Trane BACnet BCI-R Скачать руководство пользователя страница 25

BAS-SVP09B-EN

25

Object Data Points and Diagnostic Data Points

      

Analog Output, 33

Exhaust or Return Fan Configuration

Sets the equipment exhaust or 

return fan type.

NA

1.0 to 255

NA

Analog Output, 34

Power Exhaust Enable Setpoint BAS

BAS supplied power exhaust 

enabled setpoint value.

Percent (98)

0.0 to 100

NA

Table 4.

Analog Input 

Object Identifier

Object Name

Description

Units of Measure 

IP/SI

Analog Input, 1

Cooling Capacity Status

Indicates the unit cooling capacity being utilized.

Percent (98)

Analog Input, 2

Heat Primary Capacity Status

Indicates the unit primary heating capacity being 

utilized.

Percent (98)

Analog Input, 3

Heat Secondary Capacity Status

Indicates the unit secondary heating capacity being 

utilized.

Percent (98)

Analog Input, 5

Reheat Capacity Status

Indicates the unit reheat heating capacity being 

utilized.

Percent (98)

Analog Input, 6

Filter Runtime Hours

Indicates the number of hours air has flowed through 

the filter.

Hours (71)

Analog Input, 7

Supply Fan Speed Command

Indicates the unit commanded supply fan speed.

Percent (98)

Analog Input, 8

Exhaust Fan Speed Command

Indicates the unit commanded exhaust fan speed.

Percent (98)

Analog Input, 9

Exhaust Damper Position Status

Indicates the unit exhaust damper position.

Percent (98)

Analog Input, 11

Outdoor Air Damper Position Status

Indicates the unit outdoor air damper position.

Percent (98)

Analog Input, 15

Space Temperature Active

The space temperature currently used for unit control. Fahrenheit (64)

Celcius (62)

Analog Input, 16

Space Humidity Active

The space humidity value from a unit-mounted control. Percent-relative-humidity (29)

Analog Input, 18

Outdoor Air Temperature Active

The outdoor air temperature currently used for unit 

control.

Fahrenheit (64)

Celcius (62)

Analog Input, 20

Outdoor Air Humidity Active

The outdoor air humidity value used for unit control.

Percent-relative-humidity (29)

Analog Input, 24

Discharge Air Temperature Active

The discharge air temperature currently used for unit 

control.

Fahrenheit (64)

Celcius (62)

Analog Input, 25

Mixed Air Temperature

The mixed air temperature value from a unit-mounted 

sensor.

Fahrenheit (64)

Celcius (62)

Analog Input, 26

Return Air Temperature

The return air temperature value from a unit-mounted 

sensor.

Fahrenheit (64)

Celcius (62)

Analog Input, 28

Duct Static Pressure Active

Duct static air pressure value currently being used for 

unit control.

0.0 inH2O = 0 Pa (53)

7.9 inH2O = 1967 Pa

Analog Input, 31

Space Static Air Pressure Active

Space static air pressure value being used for unit 

control.

-0.67 inH2O = -167 Pa (53)

0.67 inH2O = 167 Pa

Analog Input, 32

Space CO

2

 Concentration Active

Space CO

2

 concentration being used for unit control.

Part-per-million (96)

 

mg/kg

Analog Input, 34

Outdoor Air Flow Active

Outdoor airflow utilitzed by the unit.

0 CFM = 0 l/s (litres/second)

65535 CFM = 30929 l/s (87)

Analog Input, 48

Duct Static Pressure Setpoint Active

Duct static pressure setpoint value being used for unit 

control.

0.0 inH2O = 0 Pa (53)

5.1 inH2O = 1270 Pa

Analog Input, 50

Space Temperature Setpoint Active

Space temperature setpoint value being used for unit 

control.

Fahrenheit (64)

Celcius (62)

Analog Input, 52

Discharge Air Temperature Setpoint Active

Discharge air temperature setpoint value being used 

for unit control.

Fahrenheit (64)

Celcius (62)

Analog Input, 54

Morning Warmup Temperature Setpoint 

Active

The air temperature setpoint used during morning 

warmup mode.

