22
BAS-SVP09B-EN
BACnet Data Points and Configuration Property Definitions
BACnet Protocol
Data Link Layer Options
Device Address Binding
Networking Options
Data Link Layer Description
Supported
Option
ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), Baud Rate(s)
BACnet IP, (Annex J)
9
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)(10Base2, 10Base5, 10BaseT, Fiber)
LonTalk, (Clause 11), Medium
MS/TP Master (Clause 9), Baud Rate(s): 9600, 19200, 38400, and 76800 @1.5% Nominal Baud Rate
9
MS/TP Slave (Clause 9), Baud Rate(s)
Other
Point-to-Point, EIA 232 (Clause 10), Baud Rate(s): 9600, 19200, 38400
Point-to-Point, Modem (Clause 10), Baud Rate(s): 9600, 19200, 38400
Device Address Binding
Supported
Static Device Binding Supported
No
Networking Descriptions
Supported
Option
Annex H, BACnet Tunneling
BACnet/IP Broadcast Management Device (BBMD)
9
Does the BBMD Support Registrations by Foreign Devices?
9
Router
9