Object Data Points and Diagnostic Data Points
Analog Input, 8
Exhaust Fan Speed Command
Indicates the unit commanded exhaust fan speed.
Multi-State Input, 38
Exhaust Fan Status
Indicates the commanded state of the exhaust fan.
Analog Output, 33
Exhaust or Return Fan Configuration
Sets the equipment exhaust or return fan type.
Analog Input, 90
Exhaust or Return Fan Type
Describes the exhaust or return fan type installed in the unit.
Analog Input, 6
Filter Runtime Hours
Indicates the number of hours air has flowed through the filter.
Analog Value, 1
Filter Runtime Hours Setpoint
The setpoint value used by the filter run hours calculation.
Binary Output, 13
Filter Timer Reset
Command the unit to reset the accumulated filter run hours.
Analog Output, 20
Heat Capacity Enable Setpoint BAS
BAS supplied heating demand limit capacity setpoint value.
Multi-State Output, 8
Heat Cool Mode Request BAS
Command the unit to a specific application mode.
Binary Output, 5
Heat Lockout Command
Command the unit to prevent heating operation.
Multi-State Input, 29
Heat Output 1
Indicates the commanded state of heating output 1.
Multi-State Input, 30
Heat Output 2
Indicates the commanded state of heating output 2.
Multi-State Input, 31
Heat Output 3
Indicates the commanded state of heating output 3.
Multi-State Input, 32
Heat Output 4
Indicates the commanded state of heating output 4.
Analog Input, 2
Heat Primary Capacity Status
Indicates the unit primary heating capacity being utilized.
Analog Input, 3
Heat Secondary Capacity Status
Indicates the unit secondary heating capacity being utilized.
Multi-State Input, 23
Heating Setpoint Source
Indicates the source of the space heating setpoint.
Binary Output, 19
Lead-Lag Enable Command
Command the unit compressor startup order
Analog Input, 25
Mixed Air Temperature
The mixed air temperature value from a unit-mounted sensor.
Binary Output, 20
Morning Warmup Enable Command
Command the unit morning warmup operation
Analog Output, 4
Morning Warmup Setpoint BAS
BAS supplied temperature setpoint used in morning warmup mode.
Analog Input, 54
Morning Warmup Temperature Setpoint Active
The air temperature setpoint used during morning warmup mode.
Multi-State Output, 7
Occupancy Request
Command the unit into an occupancy mode.
Multi-State Input, 20
Occupancy Status
Indicates the current occupancy mode of the unit.
Analog Output, 29
Occupied Offset
Offset used to calculate setpoints in occupied mode.
Analog Input, 11
Outdoor Air Damper Position Status
Indicates the unit outdoor air damper position.
Analog Input, 34
Outdoor Air Flow Active
Outdoor airflow utilitzed by the unit.
Analog Input, 20
Outdoor Air Humidity Active
The outdoor air humidity value used for unit control.
Analog Output, 15
Outdoor Air Humidity BAS
BAS supplied outdoor air humidity sensor value.
Analog Input, 57
Outdoor Air Minimum Flow Setpoint Active
The minimum outdoor airflow setpoint being utilized by the unit.
Analog Output, 16
Outdoor Air Minimum Flow Setpoint BAS
BAS supplied minimum outdoor airflow setpoint.
Analog Input, 18
Outdoor Air Temperature Active
The outdoor air temperature currently used for unit control.
Analog Output, 14
Outdoor Air Temperature BAS
BAS supplied outdoor air temperature sensor value.
Multi-State Input, 43
Outdoor Damper Status
Indicates the operating state of the outdoor damper.
Analog Output, 34
Power Exhaust Enable Setpoint BAS
BAS supplied power exhaust enabled setpoint value.
Analog Input, 82
Preheat Type
Describes the heating type installed in the unit.
Multi-State Input, 35
Primary Filter Status
Indicates the primary filter media state.
Analog Input, 5
Reheat Capacity Status
Indicates the unit reheat heating capacity being utilized.
Analog Input, 83
Reheat Type
Describes the reheat type installed in the unit.
Binary Output, 14
Reset Diagnostic
Command the unit to reset and clear diagnostics.
Analog Input, 26
Return Air Temperature
The return air temperature value from a unit-mounted sensor.
Analog Input, 97
RTAM Major Version
Major software version number of the RTAM module
Analog Input, 98
RTAM Minor Version
Minor software version number of the RTAM module
Analog Input, 105
RTCM Major Version
Major software version number of the RTCM module
Analog Input, 106
RTCM Minor Version
Minor software version number of the RTCM module
Analog Input, 101
RTDM Major Version
Major software version number of the RTDM module
Table 11. All Object Types Sorted by Object Name (
Refer to previous tables for detailed descriptions of objects
) (continued)
Object Identifier
Object Name
Description