Fahrenheit (64)

Celcius (62)

Analog Input, 57

Outdoor Air Minimum Flow Setpoint Active

The minimum outdoor airflow setpoint being utilized by 

the unit.

0 CFM = 0 l/s (litres/second)

65000 CFM = 30676 l/s (87)

Analog Input, 58

Dehumidification High Limit Setpoint

Humidity setpoint value that starts dehumidification 

control.

Percent (98)

Analog Input, 61

Discharge Air Reheat Setpoint Active

Indicates the active supply air reheat temperature 

setpoint.

Fahrenheit (64)

Celcius (62)

Table 3.

Analog Output (continued)

Object Identifier Object Name

Description

Units of Measure

IP/SI

Valid Range

Refresh 

Rate 

(Sec.)

Содержание BACnet BCI-R

Страница 1: ...cautions in the literature and on the tags stickers and labels that are attached to the equipment March 2011 BAS SVP09B EN Integration Guide BACnet Communication Interface for ReliaTel Controllers BCI...

Страница 2: ...t the written permission of Trane Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change...

Страница 3: ...ration 13 BAS Unit Control 13 Initiating System Control 13 Output and Input Object Data Points 13 Periodic Update of BAS Values 14 BAS Communication Failure 14 Input Output Commands and Calculations 1...

Страница 4: ...ilding automation systems or components from different manufacturers to share information and control functions BACnet provides building owners the capability to connect various types of building cont...

Страница 5: ...not have defaults the BST or Tracer TU will display the device units of the controller to which it is connected Setting Addresses on the Rotary Switches There are three rotary switches on the front o...

Страница 6: ...Communication If using a wireless COMM interface WCI set the link select switch to IMC as shown in Figure 2 For wiring instructions refer to the BACnet Communication Interface for ReliaTel Controller...

Страница 7: ...tup Tool Online help is available by clicking the help icon located in upper right portion of the screen 1 Open the Tracer BACnet Setup Tool The Controller Settings screen appears Figure 3 2 In the Pr...

Страница 8: ...irect Connection USB cable radio button if it is not already selected 4 Click the Connect button and the Unit Summary page will appear after successful connection To configure the BCI R controller 1 S...

Страница 9: ...ystems p 10 BACnet Device ID Tracer SC uses the rotary dial settings MAC address to create the BACnet device ID The Tracer SC adds an SC rotary dial address and a link number to artificially create a...

Страница 10: ...rom the rotary dials Although 999 is possible from the dials the maximum allowed number by BACnet is 127 The Max Master is not adjustable in Trane SC systems For example if the MAC address is 101 and...

Страница 11: ...OK When the controller is cleared the Select Device Units message box appears 5 Click OK and then expand the Controller Units box on the Controller Settings screen 6 Select the units SI IP or Custom...

Страница 12: ...immediately often within one second Immediately after the points are created the device units are set and saved and appear on the Controller Units screen The values that correspond to the device unit...

Страница 13: ...quest Multi State Output 8 Heat Cool Mode Request BAS Multi State Output 2 Emergency Override Command Analog Output 2 Space Temperature Setpoint BAS Analog Output 29 Occupied Offset Analog Output 30 S...

Страница 14: ...pace CO2 Concentration BAS Space Humidity BAS Input Output Commands and Calculations This section will provide the following information about certain inputs and outputs that perform Filter timer and...

Страница 15: ...points are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoin...

Страница 16: ...ent Not illuminated The controller is off Link Tx Rx TX blinks green Data is being transferred received or transmitted RX blinks yellow Blinks at the data transfer rate when the unit receives data fro...

Страница 17: ...Cnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC 9 BACnet Building Controller B BC BACnet Operator Workstation B OWS BACnet Smart Actuator B SA BACnet Smart Sens...

Страница 18: ...nt Dynamic Device Binding A DM DDB A 9 Device Management Dynamic Device Binding B DM DDB B 9 Device Management Dynamic Object Binding B DM DOB B 9 Device Management List Manipulation B DM LM B 9 Devic...

Страница 19: ...bility Min_Pres Value Max_Pres_Value Time_Delay Notification _Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Yes Yes only user created ob...

