41
CDHF-SVU01C-EN
Operator
Interface
Report name: System Evaporator
Description
Resolution
Units
Dependencies
1. Evap Entering Water Temp
+ or – XXX.X
Temperature
2. Evap Leaving Water Temp
+ or – XXX.X
Temperature
3. Evap Water Flow Switch Status
(Flow, No Flow)
4. Evap Differential Wtr Press
XXX.X
Diff Pressure
If option installed
5. Approx Evap Water Flow
XXXX
Flow
If option installed
6. Approx Chiller Capacity
XXXX
Tons
If option installed
Report name: Circuit Evaporator
Description
Resolution
Units
Dependencies
1. Evap Sat Rfgt Temp
+ or – XXX.X
Temperature
2. Evap Rfgt Pressure
XXX.X
Pressure
3. Evap Approach Temp
+ or – XXX.X
Temperature
Report name: System Condenser
Description
Resolution
Units
Dependencies
1. Cond Entering Water Temp
+ or – XXX.X
Temperature
2. Cond Leaving Water Temp
+ or – XXX.X
Temperature
3. Cond Water Flow Switch Status
(Flow, No Flow)
4. Cond Differential Wtr Press
XXX.X
Diff Pressure
If option installed
5. Approx Cond Water Flow
XXXX
Flow
If option installed
6. Outdoor Air Temperature
+ or – XXX.X
Temperature
If option installed
Report name: Circuit Condenser
Description
Resolution
Units
Dependencies
1. Cond Sat Rfgt Temp
+ or – XXX.X
Temperature
2. Cond Rfgt Pressure
XXX.X
Pressure
3. Cond Approach Temp
+ or – XXX.X
Temperature
Note:
Approach temperatures shown are the mathematical difference between the chiller leaving water temperature and
the corresponding saturated refrigerant temperature of same circuit. When one compressor is operational the approach
value will be similar to those values found on single compressor models. However when both compressors are
operating, the upstream compressor circuits approach will be the mathematical difference of the upstream chillers
refrigerant temperature and the leaving water temperature after the down stream chillers circuit. Therefore the approach
of the upstream circuit will be a negative number in many instances, when both compressors are operating.
Содержание CenTraVac Duplex CDHE
Страница 1: ...CDHF SVU01C EN X39640670030 Operation Maintenance Duplex CDHF CDHG Water Cooled CenTraVac With CH530 ...
Страница 9: ...9 CDHF SVU01C EN General Information Figure 2 General Duplex unit components 2 stage compressor ...
Страница 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Страница 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Страница 53: ...53 CDHF SVU01C EN Control System Components ...
Страница 65: ...65 CDHF SVU01C EN Control System Components ...
Страница 66: ...CDHF SVU01C EN 66 Control System Components ...
Страница 88: ...CDHF SVU01C EN 88 Figure 35 Return CWR Figure 36 Constant CWR Machine Protection and Adaptive Control ...
Страница 104: ...CDHF SVU01C EN 104 ...
Страница 105: ...105 CDHF SVU01C EN ...
Страница 106: ...CDHF SVU01C EN 106 ...
Страница 107: ...107 CDHF SVU01C EN ...
Страница 108: ...CDHF SVU01C EN 108 ...
Страница 109: ...109 CDHF SVU01C EN ...
Страница 110: ...CDHF SVU01C EN 110 ...
Страница 111: ...111 CDHF SVU01C EN ...
Страница 112: ...CDHF SVU01C EN 112 ...
Страница 113: ...113 CDHF SVU01C EN ...
Страница 114: ...CDHF SVU01C EN 114 ...
Страница 115: ...115 CDHF SVU01C EN ...