BAS-SVP09B-EN
Object Data Points and Diagnostic Data Points
Binary Input, 22
Economizer Airside Enable Status
Indicates the status of the airside economizer
system.
Inactive = Disabled
Active = Enabled
Binary Input, 165
Alarm Relay Output Status
Indicates the state of the alarm relay on the
unit.
Inactive = De-energized
Active = Energized
Binary Input, 292
Supply Air Tempering Status
Indicates the status of the supply air
tempering function.
Inactive = Inactive
Active = Active
Table 10. Diagnostics, Binary Input
Object Identifier
Object Name
Description
Notification Class
Binary Input, 29
Diagnostic: Zone Temperature Sensor Failure
Diagnostic: Zone Temp Sensor Failure
002 – Service Required
Binary Input, 30
Diagnostic: Supply Air Temp Sensor Fail
Diagnostic: Supply Air Temp Sensor Fail
002 – Service Required
Binary Input, 32
Diagnostic: Outdoor Air Temperature Sensor Fail Diagnostic: OA Temperature Sensor Fail
002 – Service Required
Binary Input, 34
Diagnostic: Local Cool Setpoint Fail
Diagnostic: Local Cool Setpoint Fail
002 – Service Required
Binary Input, 35
Diagnostic: Local Zone Heat Setpoint Fail
Diagnostic: Local Zone Heat Setpoint Fail
002 – Service Required
Binary Input, 36
Diagnostic: SA Pressure Sensor Fail
Diagnostic: Supply Air Press Sensor Fail
002 – Service Required
Binary Input, 37
Diagnostic: Outdoor Humidity Sensor Failure
Diagnostic: OA Humidity Sensor Failure
002 – Service Required
Binary Input, 38
Diagnostic: Local Emergency Stop Initiated
Diagnostic: Local Emergency Stop Initiated
001 – Critical
Binary Input, 39
Diagnostic: Fan Failure
Diagnostic: Fan Failure
001 – Critical
Binary Input, 40
Diagnostic: Exhaust Fan Proving Failure
Diagnostic: Exhaust Fan Proving Failure
001 – Critical
Binary Input, 43
Diagnostic: Compressor 1 LPC Lockout
Diagnostic: Compressor 1 LPC Lockout
001 – Critical
Binary Input, 44
Diagnostic: Compressor 2 LPC Lockout
Diagnostic: Compressor 2 LPC Lockout
001 – Critical
Binary Input, 45
Diagnostic: Coil Temp Sensor #1 Fail
Diagnostic: Coil Temp Sensor 1 Fail 1
002 – Service Required
Binary Input, 46
Diagnostic: Coil Temp Sensor #2 Fail
Diagnostic: Coil Temp Sensor 2 Fail
002 – Service Required
Binary Input, 47
Diagnostic: Compressor 1 HPC Lockout
Diagnostic: Compressor 1 HPC Lockout
001 – Critical
Binary Input, 48
Diagnostic: Compressor 2 HPC Lockout
Diagnostic: Compressor 2 HPC Lockout
001 – Critical
Binary Input, 51
Diagnostic: Heat Failure
Diagnostic: Heat Failure
003 – Advisory
Binary Input, 54
Diagnostic: SA Pressure Setpoint Failure
Diagnostic: SA Pressure Setpoint Failure
002 – Service Required
Binary Input, 55
Diagnostic: Space Pressure Setpoint Fail
Diagnostic: Space Pressure Setpoint Fail
002 – Service Required
Binary Input, 56
Diagnostic: Space Pressure Sensor Fail
Diagnostic: Space Pressure Sensor Fail
002 – Service Required
Binary Input, 57
Diagnostic: Return Air Temp Sensor Fail
Diagnostic: Return Air Temp Sensor Fail
002 – Service Required
Binary Input, 58
Diagnostic: Return Air Humidity Sensor Fail
Diagnostic: Return Air Humidity Sensor Fail
002 – Service Required
Binary Input, 59
Diagnostic: Auto - SA High Press Limit
Diagnostic: Auto - SA High Press Limit
002 – Service Required
Binary Input, 74
Diagnostic: SA Temp Cool Setpoint Fail
Diagnostic: SA Temp Cool Setpoint Fail
002 – Service Required
Binary Input, 75
Diagnostic: SA Temp Heat Setpoint Fail
Diagnostic: SA Temp Heat Setpoint Fail
002 – Service Required
Binary Input, 76
Diagnostic: Dirty Filter
Diagnostic: Dirty Filter
003 – Advisory
Binary Input, 83
Diagnostic: CO2 Sensor Failure
Diagnostic: CO2 Sensor Failure
002 – Service Required
Binary Input, 86
Diagnostic: Velocity Press Sensor Fail
Diagnostic: Velocity Press Sensor Fail
002 – Service Required
Binary Input, 95
Diagnostic: Mixed Air Temp Sensor Failure
Diagnostic: Mixed Air Temp Sensor Failure
002 – Service Required
Binary Input, 106
Diagnostic: Space Humidity Sensor Fail
Diagnostic: Space Humidity Sensor Fail
002 – Service Required
Binary Input, 107
Diagnostic: Entering Evap Temp Sensor Fail
Diagnostic: Entering Evap Temp Sensor Fail
002 – Service Required
Binary Input, 123
Diagnostic: SA Reheat Setpoint Failure
Diagnostic: SA Reheat Setpoint Failure
002 – Service Required
Binary Input, 125
Diagnostic: Dehumid Setpoint Failure
Diagnostic: Dehumid Setpoint Failure
002 – Service Required
Binary Input, 147
Diagnostic: Maintenance Required
Diagnostic: Maintenance Required
002 – Service Required
Binary Input, 148
Diagnostic: Unit Communications Failure
Diagnostic: Unit Communications Failure
002 – Service Required
Binary Input, 151
Diagnostic: External Auto-Stop
Diagnostic: External Auto-Stop
004 – Information
Binary Input, 239
Diagnostic: Morning Warmup Setpoint Fail
Diagnostic: Morning Warmup Setpoint Fail
002 – Service Required
Binary Input, 242
Diagnostic: Min OA Flow Setpoint Fail
Diagnostic: Min OA Flow Setpoint Fail
002 – Service Required
Binary Input, 244
Diagnostic: Comp 1 Disable Input LPC
Diagnostic: Comp 1 Disable Input LPC
004 – Information
Binary Input, 245
Diagnostic: Comp 2 Disable Input LPC
Diagnostic: Comp 2 Disable Input LPC
004 – Information
Table 9.
Binary Input (continued)
Object Identifier
Object Name
Description
Object States