Страница 20: ...set Elapsed_Active_Time Time_Of_Active_Time_Reset Priority_Array Relinquish_Default Minimum_On_Time Minimum_Off_Time Time_Delay Notification_Class Alarm_Value Event_Enable Acked_Transitions Notify_Typ...

Страница 21: ...lue Status_Flags Event_State Out_Of_Service Number_Of_States Object_Name Description State_Text Out_Of_Service Present_Value Reliability Priority_Array Relinquish_Default Time_Delay Notification_Class...

Страница 22: ...net Clause 7 10Base2 10Base5 10BaseT Fiber LonTalk Clause 11 Medium MS TP Master Clause 9 Baud Rate s 9600 19200 38400 and 76800 1 5 Nominal Baud Rate 9 MS TP Slave Clause 9 Baud Rate s Other Point to...

Страница 23: ...s support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes any character set Character Set Descriptions...

Страница 24: ...a 53 0 3 inH2O 74 Pa 0 3 to 0 2 NA Analog Output 10 Space Static Pressure BAS BAS supplied space static air pressure sensor value 0 67 inH2O 167 Pa 53 0 67 inH2O 167 Pa 0 67 to 0 67 900 Analog Output...

Страница 25: ...Discharge Air Temperature Active The discharge air temperature currently used for unit control Fahrenheit 64 Celcius 62 Analog Input 25 Mixed Air Temperature The mixed air temperature value from a uni...

Страница 26: ...Major software version number of the RTRM module NA Analog Input 92 RTRM Minor Version Minor software version number of the RTRM module NA Analog Input 93 RTOM Major Version Major software version num...

Страница 27: ...states apply to all equipment Multi State Input 2 Trane Unit Type General description of the equipment type classification 1 1 Heat 1 Cool 2 Heat Pump 3 Blower Coil 4 Unit Ventilator 5 Fan Coil 6 Roof...

Страница 28: ...tate Input 29 Heat Output 1 Indicates the commanded state of heating output 1 1 Off 2 On 3 Not Present Multi State Input 30 Heat Output 2 Indicates the commanded state of heating output 2 1 Off 2 On 3...

Страница 29: ...d clear diagnostics Inactive Inactive Normal Active Reset Binary Output 15 Dehumidification Enable Command Command the operating state of the dehumidification system Active Inactive Disabled Active Au...

Страница 30: ...Pressure Setpoint Failure Diagnostic SA Pressure Setpoint Failure 002 Service Required Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail 002 Service Requ...

Страница 31: ...Disable Input HPC 004 Information Binary Input 270 Diagnostic Comp 2 Disable Input HPC Diagnostic Comp 2 Disable Input HPC 004 Information Binary Input 271 Diagnostic CO2 Low Limit Setpoint Fault Dia...

Страница 32: ...e Command Command the operating state of the dehumidification system Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Analog Output 6 D...

Страница 33: ...morning warmup mode Multi State Output 7 Occupancy Request Command the unit into an occupancy mode Multi State Input 20 Occupancy Status Indicates the current occupancy mode of the unit Analog Output...

Страница 34: ...Setpoint Input Cooling temperature setpoint from space sensor module Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Analog Input 87 Spac...

Страница 35: ...n Binary Input 252 Diagnostic Default Defrost Flag Diagnostic Default Defrost Flag 004 Information Binary Input 287 Diagnostic Defrost Default Mode Ckt 1 Diagnostic Defrost Default Mode Ckt 1 004 Info...

Страница 36: ...od Dehumid Config Error Diagnostic Mod Dehumid Config Error 004 Information Binary Input 239 Diagnostic Morning Warmup Setpoint Fail Diagnostic Morning Warmup Setpoint Fail 002 Service Required Binary...

Страница 37: ...ail Diagnostic Space Pressure Setpoint Fail 002 Service Required Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail 002 Service Required Binary Input 30 Di...

Страница 38: ...cks Building Automation Control network BACnet and ANSI ASHRAE Standard 135 2008 An interoperable protocol developed specifically for the building controls industry The American National Standards Ins...

Страница 39: ...BAS SVP09B EN 39 Glossary...

Страница 40: ...Trane offers a broad portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and pro...

Отзывы: