ARTC-SVX001B-EN
47
Chiller Performance Data
This manual uses a typical 120-ton air-cooled chiller
consisting of four modules with brazed plate
evaporators for example purposes. The model number
and a chiller’s precise electrical and refrigerant data
can be found on the chiller model nameplate. See
“Model Number and Coding,” p. 7
Table 9. Typical Manhattan™ air-cooled chiller specification for example purposes
Chiller System (four 30-ton air-cooled chiller modules) Model # TPACVMV0300D4-MM
Evaporator Type
brazed plate
Condenser Type
copper tube aluminum fin
Evaporator Flow
274 gpm
Evaporator Fluid
70/30 water/glycol
Entering Fluid Temperature
54 °F (12 °C)
Ambient Design Temperature
95 °F (35 °C)
Leaving Fluid Temperature
44 °F (7 °C)
Evaporator Pressure Drop
5.8 psi
Maximum Evaporator Operating
Pressure
650 psi (refrigerant side)
System Capacity
1,2274,000 btu/hr. (106.2 tons)
Refrigerant
R410A
Connections
6 in. roll grooved
Chiller Modules (4)
Compressors
two per module
Rated Load Amps
46 amps each
Horsepower
15
Total Full Load Amps
123 amps per module
Locked Rotor Amps
340 amps
Electrical Power Supply
208/60/3
System
Total Full Load Amps
492 amps
Maximum Overcurrent Capacity
600 amps
Minimum Circuit Ampacity
506 amps
Fans (2 ECM type)
5.7 amps each
Dimensions
Each Chiller Module
39 W x 95 L x 87 H in.
(a)
Overall Chiller System
156 W x 95 L x 87 H in.
(b)
Weight
Each Chiller Module
2,500 lbs.
Overall Chiller System
10,000 lbs.
(a)
Primary module is 46 in. wide, including power distribution panel.
(b)