background image

2

 

18-GJ11D1-2

LAMPS CONTAIN MERCURY!

 

Follow local and state 

guidelines for disposal of mercury bulbs.

CAUTION

!

SAFETY HAZARD! 

This information is for use by individu-

als having adequate backgrounds of electrical and mechanical 
experience. Any attempt to repair a central air conditioning 
product may result in personal injury and/or property dam-
age. The manufacturer or seller cannot be responsible for the 
interpretation of this information, nor can it assume any liability 
in connection with its use.

WARNING

!

PERSONAL INJURY HAZARD!

 

Disconnect input 

power before beginning installation. Professional installation 
required per NEC standards. The power supply to this ultravio-
let appliance must be disconnected before opening or servicing 
the unit. Any access panels or doors, within sight of the UV 
lamps, must be interlocked so as to disconnect power to the 
UV appliance upon opening or removal.

WARNING

!

IMPORTANT -  Avoid touching the lamp with bare hands as skin oils can ac-
celerate future glass soiling and degrade the lamp performance. Wipe the lamp 
with a clean cloth and rubbing alcohol or glass cleaner after handling. 

WARNING

!

HAZARDOUS VOLTAGE AND ExPOSURE TO 
ULTRAVIOLET RADIATION! 

This product contains 

components that emit high-intensity ultraviolet (UV-C) radiation 
which can be harmful to unprotected eyes and skin. Disconnect 
all electrical power, including remote disconnects, before ser-
vicing. Follow proper lockout/tagout procedures to ensure the 
power can not be inadvertently energized. Failure to disconnect 
power before servicing could result in death or serious injury.

HAZARDOUS VAPORS! 

If UV bulbs are broken, an ap-

propriate respirator should be considered to prevent inhalation 
of mercury vapors. Failure to use a respirator could result in 
death or serious injury.

BROKEN GLASS! 

Bulbs are fragile and can be easily 

broken. Always use gloves and eye protection when handling 
these bulbs. Failure to handle bulbs properly may result in 
minor to moderate injury. 

WARNING

!

CAUTION

!

WARNING

!

HAZARDOUS VOLTAGE! 

Multiple power sources may 

be present. Disconnect all electrical power, including remote 
disconnects, before servicing. Follow proper lockout/tagout 
procedures to ensure the power can not be inadvertently ener-
gized. Failure to disconnect power before servicing could result 
in death or serious injury.

Safety Information

Содержание BAYUVCLK001

Страница 1: ...ep tible to deterioration by the UV C lamp shall be shielded from direct exposure to the light This kit was designed with this consideration and the reflectors must be in place In addition UV C radiat...

Страница 2: ...h and rubbing alcohol or glass cleaner after handling WARNING Hazardous Voltage and Exposure to Ultraviolet Radiation This product contains components that emit high intensity ultraviolet UV C radiati...

Страница 3: ...not remove the liner until these items have been placed into unit and proper mounting locations within the unit have been confirmed IMPORTANT The two lamp brackets are not symmetrical One is marked Ri...

Страница 4: ...Bkt Upflow Horizontal Right Downflow Horizontal Left Left Bkt Ballast Right Bkt Left Bkt Ballast Right Bkt Left Bkt Ballast Right Bkt Left Bkt Ballast UV Lamp Brackets and Ballast locations for Air H...

Страница 5: ...Measure7 5inchesabovethecrossbarandmake a mark on the inside of the air handler cabinet use a screwdriver or other metal object to scribe line STEP 4 Draw a level line to the back of the air handler c...

Страница 6: ...ompartment inner wall STEP 8 Cut the cable tie on the left side lamp bracket assembly Slide the lamp and reflector assembly out of the lamp bracket as shown STEP 9 Measure 7 5 inches above the cross b...

Страница 7: ...liner until proper mounting locations within the unit have been confirmed NOTE Use isopropyl alcohol to thoroughly clean and dry the surfaces of the inside coil compartment wall in the areas where th...

Страница 8: ...lugs The tie prevents strain on the splices STEP 12 Connect the ballast assembly in series with the high voltage leads Ballast assembly with power plugs Unconnected From Blower Compartment From Blower...

Страница 9: ...g on the air handler cross bar The notch of the ballast assembly will slide into the ridge of the air handler Ensure a solid fit before removing peel off liner and exposing the adhesive back Note Be c...

Страница 10: ...ng UV Lamp wiring connections NOTE If the coil was removed before installation replace the coil before continuing with the kit installation STEP 16 Install the left and right side lamps and reflectors...

Страница 11: ...cure the grounding wire in place Then place a second factory supplied nut onto the stud and tighten in place also STEP 19 Support the lamp and place the pin connector on the lamp The connector is posi...

Страница 12: ...ers to extend the life of the lamp This accessory kit will disable the lamp during the heating season kit is purchased separately STEP 23 Use the provided cable ties to secure all wires STEP 24 Apply...

Страница 13: ...V appliance upon opening or removal WARNING STEP 26 Remove the heater panel STEP 27 Set the system comfort control to OFF and restore power STEP 28 Use an ammeter to check for current flow on the high...

Страница 14: ...the unit 2 Open the coil panel 3 Cut the cable tie and remove the plug from the lamp 4 Wearing soft cloth gloves and safety glasses use two hands and firmly grasp the lamp at nearest end 5 Remove the...

Страница 15: ...15 18 GJ11D1 2 Wiring Diagram...

Страница 16: ...ne 6200 Troup Highway Tyler TX 75707 12 10 Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specifications without noti...