23
CG-SVX06F-GB
Installation
When ordered, the outdoor air
temperature sensor and associated
electronics are factory-mounted
and wired in the control panel of
the chiller. This sensor has to be
installed outdoors to allow for proper
operation of the chiller. The wiring of
the sensor has to be performed with
a 2 wires cable of 0.75 to 1.5 mm²
type H05WWF or equivalent. The
maximum length of this cable is 305
m. (see Figure 10). The IPC bus is
factory-wired.
Figure 10 - Outdoor ambient air sensor connection (self-thread screw)
Figure 11 - CGWN and CCUN main power supply connection (205-211)
L1
L2
L3
1Q10
Self-thread screw