UH1-DH1-SF-1L
Service Facts
23
DEFINITION
:
Ground Fault - Incoming or chassis
ground connection is not sensed
Polarity Fault – Incoming high
voltage wiring is reversed
Line Voltage Too Low - Line voltage
must not be below 97 VAC
Connect volt meter
to white incoming
neutral wire and
green earth ground
Does meter
read ~120 vac?
Disconnect
incoming electrical
power to furnace
YES
Reverse 120 vac
power leads to
furnace wiring
Reconnect power
Check operation
Connect volt meter
to black incoming
and chassis ground
at burner box
NO
Does meter
read ~120 vac?
Disconnect
incoming electrical
power to furnace
NO
Correct earth
ground.
Check operation
Check / correct all
ground
connections within
furnace for
continuity
Disconnect
incoming electrical
power to furnace
YES
Check operation
Is there a
voltage greater
than 10 VAC
NO
Correct neutral
and ground
problem. Furnace
must be on a
dedicated circuit.
YES
NO
6 Flash Fault LED