Problem
Probable
Cause
Solution
Duct System
1. Actual system is more restrictive than
expected.
2. Dampers closed.
3. Registers closed.
4. Leaks in supply duct.
Filters
Dirty or clogged.
Coil - DX or Chilled
Water
Dirty or clogged.
Obstructions in
High Velocity Air
Stream
1. Obstruction near unit outlet.
2. Sharp elbows near unit outlet.
3. Improperly designed turning vanes.
4. Projections, dampers or other obstructions
in part of duct system where air velocity is
high.
CFM High - Too
Much Air Flow
System
1. Oversized duct work.
2. Access door open.
3. Registers or grilles not installed.
4. Filters not in place.
5. System resistance lower than anticipated.
Blower
Blower RPM is too great.
Blower Does Not
Operate
Installation
1. Incorrect electrical connection.
2. Wrong voltage.
3. Blown fuse.
Unit
1. Broken belt(s).
2. Loose pulleys.
3. Power to unit is disconnected.
4. Motor overload protector has broken circuit.
5. Optional thermostats, firestats, freezestats
may lockout blower operation if set
incorrect.
Troubleshooting Guide — Electric Motors
Problem
Probable
Cause
Solution
Motor
Blown fuse or open
circuit breaker
Replace fuse or reset circuit breaker.
Overload trip
Check and reset, if manual.
Improper line
connections
Check connections to unit wiring diagram.
Improper current
supply
Check to determine that power supply agrees
with motor nameplate specifications.
Mechanical failure.
Determine that motor and drive turn freely.
Check bearings
T
Trro
ou
ub
blle
essh
ho
oo
ottiin
ng
g
Содержание GGAA
Страница 35: ...MUA SVX005B EN 35 Figure 12 Blower RPM Adjustment M Ma ai in nt te en na an nc ce e ...
Страница 47: ...MUA SVX005B EN 47 Motor Electric Data Table 7 Full Load Current in Amperes ...
Страница 50: ...50 MUA SVX005B EN Coil Cabinet Dimensional Data Figure 13 Coil Cabinet Dimensional Data ...
Страница 57: ...MUA SVX005B EN 57 Gas Equipment Start Up ...
Страница 58: ...58 MUA SVX005B EN N No ot te es s ...
Страница 59: ...MUA SVX005B EN 59 N No ot te es s ...