61
CDHF-SVU01C-EN
Control System
Components
External Chilled Water
Setpoint (ECWS)
The External Chilled Water Setpoint
allows the chilled water setpoint to
be changed from a remote location.
The External Chilled Water Setpoint
is found on 1A16 J2-5 to J2-6
(Ground). 2-10 vdc and 4-20 ma
corresponds to a default 34°F to 65°F
(-17.8 to 18.3°C) adjustable via service
tool.
External Current Limit Setpoint
The External Current Limit is an
option that allows the current limit
setpoint to be changed from a remote
location. The External Limit Setpoint
is found on 1A16 J2-2 to J2-3
(ground), 2-10 vdc and 4-20 ma each
correspond to a 40 to 100 percent
RLA range. UCP limits the maximum
ECLS to 100 percent.
Default 40 to 100%, adjustable via
service tool.
WPSR (WFC Water Pressure Sensing Option)
1A21 Optional Dual
WPSR = WFC
Signal #1
Evaporator Differential
Not for field use
Analog Input or output
Water Pressure
Module
1A21 Optional Dual
WPSR = WFC
Signal #2
Condenser Differential
Not for field use
Analog Input or output
Water Pressure
Module
Module Characteristics
1A1, 1A2 Power Supply :
Unit Control Power Supply Module
Converts 27 vac to 24 vdc.
Power Input Voltage: 23VRMS
minimum, 27VRMS Nominal,
30VRMS maximum
Frequency: 50-60 Hz
Current: Full load 27 VAC – 4.30 A
(RMS)
Inrush 27 VAC (RMS) ~ 30A (RMS)
Power Output: Class II Voltage 24
VDC, Rated Current 2.44 Amps.
Fused at 3 amps
(FUS01513)
1A3, 1A5, 1A10 Dual Relay Output
modules :
Relay #1 J2-1 NO, J2-2 NC, J2-3
common
Relay #2 J2 4 NO, J2-5 NC, J2-6
common
Relay Outputs at 120 VAC: 7.2 Amps
resistive, 2.88 Amps pilot duty, 1/3
HP, 7.2 FLA at 240 VAC: 5 Amps
general purpose, 14 - 26 AWG with a
maximum of two 14 AWG.
Power, 24 +/- 10 percent VDC, 60 mA
maximum, Trane IPC3 protocol. J1-1
+24VDC, J1-2 Ground, J1-3 COMM +
J1-4 COMM -
1A4, 1A6 Dual High Voltage Binary
input module:
Binary Input Signal #1 J2-1 to 2
Binary Input Signal #2 J3-1 to 2
High Voltage Binary Input: Off
Voltage: 0 to 40 VAC RMS , On
Voltage: 70 to 276 VAC RMS
Input is not polarity sensitive (Hot
and neutral can be switched), Input
impedance 130K to 280K ohms
14 - 26 AWG with a maximum of two
14 AWG
Power, 24 +/- 10 percent VDC, 20 mA
maximum. Trane IPC3 protocol. J1-1
+24VDC, J1-2 Ground, J1-3 COMM +,
J1-4 COMM -
1A7 High Power Output Module
Relay contacts at 120 VAC:
16 amps resistive, 6.4 amps,pilot
duty, 1 HP
J2-14-26 awg witha maximum of two
14 awg
J2-1 J2-2 no, J2-3 NC, J2-4 com
Содержание CenTraVac Duplex CDHE
Страница 1: ...CDHF SVU01C EN X39640670030 Operation Maintenance Duplex CDHF CDHG Water Cooled CenTraVac With CH530 ...
Страница 9: ...9 CDHF SVU01C EN General Information Figure 2 General Duplex unit components 2 stage compressor ...
Страница 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Страница 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Страница 53: ...53 CDHF SVU01C EN Control System Components ...
Страница 65: ...65 CDHF SVU01C EN Control System Components ...
Страница 66: ...CDHF SVU01C EN 66 Control System Components ...
Страница 88: ...CDHF SVU01C EN 88 Figure 35 Return CWR Figure 36 Constant CWR Machine Protection and Adaptive Control ...
Страница 104: ...CDHF SVU01C EN 104 ...
Страница 105: ...105 CDHF SVU01C EN ...
Страница 106: ...CDHF SVU01C EN 106 ...
Страница 107: ...107 CDHF SVU01C EN ...
Страница 108: ...CDHF SVU01C EN 108 ...
Страница 109: ...109 CDHF SVU01C EN ...
Страница 110: ...CDHF SVU01C EN 110 ...
Страница 111: ...111 CDHF SVU01C EN ...
Страница 112: ...CDHF SVU01C EN 112 ...
Страница 113: ...113 CDHF SVU01C EN ...
Страница 114: ...CDHF SVU01C EN 114 ...
Страница 115: ...115 CDHF SVU01C EN ...