30
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
AH-SVX03C-GB
Table 4 –
Trouble analysis
Symptom(s)
Probable Cause(s)
Recommanded Action(s)
Any Low Voltage Device not Working
Breakpoint Connector
Check Correct Connection
Tighten Connection
Repair Wiring
Differential Pressure Switch not Working
Tubes not connected
Connect Tubes
DPS failed
Blow down Positive Tube and hear click
Replace DPS
Damper not Working
Damper linkage is loose
Tighten damper linkage
Damper blade hitting an obstruction
Remove obstruction
Damper blade bent
Replace damper
Damper actuator is malfunctioning
See symptoms for mixed air damper actuator
not working
Damper actuator not working 24 VAC power
supply not present at the actuator
Control transformer furnishing the damper
actuator 24 VAC has failed
Check transformer
24 VAC power wiring is broken or shorted
Repair wiring
Damper actuator not working. 0 to 10 VDC
input signal to acuator not present
0 to 10 VDC input signal wiring broken
or shorted
Repair wiring
Valve not working
Valve not piped per recommended flow
arrangement
Re-pipe valve to recommended flow
arrangement
Valve seat hitting an obstruction in pipe
Remove obstruction
Valve actuator is malfunctioning
See symptoms for valve actuator
not working
Valve actuator not working. 24 VAC power
supply not present at the actuator
Control transformer furnishing the cooling
valve actuator 24 VAC power has failed
Check transformer
24 VAC power wiring broken or shorted
Repair wiring
Valve actuator not working. 0 to 10 VDC
input signal to actuator not present
0 to 10 VDC input signal wiring broken
or shorted
Repair wiring
Factory engineered controls