ARTC-SVX001B-EN
73
Code (hex)
Fault / Aux. code
Cause
What to do
9081
External fault 1 (Editable message
text) Programmable fault: 31.01
External event 1 source
31.02 External event 1 type
Fault in external device 1.
Check the external device. Check
setting of parameter
31.01 External
event 1 source
.
9082
External fault 2 (Editable message
text) Programmable fault: 31.03
External event 2 source
31.04 External event 2 type
Fault in external device 2.
Check the external device. Check
setting of parameter
31.03 External
event 2 source
.
9083
External fault 3 (Editable message
text) Programmable fault: 31.05
External event 3 source
31.06 External event 3 type
Fault in external device 3.
Check the external device. Check
setting of parameter
31.05 External
event 3 source
.
9084
External fault 4 (Editable message
text) Programmable fault: 31.07
External event 4 source
31.08 External event 4 type
Fault in external device 4.
Check the external device. Check
setting of parameter
31.07 External
event 4 source
.
9085
External fault 5 (Editable message
text) Programmable fault: 31.09
External event 5 source
31.10 External event 5 type
Fault in external device 5.
Check the external device. Check
setting of parameter
31.09 External
event 5 source
.
FA81
Safe torque off 1
Safe torque off function is active, ie.
STO circuit 1 is broken.
Check safety circuit connections. For
more information, see chapter The
Safe torque off function in the
Hardware manual of the drive and
description of parameter 31.22 STO
indication run/stop (page 183).
Check the value of parameter 95.04
Control board supply.
FA82
Safe torque off 2
Safe torque off function is active, ie.
STO circuit 2 is broken.
FF61
ID run
Motor ID run was not completed
successfully.
Check the nominal motor values in
parameter group
99 Motor data
.
Check that no external control
system is connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits
prevent the completion of the ID run.
Restore
parameters to default settings and
try again.
Check that the motor shaft is not
locked.
FF81
FB A force trip
A fault trip command has been
received through fieldbus adapter A.
Check the fault information provided
by the PLC.
FF8E
EFB force trip
A fault trip command has been
received through the embedded
fieldbus interface.
Check the fault information provided
by the PLC.