37
System Configuration
CONFIGURATION Menu
The CGM controlled unit has many operating functions
whose settings are preset at the factory. The following con-
figuration programming steps are provided for those cases
where the Human Interface module has been replaced after
the unit has been in operation and must be reconfigured.
Refer to the Model number stamped on the unit nameplate
located on the control panel door while scrolling through the
configuraton screes. Certain digits of this alpha/numeric
model number provide information that must be entered at
the Human Interface (HI) in order for the CGM network to
operate properly.
Press the CONFIGURATION key to display the following
screens. Check the unit model number and compare it to the
data that is displayed in the following screens
Used on Units:
All Units
Possible Values:
20, 25, 30, 40, 50, 60
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
200 VAC, 230 VAC, 380 VAC,
415 VAC, 460 VAC, 575 VAC,
1. Press the + or - key until the proper value is displayed.
Special Voltage
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Installed, Not Installed
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
51-65 F, 40-50 F, 30-39 F,
20-29 F, Special
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Installed, Not Installed
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Installed, Not Installed
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Installed, Not Installed
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Used on Units:
All Units
Possible Values:
Installed, Not Installed
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
Configuration - Model Num Digit 5,6,7
Unit Capacity 50
Configuration - Model Num Digit 8
Line Voltage 460 VAC
Configuration - Model Num Digit 11
Ice Building Control INSTALLED
Configuration - Model Num Digit 11
Leaving Solution STP Range 40 - 50 F
Configuration - Model Num Digit 13+
Hot Gas Bypass Option INSTALLED
Configuration - Model Num Digit 13+
GBAS 0-5VDC Module
INSTALLED
Configuration - Model Num Digit 13+
GBAS 0-10VDC Module INSTALLED
Configuration - Model Num Digit 13+
Superheat/Subcool Module
INSTALLED