Field Wiring
Refer to the table below for instructions on field wiring
connections.
Table 7. Field wiring instructions
Condenser
Condenser
Model No.
(Digit 15)
Paired with Air
Handler
Air Handler
Model No.
(Digit 15)
Field Control Wiring Instructions
Symbio Condenser
(cooling or heat pump)
S
Constant Volume
1
Pairing A
Symbio Condenser
(cooling or heat pump)
S
SZVAV / 2-Speed
D
Pairing B
Symbio Condenser
(cooling or heat pump)
S
Legacy CV
Electromechanical
0
182095
(a)
Symbio Condenser
(cooling or heat pump)
S
Legacy 2-Speed
Electromechanical
A
182095
(a)
Legacy Electromechanical
Condenser
E
2-Speed
(b)
C
Pairing C
Legacy Electromechanical
Condenser
E
Constant Volume
1
182095
(a)
Legacy ReliaTel
Condenser (cooling or
heat pump)
R
Constant Volume
1
182095
(a)
Note:
Gray shaded cells indicate older legacy units.
(a)
Contact the local Trane Commercial Sales office to receive a copy of Hub Case details.
(b)
2-Speed Air Handler (identified by a “C” in digit 15) is specifically designed as a replacement air handler for a system with a legacy electromechanical
condenser.
Pairing A: Symbio Condenser or Heat
Pump with Constant Volume Air Handler
1. Refer to Condenser (SS-SVX001*-EN) or Heat Pump
(SSP-SVX001*-EN) IOM for instructions on
connecting a room thermostat or other zone control
device to the controls of the outdoor unit.
2. 24VAC connection
a. For TWE060 units, transformer TNS3 is
provided and factory wired to supply 24VAC to
the Relay Board.
b. For all other units, 24VAC should be supplied to
the air handler from the outdoor unit as shown
in the schematic (See
Figure 23, p. 31
).
3. Thermostat interface
Interconnection wiring as shown in
Figure 24, p. 31
is required to initiate air handler supply fan
operation and to prevent air handler coil frosting (if
desired).
4. Electric Heat (when installed)
a. IMC (InterModule Communication) wiring is
required as shown in
Figure 25, p. 31
.
IIm
mp
po
orrtta
an
ntt:: IMC (+, -) signal wiring should be a
twisted pair.
b. For all other wiring associated with electric heat,
refer to Air Handler unit schematic and Electric
Heat Accessory Installation Guide (ACC-
SVN91*-EN).
Pairing B: Symbio Condenser or Heat
Pump with SZVAV / 2-Speed Air Handler
1. Refer to Condenser (SS-SVX001*-EN) or Heat Pump
IOM (SSP-SVX001*-EN) for instructions on
connecting a room thermostat or other zone control
device to the controls of the outdoor unit.
2. Connect 24VAC from the outdoor unit to the air
handler as shown in
Figure 23, p. 31
.
3. Thermostat interface
Interconnection wiring as shown in
Figure 24, p. 31
is required to initiate air handler supply fan
operation and to prevent air handler coil frosting (if
desired).
4. Make IMC and MODBUS connections between
outdoor and indoor units as shown on the unit
schematic (see
Figure 25, p. 31
and
Figure 26, p.
32
).
IIm
mp
po
orrtta
an
ntt:: Ensure MODBUS and IMC signal wires
(+, -) are twisted pairs.
5. Electric Heat (when installed)
a. The IMC circuit (connected per step 4) controls
stages of electric heat.
b. For all other wiring associated with electric heat,
IIn
nsstta
alllla
attiio
on
n