5. AIRFLOW PERFORMANCE (

O

XBOX

 AIR HANDLERS ARE SUITABLE FOR MOBILE

HOME APPLICATIONS)

Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size. 

External static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat 

operation. 

AIRFLOW PERFORMANCE DATA

0[0]

0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200]

SCFM

590

544

511

447

404

345

311

273

239

Power/W

49

57

64

70

75

82

91

97

102

Current/A

0.77

0.81

0.84

0.87

0.91

0.94

0.99

1.02

1.11

SCFM

681

633

591

535

490

446

388

354

313

Power/W

63

69

77

83

90

96

103

111

118

Current/A

0.84

0.87

0.93

0.96

0.99

1.03

1.07

1.13

1.16

SCFM

788

736

687

648

597

558

511

473

429

Power/W

86

91

100

108

114

121

128

133

142

Current/A

0.95

0.99

1.11

1.14

1.18

1.21

1.26

1.31

1.37

SCFM

883

842

796

758

717

681

642

599

524

Power/W

121

128

135

144

151

159

165

173

181

Current/A

1.21

1.28

1.32

1.38

1.43

1.47

1.54

1.59

1.64

SCFM

1103

1073

1036

998

967

934

896

855

814

Power/W

233

241

249

258

265

275

281

286

291

Current/A

1.97

2.03

2.09

2.16

2.22

2.29

2.34

2.37

2.41

SCFM

590

544

511

447

404

345

311

273

239

Power/W

49

57

64

70

75

82

91

97

102

Current/A

0.77

0.81

0.84

0.87

0.91

0.94

0.99

1.02

1.11

SCFM

681

633

591

535

490

446

388

354

313

Power/W

63

69

77

83

90

96

103

111

118

Current/A

0.84

0.87

0.93

0.96

0.99

1.03

1.07

1.13

1.16

SCFM

788

736

687

648

597

558

511

473

429

Power/W

86

91

100

108

114

121

128

133

142

Current/A

0.95

0.99

1.11

1.14

1.18

1.21

1.26

1.31

1.37

SCFM

883

842

796

758

717

681

642

599

524

Power/W

121

128

135

144

151

159

165

173

181

Current/A

1.21

1.28

1.32

1.38

1.43

1.47

1.54

1.59

1.64

SCFM

1103

1073

1036

998

967

934

896

855

814

Power/W

233

241

249

258

265

275

281

286

291

Current/A

1.97

2.03

2.09

2.16

2.22

2.29

2.34

2.37

2.41

SCFM

898

752

603

511

405

360

301

259

203

Power/W

78

72

65

60

54

48

41

38

36

Current/A

0.68

0.64

0.59

0.52

0.46

0.42

0.36

0.29

0.28

SCFM

1026

902

810

694

630

544

490

409

366

Power/W

109

99

106

111

120

126

135

140

148

Current/A

0.94

0.86

0.91

0.95

1.03

1.07

1.14

1.18

1.24

SCFM

1161

1114

1052

992

893

825

768

694

646

Power/W

148

158

164

175

187

193

203

209

219

Current/A

1.26

1.34

1.39

1.48

1.57

1.61

1.69

1.73

1.81

SCFM

1287

1244

1186

1142

1078

969

914

892

893

Power/W

194

205

211

221

233

241

252

253

253

Current/A

1.62

1.69

1.75

1.83

1.93

1.98

2.07

2.08

2.11

SCFM

1491

1442

1396

1348

1302

1243

1150

1088

1029

Power/W

290

298

307

318

325

337

351

362

367

Current/A

2.35

2.42

2.49

2.58

2.64

2.73

2.83

2.92

2.96

SCFM

898

752

603

511

405

360

301

259

203

Power/W

78

72

65

60

54

48

41

38

36

Current/A

0.68

0.64

0.59

0.52

0.46

0.42

0.36

0.29

0.28

SCFM

1026

902

810

694

630

544

490

409

366

Power/W

109

99

106

111

120

126

135

140

148

Current/A

0.94

0.86

0.91

0.95

1.03

1.07

1.14

1.18

1.24

SCFM

1161

1114

1052

992

893

825

768

694

646

Power/W

148

158

164

175

187

193

203

209

219

Current/A

1.26

1.34

1.39

1.48

1.57

1.61

1.69

1.73

1.81

SCFM

1287

1244

1186

1142

1078

969

914

892

893

Power/W

194

205

211

221

233

241

252

253

253

Current/A

1.62

1.69

1.75

1.83

1.93

1.98

2.07

2.08

2.11

SCFM

1491

1442

1396

1348

1302

1243

1150

1088

1029

Power/W

290

298

307

318

325

337

351

362

367

Current/A

2.35

2.42

2.49

2.58

2.64

2.73

2.83

2.92

2.96

Outdoor Unit

Size(Tons)

1.5

2

2.5

3

36

1

2

3

4

(Factory Default)

5

5

36

1

2

3

(Recommended)

4

(Factory Default)

24

1

2

3

4

(Factory Default)

5

5

 Air

Handler

Model

Motor Speed

CFM Wet Coil without filter and Electric Heat

External Static Pressure-Inches W.C.[kPa]

24

1

2

3

(Recommended)

4

(Factory Default)

Содержание Oxbox J4AC4018A1

Страница 1: ...tion or operation Failure to follow these instruction may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury...

