![Trane BCHC Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/trane/bchc/bchc_installation-and-operation-manual_1149595014.webp)
14
BCXC-SVX01A-EN
Dimensions
and Weights
Installation
High-Capacity Hydronic Coil Connection
Sizes, in.
Unit
Size
2-row
4-row
6-row
12
0.625
0.625
0.625
18
0.625
0.625
0.625
24
0.750
0.750
0.750
36
0.750
0.750
0.750
54
1.125
1.125
1.125
72
1.125
1.125
1.125
90
1.125
1.125
1.125
Hydronic Coil Connection Sizes, in.
Unit
Size
1-row
2-row
4-row
6-row
12
0.750
0.750
0.750
0.750
18
0.750
0.750
0.750
0.750
24
0.875
0.875
0.875
0.875
36
0.875
0.875
0.875
0.875
54
1.125
1.375
1.375
1.375
72
1.125
1.375
1.375
1.375
90
1.125
1.375
1.625
1.625
Coil Connections
Steam Coil
Steam Coil Box Dimensions and Weights, in-lbs.
Unit
Coil Connections, NPT
Size
H
W
A
B
C
Weight
Supply
Return
12
14.00
24.00
12.06
18.04
2.98
34
1.0
0.75
18
14.00
28.00
12.06
22.04
2.98
37
1.0
0.75
24
18.00
28.00
16.06
22.04
2.98
40
1.5
1.00
36
18.00
40.00
16.06
34.04
2.98
48
1.5
1.00
54
22.00
40.00
20.06
34.04
2.98
50
2.0
1.00
72
22.00
48.00
20.06
42.04
2.98
56
2.0
1.00
90
28.00
48.00
26.06
40.04
3.98
63
2.5
1.25
ACCESS PANEL
FILTER ACCESS
HEA
TING COIL
21.00
0.97
0.97
H A
B
W
C
C
NOTES:
1. FILTER ACCESS & ACCESS PANEL LOCATED ON BOTH
SIDES.
2. WEIGHT INCLUDES CABINET WITH AVERAGE FILTER,
BUT DOES NOT INCLUDE COIL WEIGHT. SEE GENERAL
DATA SECTION FOR COIL WEIGHTS.
DX Coil Connection Sizes, in. O.D.
Unit
Size
suction
liquid
12
1
/
2
1
/
2
18
1
/
2
1
/
2
24
7
/
8
1
/
2
36
7
/
8
1
/
2
54
7
/
8
1
/
2
72
7
/
8
1
/
2
90
1
1
/
4
1
/
2
Note: The DX coil is equipped with a single distributor. Do
not manifold two, independent refrigeration circuits into
a single-circuited DX (evaporator) coil.