23
8. Approximately two minutes after satisfying the thermostat, fan operation ceases.
Optional Gas Controls
These units are available with optional gas controls which will give either multi-stage or
modulating operation. The sequence of operation of those units equipped with these optional
gas controls differs only at what rate each duct furnace’s main burners ignite and operate at, or
the order of duct furnace firing for those units equipped with two or three duct furnaces.
•
T
Tw
wo
o S
Stta
ag
ge
e U
Un
niittss:: Two stages of heating; first stage is 50% of full rate, second stage is 100%
of full rate. Main burner ignition is at first stage only.
•
T
Th
hrre
ee
e S
Stta
ag
ge
e U
Un
niittss::
–
Dual duct furnace models
: First furnace is equipped with two stage heating; second
furnace is equipped with single stage heating but fi red independently, giving three stages
of heating.
–
Triple duct furnace models
: Each duct furnace is equipped with single stage heating but
fired independently, giving three stages. Each stage is 33% of the unit’s full input rate.
Duct furnace one will always light first and disengage last.
•
F
Fo
ou
urr S
Stta
ag
ge
e U
Un
niittss:: Dual duct furnace models only. Each duct furnace is equipped with two
stage heating but fired independently, giving four stages. Each stage is 25% of the units full
input rate. Duct furnace one will always light first and disengage last.
•
S
Siix
x S
Stta
ag
ge
e U
Un
niittss:: Triple duct furnace models only. Each duct furnace is equipped with two
stage heating but fired independently giving six stages. Each stage is 16.5% of the units full
input rate. Duct furnace one will always light first and disengage last.
•
E
Elle
eccttrro
on
niicc M
Mo
od
du
ulla
attiio
on
n U
Un
niittss:: These units are equipped with an electronic modulating
control which provides unit firing capabilities of 40 to 100% of the units full input rate. This
control is found in the gas train downstream of the gas valve and allows main burner ignition
only at the maximum rate. A thermostat with remote set point adjustment modulates the gas
input.
•
M
Mu
ullttii--S
Stta
ag
ge
e w
wiitth
h E
Elle
eccttrro
on
niicc M
Mo
od
du
ulla
attiio
on
n U
Un
niittss:: These dual and triple duct furnace models
are equipped with an electronic modulating control on duct furnace one and single or two
stage heating on each successive duct furnace. Furnace one (modulated) will fire first and
disengage last. Additional stages of heat will engage after furnace one has fi red at maximum
modulation capability for the duration of the delay setting. The amount of modulation and
each stage size depends upon unit size and the number of stages. See following chart.
Table 2. Optional Gas Controls Data
Number of Stages
Modulation Capabilities (% of full
input)
Stage Size (% of full input)
2
25 — 50
50
3
16.5 — 33
33
4
25 — 50
25
6
16.5 — 33
16.5
Air Handling Requirements and Adjustments
N
NO
OT
TIIC
CE
E
U
Un
niitt D
Da
am
ma
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w iin
nssttrru
uccttiio
on
nss b
be
ello
ow
w cco
ou
ulld
d rre
essu
ulltt iin
n u
un
niitt d
da
am
ma
ag
ge
e..
R
Re
em
mo
ov
ve
e w
wo
oo
od
de
en
n ssh
hiip
pp
piin
ng
g ssu
up
pp
po
orrtt ffrro
om
m b
be
en
ne
ea
atth
h b
bllo
ow
we
err h
ho
ou
ussiin
ng
g o
off b
bllo
ow
we
err S
Se
eccttiio
on
n..
•
Static Pressure through the unit should never exceed 2.0” W.C. (0.50 kPa). Units operate at a
temperature rise range of 30 to 80°F (17 to 44°C).
O
Op
pe
erra
attiio
on
n
Содержание GGAA
Страница 35: ...MUA SVX005B EN 35 Figure 12 Blower RPM Adjustment M Ma ai in nt te en na an nc ce e ...
Страница 47: ...MUA SVX005B EN 47 Motor Electric Data Table 7 Full Load Current in Amperes ...
Страница 50: ...50 MUA SVX005B EN Coil Cabinet Dimensional Data Figure 13 Coil Cabinet Dimensional Data ...
Страница 57: ...MUA SVX005B EN 57 Gas Equipment Start Up ...
Страница 58: ...58 MUA SVX005B EN N No ot te es s ...
Страница 59: ...MUA SVX005B EN 59 N No ot te es s ...