System Testing & Troubleshooting
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
5 to 255 seconds
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
The following screen will be displayed after pressing the "TEST
START" key if a SERVICE MODE screen has been displayed
during the previous 60 minutes.
Used on Units:
All Units
Possible Values:
120 to 0 Seconds
If a screen has not been displayed during the SERVICE MODE
procedure for 60 minutes and the TEST START key is pressed,
the following screen will be displayed.
Used on Units:
All Units
When the START TEST timer expires, this screen will be displayed
at the unit mounted Human Interface and at the remote mounted
Human Interface, if installed.
Used on Units:
All Units
Note:
There is no time-out period when the unit is operating in the
SERVICE TEST mode. Press the "STOP" or "AUTO" key to
discontinue the Service Test. Only the STATUS, CUSTOM,
SERVICE MODE, DIAGNOSTICS, and STOP keys are functional
once the TEST START key has been pressed.
After pressing the STOP or AUTO key, the following screen is displayed
and then the following screen is displayed:
and then the top level status screen is displayed.
Start Test in 5 Sec
Press TEST START To Begin, STOP To Halt
Test Start In 5 Sec
Press STOP To Halt
Press SERVICE MODE
To Review Selections
Service Test Is Active
Press STOP To Halt
Service Mode, STOP SYSTEM Restart
Communicating With Unit. Please Wait
Updating Unit Data. Please Wait
TRANE INTELLIPAK