![Trane BACnet BCI-R Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/trane/bacnet-bci-r/bacnet-bci-r_integration-manual_1150310008.webp)
8
BAS-SVP09B-EN
Configuring the BCI-R
To connect to Tracer TU:
1.
Connect the USB cable directly from the laptop to the BCI-R, or to an equipment control panel
USB port connected to the controller.
Important:
If using a PC with multiple USB ports, connect by using the same process outlined
below for the same piece of equipment. This is normal operation. Observe existing
USB standards for cable length. (For more information go to informational Web
sites, such as
http://www.USB.org
.)
2. Click either the
Tracer TU
desktop icon or the
Tracer TU
program item in the Tracer TU
group
on the
Start
menu.
The Tracer TU splash screen appears briefly followed by the
Connect
dialog box.
Figure 4.
Connect dialog box
3. Select the
Direct Connection (USB cable)
radio button if it is not already selected.
4. Click the
Connect
button and the
Unit
Summary
page will appear after successful connection.
To configure the BCI-R controller:
1.
Select the
Controller Settings Utility
tab from the vertical tab set located on the right side of the
TU window.
Note:
The content of this screen is based on the type of controller that is connected and the
system protocol used to communicate with the controller.
2. Enter a meaningful name for the controller.
3. Click the
Controller Units
expanding box label to display its contents.
4. Select the preferred units of measure for data communicated across the BACnet link.
5. Click the
Protocol
expanding box heading to display its contents.
6. Select the preferred
Baud Rate
in the drop-down list box.
7.
If a software Device ID is required, check the
Use Software Device ID
box and enter a BACnet
Device ID.
8. Click
Save
.
Содержание BACnet BCI-R