Literature History
CVGF-SVX03B-EN
(March 2016)
This is a new manual.
About this manual
This manual describes proper installation
of Model CVGF, 50 Hz and 60 Hz chillers
with the AdaptiView Controls platform.
See Figures 2 and 3 for an illustration of
a CVGF Centrifugal Chiller with the Adap-
tiView Unit Control Panel. These chillers
are equipped with microcomputer-based
control systems. A careful review of this
information along with the submittal
package provided for the unit will assure
that the chiller is correctly installed.
Operation and maintenance information
for models CVGF are covered in this man-
ual. This includes both 50 and 60 Hz. CVGF
centrifugal chillers equipped with the Trac-
er AdaptiVew Chiller Controller system.
A typical product description block is
shown in the Manual.
Carefully review this information and fol-
low the instructions given to successfully
install operate and maintain a CVGF unit.
If mechanical problems do occur, contact
a qualified service organization to ensure
proper diagnosis and repair of the unit.
Unit Nameplate
When the unit arrives, compare all name-
plate data with order, submittal and ship-
ping information. A typical unit nameplate
is shown in Figure 1.
The unit nameplate is located on the left
side of the unit control panel.
Note: Trane starters are identified by a
separate model number found on the
starter.
Figure 1. Typical unit nameplate
MODEL: CVGF500
MODEL NO:
CVGF0500RA0U33809405C1B5C1C23A1A201E3AA0
SERIAL NO: S.O. NO:
ELECTRICAL CHARACTERISTICS:
RATED VOLTAGE:
380 VOLTS
50HZ 3PH
NAMEPLATE NMKW:
338 kW
VOLTAGE UTILIZATION RANGE:
345- 422 VAC
MINIMUM CIRCUIT AMPACITY:
726 AMPS
MAXIMUM FUSE:
1200 AMPS
MAXIMUM CIRCUIT BREAKER
1200 AMPS
MAXIMUM OVERLOAD TRIP: 617 AMPS
MAX MAX
VOLTS-AC HZ PH
RLA
LRAY LRAD
COMPRESSOR MOTOR
380 50
3
577
1048
3286
OIL PUMP MOTOR
380
50
31.43 FLA
OIL TANK HEATER
115
50
1000 WATTS TOTAL
CONTROL CIRCUIT
115
50
1500 VA MAX
WHEN MOTOR CONTROLLER PROVIDED BY OTHERS
TRANE ENGINEERING SPEC. S6516-0360 APPLIES
GENERAL CHARACTERISTICS:
REFRIGERANT SYSTEM
TO BE FIELD CHARGED
ACTUALLY CHARGED
WITH 340 KG OF R-134A WITH KG OF R-134A
MAXIMUM REFRIGERANT WORKING PRESSURE
HI SIDE 15.2 BAR
LOW SIDE 15.2 BAR
FACTORY TEST PRESSURE
HI SIDE 16.7 BAR
LOW SIDE 16.7 BAR
FIELD LEAK TEST PRESSURE
5.17 BAR MAX.
TESTED AT
BAR
LEAK TEST AND CHARGING SPECIFICATION ARE SUPPLIED
IN CONTROL PANEL (SERVICE LITERATURE MANUAL)
MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING
U.S. PATENTS: 4686834 4689967 4715190 5056032
5058031 5434738 5563489 5836382
SERVICE LITERATURE
INSTALLATION, OPERATION AND MAINTENANCE MANUAL:
CVGF-SVN02C-EN AND CVGF-SVU02B-EN
“FOR INSTALLATION REQUIREMENTS, USE ELECTRICAL
CHARACTERISTICS NOT PRODUCT DESCRIPTION”
PRODUCT DESCRIPTION:
MODL CVGF
DSEQ A0
NTON 500
VOLT 380
HRTZ 50
CPKW 338
CPIM 940
EVSZ 500
EVBS C
EVTB TE25
EFLD WATE
EVWB NM15
EVWP 2
EVCO FLGE
EVWA RERE
CDSZ 500
CDBS C
CDTB TE28
CFLD WATE
CDWB NM15
CDCO FLGE
CDWA RERE
ORSZ 23
AGLT UL
SPKGEXPS
INSL YES
OPTM YES
WVUO YES
TRMM TRMS
LCLD CLDC
LANG ENGL
SRTY USTR
SRRL 952
PNCO DISC
TEST PTR3
General Information
CVGF-SVX03B-EN
4