SSA-SVX06H-EN
35
Table 9. Minimum VFD speed ranges
Effective
Supply Fan
Maximum
VFD Output
(Hz)
Minimum Speed Range
(60 Hz)
Effective
Supply Fan
Maximum
VFD Output
(Hz)
Minimum Speed Range
(60 Hz)
Min
Max
Min
Max
60
25
60
49.8
25
49.8
59.4
25
59.4
49.2
25
49.2
58.8
25
58.8
48.6
25
48.6
58.2
25
58.2
48
25
48
57.6
25
57.6
47.4
25
47.4
57
25
57
46.8
25
46.8
56.4
25
56.4
46.2
25
46.2
55.8
25
55.8
45.6
25
45.6
55.2
25
55.2
45
25
45
54.6
25
54.6
44.4
25
44.4
54
25
54
43.8
25
43.8
53.4
25
53.4
43.2
25
43.2
52.8
25
52.8
42.6
25
42.6
52.2
25
52.2
42
25
42
51.6
25
51.6
41.4
25
41.4
51
25
51
40.8
25
40.8
50.4
25
50.4
40.2
25
40.2
Symbio™ Condenser
Configuration Management
The Symbio™ 700 controller in the Odyssey condenser
must be properly configured to integrate appropriately
with various air handler configurations. As shipped
from the factory, the Symbio 700 in the condenser is
configured to be integrated with a single-speed,
constant volume air handler. If the air handler paired
with the condenser is a two-speed or SZVAV
configuration, the Symbio 700 configuration must be
updated in the condenser. This configuration update
can be made through either of the user interfaces on
the Symbio 700, including the Mobile Service and
Installation app.
Two-Speed Air Handler Systems
To configure the Symbio 700 for two-speed air handler
systems use the following steps and refer to through :
1. In the Mobile Service and Installation app, tap
S
Se
ettttiin
ng
gss.
2. Tap E
Ed
diitt.
3. Tap IIn
nd
do
oo
orr F
Fa
an
n T
Ty
yp
pe
e.
4. Select M
Mu
ullttii S
Sp
pe
ee
ed
d.
5. Tap A
Ap
pp
plly
y.
6. Verify that all settings are correct.
S
Stta
arrttu
up
p