1.43
1.47
1.54
1.59
1.64
SCFM
1103
1073
1036
998
967
934
896
855
814
Power/W
233
241
249
258
265
275
281
286
291
Current/A
1.97
2.03
2.09
2.16
2.22
2.29
2.34
2.37
2.41
SCFM
898
752
603
511
405
360
301
259
203
Power/W
78
72
65
60
54
48
41
38
36
Current/A
0.68
0.64
0.59
0.52
0.46
0.42
0.36
0.29
0.28
SCFM
1026
902
810
694
630
544
490
409
366
Power/W
109
99
106
111
120
126
135
140
148
Current/A
0.94
0.86
0.91
0.95
1.03
1.07
1.14
1.18
1.24
SCFM
1161
1114
1052
992
893
825
768
694
646
Power/W
148
158
164
175
187
193
203
209
219
Current/A
1.26
1.34
1.39
1.48
1.57
1.61
1.69
1.73
1.81
SCFM
1287
1244
1186
1142
1078
969
914
892
893
Power/W
194
205
211
221
233
241
252
253
253
Current/A
1.62
1.69
1.75
1.83
1.93
1.98
2.07
2.08
2.11
SCFM
1491
1442
1396
1348
1302
1243
1150
1088
1029
Power/W
290
298
307
318
325
337
351
362
367
Current/A
2.35
2.42
2.49
2.58
2.64
2.73
2.83
2.92
2.96
SCFM
898
752
603
511
405
360
301
259
203
Power/W
78
72
65
60
54
48
41
38
36
Current/A
0.68
0.64
0.59
0.52
0.46
0.42
0.36
0.29
0.28
SCFM
1026
902
810
694
630
544
490
409
366
Power/W
109
99
106
111
120
126
135
140
148
Current/A
0.94
0.86
0.91
0.95
1.03
1.07
1.14
1.18
1.24
SCFM
1161
1114
1052
992
893
825
768
694
646
Power/W
148
158
164
175
187
193
203
209
219
Current/A
1.26
1.34
1.39
1.48
1.57
1.61
1.69
1.73
1.81
SCFM
1287
1244
1186
1142
1078
969
914
892
893
Power/W
194
205
211
221
233
241
252
253
253
Current/A
1.62
1.69
1.75
1.83
1.93
1.98
2.07
2.08
2.11
SCFM
1491
1442
1396
1348
1302
1243
1150
1088
1029
Power/W
290
298
307
318
325
337
351
362
367
Current/A
2.35
2.42
2.49
2.58
2.64
2.73
2.83
2.92
2.96
Outdoor Unit
Size(Tons)
1.5
2
2.5
3
36
1
2
3
4
(Factory Default)
5
5
36
1
2
3
(Recommended)
4
(Factory Default)
24
1
2
3
4
(Factory Default)
5
5
Air
Handler
Model
Motor Speed
CFM Wet Coil without filter and Electric Heat
External Static Pressure-Inches W.C.[kPa]
24
1
2
3
(Recommended)
4
(Factory Default)