44
BCXC-SVX01A-EN
Maintenance
Maintenance
Procedures
Table M-MP-2. BCHC/BCVC Fan, Filter, & Mixing Box General Data
Unit Size
12
18
24
36
54
72
90
nominal cfm
400
600
800
1200
1800
2400
3000
airflow
minimum cfm
250
375
500
750
1125
1500
1875
maximum cfm
500
675
1000
1600
2400
3000
4000
Fan Data
fan wheel dia., in.
9.5 x 4.5
9.5 x 4.5
9.5 x 4.5
9.5 x 4.5
9.5 x 4.5
9.5 x 4.5
9.5 x 4.5
max rpm
2300
2300
1800
1800
1500
1500
1500
motor hp
0.33-1.0
0.33-1.0
0.33-1.0
0.33-1.5
0.33-2.0
0.33-3.0
0.33-3.0
Unit Flat Filter
qty. - size, in.
1 - 12x 24
1 - 12x 24
1 - 16x 25
2 - 16x 20
1 - 20x 20
3 - 16x 25
2 - 20x 25
1 - 20x 25
1 - 16x 25
area, sq. ft.
2.000
2.000
2.778
4.444
5.556
6.250
8.333
velocity, ft./min.
200
300
288
270
324
384
360
Angle Filter
qty. - size, in.
2 - 12x24
2 - 12x24
2 - 12x24
2 - 20x20
4 - 16x20
4- 16x20
4- 20x20
area, sq. ft.
4.000
4.000
4.000
5.556
8.889
8.889
11.111
velocity, ft./min.
100
150
200
216
203
270
270
Bottom/Top Access Filter Box
qty. - size, in.
1 - 12x20
1 - 12x24
1 - 16x25
1 - 16x20
1 - 16x20
1 - 20x25
2 - 16x25
1 - 16x16
1 - 20x20
1 - 20x20
1 - 14x25
area, sq. ft.
1.7
2.0
2.8
4.0
5.0
6.3
8.0
velocity, ft./min.
240
300
288
300
360
384
375
Mixing Box
damper opening width, in.
15.5
19.5
19.5
31.5
31.5
31.5
31.5
damper opening height, in.
7
7
7
7
12.75
12.75
12.75
area, sq. ft.
0.753
0.948
0.948
1.531
2.789
2.789
2.789
velocity, ft./min.
531
633
844
784
645
861
1076
Note: Minimum airflow limits apply to units with hot water or electric heat only. There is no minimumairflow limit on cooling on units. Maximum airflow limits are to help prevent
moisture carryover.
Table M-MP-3. BCHC/BCVC Piping Package
Waterflow Limits
Piping
Size
gpm
1
/
2
”
8.6
3
/
4
”
19.3
1”
34.3
1
1
/
4
”
53.5
Note: Trane recommends these maximum gpms to help
prevent erosion and/or noise problems. However lower
gpms may be necessary, depending on the
systemdesign, to avoid exceeding close-off pressure
limit of the control valve.