Object Data Points and Diagnostic Data Points
Table 12. Notification Classes
Notification Class
Severity
Class 001
Critical
Class 002
Service Required
Class 003
Advisory
Class 004
Information
Table 13. Diagnostic Objects Sorted by Object Name
Object Identifier
Binary Input (BI)
Object Name
Description
Notification Class
Binary Input, 59
Diagnostic: Auto - SA High Press Limit
Diagnostic: Auto - SA High Press Limit
002 – Service Required
Binary Input, 271
Diagnostic: CO2 Low Limit Setpoint Fault
Diagnostic: CO2 Low Limit Setpoint Fault
004 – Information
Binary Input, 83
Diagnostic: CO2 Sensor Failure
Diagnostic: CO2 Sensor Failure
002 – Service Required
Binary Input, 257
Diagnostic: CO2 Setpoint Failure
Diagnostic: CO2 Setpoint Failure
004 – Information
Binary Input, 45
Diagnostic: Coil Temp Sensor 1 Fail
Diagnostic: Coil Temp Sensor 1 Fail 1
002 – Service Required
Binary Input, 46
Diagnostic: Coil Temp Sensor 2 Fail
Diagnostic: Coil Temp Sensor 2 Fail
002 – Service Required
Binary Input, 269
Diagnostic: Comp 1 Disable Input HPC
Diagnostic: Comp 1 Disable Input HPC
004 – Information
Binary Input, 244
Diagnostic: Comp 1 Disable Input LPC
Diagnostic: Comp 1 Disable Input LPC
004 – Information
Binary Input, 270
Diagnostic: Comp 2 Disable Input HPC
Diagnostic: Comp 2 Disable Input HPC
004 – Information
Binary Input, 245
Diagnostic: Comp 2 Disable Input LPC
Diagnostic: Comp 2 Disable Input LPC
004 – Information
Binary Input, 47
Diagnostic: Compressor 1 HPC Lockout
Diagnostic: Compressor 1 HPC Lockout
001 – Critical
Binary Input, 43
Diagnostic: Compressor 1 LPC Lockout
Diagnostic: Compressor 1 LPC Lockout
001 – Critical
Binary Input, 48
Diagnostic: Compressor 2 HPC Lockout
Diagnostic: Compressor 2 HPC Lockout
001 – Critical
Binary Input, 44
Diagnostic: Compressor 2 LPC Lockout
Diagnostic: Compressor 2 LPC Lockout
001 – Critical
Binary Input, 297
Diagnostic: DCV Min Position at Minimum Fan Speed Diagnostic: DCV Min Position at Minimum Fan
Speed
004 – Information
Binary Input, 293
Diagnostic: DCV Min Position Setpoint Fail
Diagnostic: DCV Min Position Setpoint Fail
004 – Information
Binary Input, 252
Diagnostic: Default Defrost Flag
Diagnostic: Default Defrost Flag
004 – Information
Binary Input, 287
Diagnostic: Defrost Default Mode Ckt 1
Diagnostic: Defrost Default Mode Ckt 1
004 – Information
Binary Input, 283
Diagnostic: Defrost Default Mode Ckt 2
Diagnostic: Defrost Default Mode Ckt 2
004 – Information
Binary Input, 125
Diagnostic: Dehumid Setpoint Failure
Diagnostic: Dehumid Setpoint Failure
002 – Service Required
Binary Input, 248
Diagnostic: Demand Defrost Fault A
Diagnostic: Demand Defrost Fault A
004 – Information
Binary Input, 284
Diagnostic: Demand Defrost Fault A Ckt 1
Diagnostic: Demand Defrost Fault A Ckt 1
004 – Information
Binary Input, 280
Diagnostic: Demand Defrost Fault A Ckt 2
Diagnostic: Demand Defrost Fault A Ckt 2
004 – Information
Binary Input, 249
Diagnostic: Demand Defrost Fault B
Diagnostic: Demand Defrost Fault B
004 – Information
Binary Input, 285
Diagnostic: Demand Defrost Fault B Ckt 1
Diagnostic: Demand Defrost Fault B Ckt 1
004 – Information
Binary Input, 281
Diagnostic: Demand Defrost Fault B Ckt 2
Diagnosti: Demand Defrost Fault B Ckt 2
004 – Information
Binary Input, 250
Diagnostic: Demand Defrost Fault C
Diagnostic: Demand Defrost Fault C
004 – Information
Binary Input, 286
Diagnostic: Demand Defrost Fault C Ckt 1
Diagnostic: Demand Defrost Fault C Ckt 1
004 – Information
Binary Input, 282
Diagnostic: Demand Defrost Fault C Ckt 2
Diagnostic: Demand Defrost Fault C Ckt 2
004 – Information
Binary Input, 251
Diagnostic: Demand Defrost Fault D
Diagnostic: Demand Defrost Fault D
004 – Information
Binary Input, 298
Diagnostic: Design Min Position at Midpoint Fan Speed
Fail
Diagnostic: Design Min Position at Midpoint Fan
Speed Fail
004 – Information
Binary Input, 296
Diagnostic: Design Min Position at Minimum Fan Speed
Fail
Diagnostic: Design Min Position at Minimum Fan
Speed Fail
004 – Information
Binary Input, 294
Diagnostic: Design Min Position Setpoint Fail
Diagnostic: Design Min Position Setpoint Fail
004 – Information
Binary Input, 76
Diagnostic: Dirty Filter
Diagnostic: Dirty Filter
003 – Advisory
Binary Input, 289
Diagnostic: Discharge Air Heat Setpoint Failure
Diagnostic: Discharge Air Heat Setpoint Failure
004 – Information
Binary Input, 264
Diagnostic: Economizer Actuator Fault
Diagnostic: Economizer Actuator Fault
004 – Information