background image

3

 

18-GJ11D1-2

Pre-installation Instructions

1.  Read all instructions before installing UV lamp kit.

2.  Avoid touching the lamp with bare hands as skin oils can ac-

celerate future glass soiling and degrade the lamp performance. 
Wipe the lamp with a clean cloth and rubbing alcohol or glass 
cleaner after handling. 

2.  Disconnect all power to the air handler.

WARNING

!

HAZARDOUS VOLTAGE! 

Multiple power sources 

may be present. Disconnect all electrical power, including 
remote disconnects, before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be inadver-
tently energized. Failure to disconnect power before servic-
ing could result in death or serious injury.

IMPORTANT:  The Right side lamp bracket must be installed before 
installing the ballast assembly.

IMPORTANT:  The lamp brackets and the ballast assembly are provided 
with aggressive adhesive on back. The adhesive has a peel-off liner. 
Do not remove the liner until these items have been placed into unit and 
proper mounting locations within the unit have been confirmed.                                                          

IMPORTANT:  The two lamp brackets are not symmetrical. One is 
marked Right and the other is marked Left. These markings apply to an 
air handler in the vertical upflow configuration (with V-shaped coil orien-
tation).  It is very important that the right side and left side brackets are 
placed on the proper side so that UV light is directed toward the center 
of the coil. Further references to left and right side brackets, top, and bot-
tom in this document assume upflow air handler configuration. For other 
configurations see the illustration on page 4 for proper bracket location.

NOTE:  Use isopropyl alcohol to thoroughly clean and dry the surfaces 
of the inside coil compartment wall in the areas where the lamp brackets 
and ballast assembly will be permanently mounted.

NOTE:  For new air handler installations, if a UV lamp kit is installed, it 
is recommended to remove the coil and install the lamp brackets before 
installing the air handler. 

Right

Left

End views 

(Front of unit)

Содержание BAYUVCLK001

Страница 1: ...ep tible to deterioration by the UV C lamp shall be shielded from direct exposure to the light This kit was designed with this consideration and the reflectors must be in place In addition UV C radiat...

Страница 2: ...h and rubbing alcohol or glass cleaner after handling WARNING Hazardous Voltage and Exposure to Ultraviolet Radiation This product contains components that emit high intensity ultraviolet UV C radiati...

Страница 3: ...not remove the liner until these items have been placed into unit and proper mounting locations within the unit have been confirmed IMPORTANT The two lamp brackets are not symmetrical One is marked Ri...

Страница 4: ...Bkt Upflow Horizontal Right Downflow Horizontal Left Left Bkt Ballast Right Bkt Left Bkt Ballast Right Bkt Left Bkt Ballast Right Bkt Left Bkt Ballast UV Lamp Brackets and Ballast locations for Air H...

Страница 5: ...Measure7 5inchesabovethecrossbarandmake a mark on the inside of the air handler cabinet use a screwdriver or other metal object to scribe line STEP 4 Draw a level line to the back of the air handler c...

Страница 6: ...ompartment inner wall STEP 8 Cut the cable tie on the left side lamp bracket assembly Slide the lamp and reflector assembly out of the lamp bracket as shown STEP 9 Measure 7 5 inches above the cross b...

Страница 7: ...liner until proper mounting locations within the unit have been confirmed NOTE Use isopropyl alcohol to thoroughly clean and dry the surfaces of the inside coil compartment wall in the areas where th...

Страница 8: ...lugs The tie prevents strain on the splices STEP 12 Connect the ballast assembly in series with the high voltage leads Ballast assembly with power plugs Unconnected From Blower Compartment From Blower...

Страница 9: ...g on the air handler cross bar The notch of the ballast assembly will slide into the ridge of the air handler Ensure a solid fit before removing peel off liner and exposing the adhesive back Note Be c...

Страница 10: ...ng UV Lamp wiring connections NOTE If the coil was removed before installation replace the coil before continuing with the kit installation STEP 16 Install the left and right side lamps and reflectors...

Страница 11: ...cure the grounding wire in place Then place a second factory supplied nut onto the stud and tighten in place also STEP 19 Support the lamp and place the pin connector on the lamp The connector is posi...

Страница 12: ...ers to extend the life of the lamp This accessory kit will disable the lamp during the heating season kit is purchased separately STEP 23 Use the provided cable ties to secure all wires STEP 24 Apply...

Страница 13: ...V appliance upon opening or removal WARNING STEP 26 Remove the heater panel STEP 27 Set the system comfort control to OFF and restore power STEP 28 Use an ammeter to check for current flow on the high...

Страница 14: ...the unit 2 Open the coil panel 3 Cut the cable tie and remove the plug from the lamp 4 Wearing soft cloth gloves and safety glasses use two hands and firmly grasp the lamp at nearest end 5 Remove the...

Страница 15: ...15 18 GJ11D1 2 Wiring Diagram...

Страница 16: ...ne 6200 Troup Highway Tyler TX 75707 12 10 Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specifications without noti...