Table 3. Values for start reset types
The values for “RESET TYPE” are:
Reset
Outdoor
Return
Const Return
Type:
Disable
Air Reset
Reset
Reset
The values for “RESET RATIO” for each of the reset types are:
Reset
Reset
Increment
Increment
Factory
Type
Ratio
English
SI Units
Default
Range
Units
Value
Return
10 to 120 percent
1 percent
1 percent
50 percent
Outdoor -80 to 80 percent
1 percent
1 percent
10 percent
The values for “START RESET “ for each of the reset types are:
Reset
Start
Increment
Increment
Factory
Type
Reset
English
SI Units
Default
Range
Units
Value
Return
4 to 30°F
0.1°F
0.1°C
10°F (5.6°C)
(2.2 to 16.7°C)
Outdoor 50 to 130°F
0.1°F
0.1°C
90°F
(10 to 54.44°C)
(32.22°C)
The values for “MAXIMUM RESET” for each of the reset types are:
Reset
Maximum
Increment
Increment
Factory
Reset
English
SI Units
Default
Range
Units
Value
Return
0 to 20°F
0.1°F
0.1°C
5°F
(0.0 to 11.11°C)
(2.78°C)
Outdoor 0 to 20°F
0.1°F
0.1°C
5°F
(0.2 to 11.11°C)
(2.78°C)
Constant Return
CWS’ = CWS + 100 percent
(Design Delta Temperature) - (TWE-
TWL) and CWS’ > or = CWS and
CWS’ -CWS < or = Maximum Reset
Notice that Constant Return is
nothing more than a specific case of
Return Reset offered for operator
convenience.
When any type of CWR is enabled,
the UCP will step the CWS toward
the desired CWS (based on the above
equations and setup parameters) at a
rate of 1°F every 5 minutes until the
Active CWS equals the desired
CWS’. This applies when the chiller
is running only.
Using the Equation for calculating
CWR for Outdoor Air Temperature
Equation:
Degrees of Reset = Reset Ratio*(Start
Reset - TOD)
The chiller will start at the Differential
to Start value above a fully reset CWS
or CWS for both Return and Outdoor
Reset.
The graph on the next page, shows
the reset function for Outdoor Air
Temperature:
Note:
This graph
assumes that Maximum Reset is set
to 20 degrees.
Degrees of Reset:
Degrees of Reset = Active CWS -
Front Panel CWS
or
Degrees of Reset = CWS’ - CWS
To obtain Active CWS from Degrees
of Reset: Active CWS = Degrees of
Reset + Front Panel CWS
Machine Protection
and Adaptive
Control
(* = multiply)
Содержание CenTraVac Duplex CDHE
Страница 1: ...CDHF SVU01C EN X39640670030 Operation Maintenance Duplex CDHF CDHG Water Cooled CenTraVac With CH530 ...
Страница 9: ...9 CDHF SVU01C EN General Information Figure 2 General Duplex unit components 2 stage compressor ...
Страница 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Страница 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Страница 53: ...53 CDHF SVU01C EN Control System Components ...
Страница 65: ...65 CDHF SVU01C EN Control System Components ...
Страница 66: ...CDHF SVU01C EN 66 Control System Components ...
Страница 88: ...CDHF SVU01C EN 88 Figure 35 Return CWR Figure 36 Constant CWR Machine Protection and Adaptive Control ...
Страница 104: ...CDHF SVU01C EN 104 ...
Страница 105: ...105 CDHF SVU01C EN ...
Страница 106: ...CDHF SVU01C EN 106 ...
Страница 107: ...107 CDHF SVU01C EN ...
Страница 108: ...CDHF SVU01C EN 108 ...
Страница 109: ...109 CDHF SVU01C EN ...
Страница 110: ...CDHF SVU01C EN 110 ...
Страница 111: ...111 CDHF SVU01C EN ...
Страница 112: ...CDHF SVU01C EN 112 ...
Страница 113: ...113 CDHF SVU01C EN ...
Страница 114: ...CDHF SVU01C EN 114 ...
Страница 115: ...115 CDHF SVU01C EN ...