21
CG-SVX06F-GB
Installation
Figure 8 - CGWN and CCUN main power supply connection (1) (205-211)
2
1
1 = Power cable inlet
2 = Disconnect switch
(1) shown here : CGWN. Components in same location on CCUN.
Electrical connections
CAUTION:
1. The greatest care should be taken
when cutting through passages
and installing electric wiring.
Under no circumstances should
chips of metal or cuttings of
copper or isolating material fall
into the starter panel or electric
components. Relays, contactors,
terminals and control wiring should
be covered and protected before
power supplies are connected.
2. Install power supply cabling
as shown in wiring diagram.
Adequate cable gland should be
chosen, ensuring no foreign bodies
enter the electrical housing or
components.
CAUTION:
1. Cabling must comply with local
standards. The type and location
of fuses must also comply with
standards. As a safety measure,
fuses should be visibly installed,
close to the unit.
2. CAUTION! To avoid corrosion,
overheating or general damage,
at terminal connections, unit is
designed for copper conductors
only. In case of aluminum
conductors an intermediate
connection box must be added.
In case of aluminum cable bi
material connecting device is
mandatory. Cable routing inside
control panel should be made
case by case by installer.
Soft starter recommended setting
Acceleration time: 0.5 seconds full
speed
Start-up torque: 50%
Deceleration time: 0 seconds
Use adjustment setting button.