Table 5 - Recommended liquid line diameters for vertical or horizontal risers (Circuit 1)
Table 6 - Recommended liquid line diameters for vertical or horizontal risers (Circuit 2)
Leaving chilled water temperature (°C)
Unit size
-12
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
CCUN
205
5/8”
7/8”
1”1/8
CCUN
206
5/8”
7/8”
1”1/8
CCUN
207
5/8”
7/8”
1”1/8
CCUN
208
7/8”
1”1/8
1”3/8
CCUN
209
7/8”
1”1/8
1”3/8
CCUN
210
7/8”
1”1/8
1”3/8
CCUN
211
7/8”
1”1/8
1”3/8
CCUN
212
1”1/8
1”3/8
1”5/8
CCUN
213
1”1/8
1”3/8
1”5/8
CCUN
214
1”1/8
1”3/8
1”5/8
CCUN
215
1”1/8
1”3/8
1”5/8
Leaving chilled water temperature (°C)
Unit size
-12
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
CCUN
205
5/8”
7/8”
1”1/8
CCUN
206
5/8”
7/8”
1”1/8
CCUN
207
5/8”
7/8”
1”1/8
CCUN
208
7/8”
1”1/8
1”3/8
CCUN
209
7/8”
1”1/8
1”3/8
CCUN
210
7/8”
1”1/8
1”3/8
CCUN
211
7/8”
1”1/8
1”3/8
CCUN
212
1”1/8
1”3/8
CCUN
213
1”1/8
1”3/8
1”5/8
CCUN
214
1”1/8
1”3/8
1”5/8
CCUN
215
1”1/8
1”3/8
1”5/8