Страница 2: ...orizontal left or downflow Multiple electrical entry locations Field installed electric heater kits 5 7 5 10 15 20 kW available as an accessory Dual front panel design for ease of maintenance Blower a...

Страница 3: ...e possibly resulting in fire electrical shock property damage personal injury or death The unit must be permanently grounded Failure to do so can result in electrical shock causing personal injury or...

Страница 4: ...lications Top and side power and control wiring accessible screw terminals for control wiring all combine to make the installation easy and minimize installation cost See Fig 6 2 GENERAL CAUTION Make...

Страница 5: ...as insulation so that the thickness is more than 2 in and fits inside the installation space opening Respectively condensation may form on the surface of the insulation Be sure to use insulation that...

Страница 6: ...5 8 500 21 5 8 550 18 456 UPFLOW UNIT SHOWN UNIT MAY BE INSTALLED UPFLOW DOWNFLOW HORIZONTAL RIGHT OR LEFT AIR SUPPLY Fig 6 DIMENSIONS SUPPLY AIR FLANGES ARE PROVIDED FOR FIELD INSTALLATION ELECTRICA...

Страница 7: ...ay from breaker while setting that side of breaker into opening When breaker is in place release tab locking circuit breaker into location in opening Repeat above operation for remaining breaker s if...

Страница 8: ...ont service panel removed view AIRFLOW AIRFLOW Fig 9 INDOOR COIL AND DRAIN PAN SET UP HORIZONTAL ADAPTER KIT VAPOR LINE CONNECTION LIQUID LINE CONNECTION PRIMARY DRAIN CONNECTION VERTICAL DRAIN PAN AU...

Страница 9: ...en installed in accordance with electrical codes to the unit cabinet Grounding may also be accomplished by attaching ground wire s to ground lug s provided in the unit wiring compartment Ground lug s...

Страница 10: ...W Heat Strip 24 36 60 24 36 60 24 36 60 2 7 5kW Heat Strip 3 10kW Heat Strip 4 5 15kW Heat Strip double Breaker panel 20kW Heat Strip double Breaker panel 36 60 36 60 240 208 240 208 5 29 9 26 4 30 30...

Страница 11: ...32 1 38 1 43 1 47 1 54 1 59 1 64 SCFM 1103 1073 1036 998 967 934 896 855 814 Power W 233 241 249 258 265 275 281 286 291 Current A 1 97 2 03 2 09 2 16 2 22 2 29 2 34 2 37 2 41 SCFM 898 752 603 511 405...

Страница 12: ...1284 1226 1151 1076 946 904 893 869 Power W 143 151 159 168 177 191 197 195 194 Current A 1 23 1 26 1 33 1 41 1 50 1 61 1 63 1 61 1 62 SCFM 1531 1477 1418 1366 1299 1239 1138 1064 1001 Power W 200 211...

Страница 13: ...return ductwork grills special filters accessories etc are accounted for in total resistance See airflow performance tables in this manual Design the duct system in accordance with ACCA Manual D Desig...

Страница 14: ...recommended that a professional installation technician is contacted to ensure installation of these such filtration systems are installed correctly IMPORTANT Do not double filter the return air duct...

Страница 15: ...R MANUAL BOLT 9 FILTER INSTALLATION DIMENSIONS AIR FILTER REMOVAL DIMENSIONAL DATA 1 Remove bolts manually remove air filter recover see in Fig 12 2 Hold the edge of the air filter and extract out 3 C...

Страница 16: ...the air conditioner with the ground observe the local codes 5 If necessary use the power fuse or the circuit breaker or the corresponding scale ampere Fig 13 AIR FILTER CLEAN Fig 14 CONTROL WIRING FO...

Страница 17: ...ings CAUTION NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND ATTENTION NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE FM NOTES 1 Use Copper Wire 75 Min Only Between Disconnect Swi...

Страница 18: ...CK FL FL BLUE BLUE 4 1 3 2 CB1 60A W1 WHITE L1 L2 L1 L2 BLUE RED LS LS ELEMENTS ELEMENTS BROWN BLACK 1 2 3 4 5 6 0 15kW HEAT KIT 10kW 5kW HEATER KIT PLUG 4 8 2 6 C 1 0 1 BLACK YELLOW 4 8 2 6 RELAY2 YE...

Страница 19: ...60A1C00A 090 factory installed This coil comes with a factory installed piston metering device See Table 1 for factory installed piston size Some system combinations will require a different sized pis...

Страница 20: ...19 13 7 70 37 32 26 21 16 10 65 38 34 29 24 19 13 60 40 36 31 27 22 17 55 41 37 34 30 26 21 Superheat F Indoor Temperature F Dry Bulb wet Bulb Outdoor Temp F Charge the system by superheat when using...

Отзывы: