background image

12

7. REFRIGERANT CONNECTIONS

Keep the coil connections sealed until refrigerant connections are 
made. See the Installation Instructions for the outdoor unit for details 
on line sizing, tubing installation, and charging information.
Coil is shipped with Nitrogen. Evacuate the system before charging 
with refrigerant.
Install refrigerant tubing so that it does not block service access to 
the front of the unit.
Nitrogen should flow through the refrigerant lines while brazing.
Use a brazing shield to protect the cabinet’s paint and a wet rag to 
protect the rubber grommet  and input pipe’s pistion seal ring from 
being damaged by torch flames.
 After the refrigerant connections are made, seal the gap around the 
connections with pressure sensitive gasket.  

Do not, under any circumstances, connect return ductwork to any 
other heat producing device such as fireplace insert, stove, etc. 
Unauthorized  use  of  such  devices  may  result  in  fire,  carbon 
monoxide  poisoning,  explosion,  personal  injury  or  property 
damage.

Sheet metal ductwork run in unconditioned spaces must be insulated 
and covered with a vapor barrier. Fibrous ductwork may be used if 
constructed and installed in accordance with SMACNA Construction 
Standard  on  Fibrous  Glass  Ducts.  Ductwork  must  comply  with 
National Fire Protection Association as tested by UL Standard 181 for 
Class I Air Ducts. Check local codes for requirements on ductwork 
and insulation.

Duct system must be designed within the range of external static 
pressure the unit is designed to operate against. It is important 
that the system airflow be adequate. Make sure supply and return 
ductwork, grills, special filters, accessories, etc. are accounted for 
in total resistance. See airflow performance tables in this manual.

Design the duct system in accordance with “ACCA” Manual “D” 
Design for Residential Winter and Summer Air Conditioning and 
Equipment Selection. Latest editions are available from: “ACCA” 
Air Conditioning Contractors of America, 1513 16th Street, N.W., 
Washington, D.C. 20036. If duct system incorporates flexible air 
duct, be sure pressure drop Information (straight length plus all 
turns) shown in “ACCA” Manual “D” is accounted for in system. 

Supply plenum is attached to the 3/4” duct flanges supplied with 
the unit. Attach flanges around the blower outlet.

IMPORTANT: 

If an elbow is included in the plenum close to the 

unit, it can not be smaller than the dimensions of the supply duct 
flange on the unit.

IMPORTANT:

 The front flange on the return duct if connected to 

the blower casing must not be screwed into the area where the 
power wiring is located. Drills or sharp screw points can damage 
insulation on wires located inside unit.

Secure the supply and return ductwork to the unit flanges, using 
proper  fasteners  for  the  type  of  duct  used  and  tape  the 
duct-to-unit joint as required to prevent air leaks.  

WARNING

6. DUCTWORK

Field  ductwork  must  comply  with  the  National  Fire  Protection 
Association  NFPA  90A,  NFPA  90B  and  any  applicable  local 
ordinance.

WARNING

Use a wet rag to protect the two seal ring in the input pipe from 
being damaged by torch flames while brazing. 

After the work is finished,make sure to check that there is no vapor 
leak After checking for vapor leaks,be sure to insulate the piping 
connections referring to Fig.10.

 

 

Fig.10 PIPING CONNECTIONS

Do not leave a gap

Vapor piping

Piping heat insulation

material

Liquid piping

Air

handler

Do not leave a gap

Содержание Oxbox J4AC4018A1

Страница 1: ...tion or operation Failure to follow these instruction may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury...

Страница 2: ...orizontal left or downflow Multiple electrical entry locations Field installed electric heater kits 5 7 5 10 15 20 kW available as an accessory Dual front panel design for ease of maintenance Blower a...

Страница 3: ...e possibly resulting in fire electrical shock property damage personal injury or death The unit must be permanently grounded Failure to do so can result in electrical shock causing personal injury or...

Страница 4: ...lications Top and side power and control wiring accessible screw terminals for control wiring all combine to make the installation easy and minimize installation cost See Fig 6 2 GENERAL CAUTION Make...

