Startup Form
102
OAU-SVX01K-EN
Typical Setpoints
#
BACnet Point Name Setting Default
Range
Units
Description
DISCHARGE AIR CONTROL
AV-29
Outdoor Air Cooling
Enable Setpoint
-
45–100
°F
When the Outdoor Air Temperature is above this setpoint, the unit will
be locked into Cooling Mode.
AV-33
Outdoor Air Heating
Enable Setpoint
-
15–75
°F
When the Outdoor Air Temperature is below this setpoint, the unit will
be locked into Heating Mode (takes priority over Dehumidification
Mode).
AV-10 Outdoor Air Dewpoint
Enable Setpoint
-
45–100
°F
When the Outdoor Air Dewpoint is above this setpoint, the unit will be
locked into Dehumidification Mode (takes priority over Cooling Mode).
AV-30
Discharge Air Cooling
Setpoint BAS
60
45–90
°F
Discharge air setpoint during Cooling and Dehumidification Mode.
AV-32
Discharge Air Heating
Setpoint BAS
65
45–100
°F
Discharge air setpoint during Heating Mode.
AV-67
Discharge Air
Temperature Setpoint
BAS
55
40–125
°F
Discharge air setpoint used during Heating, Cooling, and
Dehumidification Mode. Factory defaulted Out of Service, put In
Service to use.
SPACE CONTROL AND SINGLE ZONE VAV
AV-87
Space Humidity
Setpoint
45
0–100
%
Temperature setpoint and this setpoint is used to calculate a Space
Dewpoint Setpoint, which puts the unit into Dehumidification Mode.
AV-01
Occupied Cooling
Setpoint
72
55–85
°F
Space cooling setpoint used in occupied mode.
AV-02
Occupied Heating
Setpoint
70
55–85
°F
Space heating setpoint used in occupied mode.
AV-25
Space Temperature
Setpoint BAS
72
62–80
°F
Communicated space temperature setpoint (overwrites Occupied
Cooling and Heating Setpoints). Factory defaulted Out of Service, put
In Service to use.
MULTI ZONE VAV
AV-10
Outdoor Air Dewpoint
Enable Setpoint
55
45–100
°F
When the Outdoor Air Dewpoint is above this setpoint, the unit will be
locked into Dehumidification Mode (takes priority over Cooling Mode).
AV-30
Discharge Air Cooling
Setpoint BAS
60
45–90
°F
Discharge air setpoint during Cooling and Dehumidification Mode.
AV-32
Discharge Air Heating
Setpoint BAS
65
45–100
°F
Discharge air setpoint during Heating Mode.
AV-67
Discharge Air
Temperature Setpoint
BAS
55
40–125
°F
Discharge air setpoint used during Heating, Cooling, and
Dehumidification Mode. Factory defaulted Out of Service, put In
Service to use.
AIR BALANCE
AV-39
Supply Fan Air Flow
Setpoint
Varies
0–25000
cfm
Setpoint used to control the supply fan for constant volume. Only
used on OAB and OAG cabinets (not VAV).
AV-46
Duct Static Pressure
Setpoint BAS
1.5
-1–6
in.H
2
O
Setpoint used to control supply fan to static pressure. Factory default
range is 0-2 in. WC, but can be re-configured for 0-5 in. WC.
AV-40
Exhaust Fan Speed
Setpoint BAS
80
0–100
%
Setpoint used for constant speed exhaust fan. Used on OAD, OAK, and
OAN cabinets that have exhaust, but do not have modulating OA/RA
dampers.
AV-57
Exhaust Fan Air Flow
Setpoint
Varies
0–25000
cfm
Setpoint used for constant volume exhaust fan control. Used on OAB
and OAG cabinets that have exhaust, but do not have modulating OA/
RA dampers.
AV-48
Outdoor Air Damper
Minimum Position
Setpoint
Varies
0–100
%
Setpoint used to limit the outdoor air damper position during all
operation. Typically adjusted during air balance. Factory set at an
estimate based on submittal data.