Страница 5: ...as insulation so that the thickness is more than 2 in and fits inside the installation space opening Respectively condensation may form on the surface of the insulation Be sure to use insulation that...

Страница 6: ...5 8 500 21 5 8 550 18 456 UPFLOW UNIT SHOWN UNIT MAY BE INSTALLED UPFLOW DOWNFLOW HORIZONTAL RIGHT OR LEFT AIR SUPPLY Fig 6 DIMENSIONS SUPPLY AIR FLANGES ARE PROVIDED FOR FIELD INSTALLATION ELECTRICA...

Страница 7: ...ay from breaker while setting that side of breaker into opening When breaker is in place release tab locking circuit breaker into location in opening Repeat above operation for remaining breaker s if...

Страница 8: ...ont service panel removed view AIRFLOW AIRFLOW Fig 9 INDOOR COIL AND DRAIN PAN SET UP HORIZONTAL ADAPTER KIT VAPOR LINE CONNECTION LIQUID LINE CONNECTION PRIMARY DRAIN CONNECTION VERTICAL DRAIN PAN AU...

Страница 9: ...en installed in accordance with electrical codes to the unit cabinet Grounding may also be accomplished by attaching ground wire s to ground lug s provided in the unit wiring compartment Ground lug s...

Страница 10: ...W Heat Strip 24 36 60 24 36 60 24 36 60 2 7 5kW Heat Strip 3 10kW Heat Strip 4 5 15kW Heat Strip double Breaker panel 20kW Heat Strip double Breaker panel 36 60 36 60 240 208 240 208 5 29 9 26 4 30 30...

Страница 11: ...32 1 38 1 43 1 47 1 54 1 59 1 64 SCFM 1103 1073 1036 998 967 934 896 855 814 Power W 233 241 249 258 265 275 281 286 291 Current A 1 97 2 03 2 09 2 16 2 22 2 29 2 34 2 37 2 41 SCFM 898 752 603 511 405...

Страница 12: ...1284 1226 1151 1076 946 904 893 869 Power W 143 151 159 168 177 191 197 195 194 Current A 1 23 1 26 1 33 1 41 1 50 1 61 1 63 1 61 1 62 SCFM 1531 1477 1418 1366 1299 1239 1138 1064 1001 Power W 200 211...

Страница 13: ...return ductwork grills special filters accessories etc are accounted for in total resistance See airflow performance tables in this manual Design the duct system in accordance with ACCA Manual D Desig...

Страница 14: ...recommended that a professional installation technician is contacted to ensure installation of these such filtration systems are installed correctly IMPORTANT Do not double filter the return air duct...

Страница 15: ...R MANUAL BOLT 9 FILTER INSTALLATION DIMENSIONS AIR FILTER REMOVAL DIMENSIONAL DATA 1 Remove bolts manually remove air filter recover see in Fig 12 2 Hold the edge of the air filter and extract out 3 C...

Страница 16: ...the air conditioner with the ground observe the local codes 5 If necessary use the power fuse or the circuit breaker or the corresponding scale ampere Fig 13 AIR FILTER CLEAN Fig 14 CONTROL WIRING FO...

Страница 17: ...ings CAUTION NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND ATTENTION NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE FM NOTES 1 Use Copper Wire 75 Min Only Between Disconnect Swi...

Страница 18: ...CK FL FL BLUE BLUE 4 1 3 2 CB1 60A W1 WHITE L1 L2 L1 L2 BLUE RED LS LS ELEMENTS ELEMENTS BROWN BLACK 1 2 3 4 5 6 0 15kW HEAT KIT 10kW 5kW HEATER KIT PLUG 4 8 2 6 C 1 0 1 BLACK YELLOW 4 8 2 6 RELAY2 YE...

Страница 19: ...60A1C00A 090 factory installed This coil comes with a factory installed piston metering device See Table 1 for factory installed piston size Some system combinations will require a different sized pis...

Страница 20: ...19 13 7 70 37 32 26 21 16 10 65 38 34 29 24 19 13 60 40 36 31 27 22 17 55 41 37 34 30 26 21 Superheat F Indoor Temperature F Dry Bulb wet Bulb Outdoor Temp F Charge the system by superheat when using...

Отзывы: