background image

 

Page 17

Installer’s Guide

Gas Pressure Set-up Precautions

IMPORTANT:  

Do not connect gas piping to the unit until a line 

pressure test has been completed. This unit should never be 

exposed to gas line pressure in excess of 14 inches water column 

(1/2 PSIG). The furnace and its equipment shutoff valve must be 

disconnected from the gas supply piping system during any pres-
sure testing of that system at test pressures in excess of 1/2 psi. 

The furnace must be isolated from the gas supply piping system 

by closing its individual manual shut-off valve during any pressure 

testing of the gas supply piping system at test pressures less than 

or equal to 1/2 psig (3.48 kPa).

Gas Supply Line Pressure

Before connecting the unit to the gas supply line, be sure to deter-

mine the gas pressure in the line.

If the gas supply pressure is excessive (above 14 inches water 

column or 1/2 psig), install a pressure regulator either at the supply 

source or in the branch circuit serving the unit.  Once the regulator 

is installed, set it to provide a pressure of 7 inches water column 

with the unit operating and no greater than 14 inches water column 

with the unit not operating.

NOTE: Gas pressure in excess of 14 inches water column 

(1/2  psig) may damage the regulator, while improper regulation 

may result at pressures lower than 5.5 inches water column at 

the unit inlet.

If the supply line pressure is below the minimum supply pressure 

indicated on the unit nameplate, contact the gas supply company.

Follow these steps to complete the installation of the unit gas pip-

ing.  See Figure 17.

NOTE:  The shut-off gas cock must be installed outside of the 

unit and should meet the specifications of all applicable national 

and local codes

.

Table 2. Natural Gas Only

TABLE OF CUBIC FEET PER HOUR OF GAS

FOR VARIOUS PIPE SIZES AND LENGTHS

PIPE
SIZE

(inch)

LENGTH OF PIPE (feet)

10

20

30

40

50

60

70

1/2

132

92

73

63

56

50

46

3/4

278

190

152

130

115

105

96

1

520

350

285

245

215

195

180

1-1/4

1050

730

590

520

440

400

370

  THIS TABLE IS BASED ON PRESSURE DROP OF 0.3 INCH W.C. 
AND 0.6 SP.GR. GAS

IMPORTANT

:

  

Before making the gas pipe connection give serious 

consideration to providing the clearance necessary to remove the 
access panels on the unit (e.g., economizer and filter access panels).

NOTE:  In the absence of local codes, the installation must con-
form with American National Standard--Z223.1--National Fuel 
Gas Code, Latest Revision.

The available gas supply must agree with the required gas supply 
marked on the unit nameplate.  Minimum permissible gas supply 
pressure for purpose of 

input adjustment

 must be at least 7.0 in. w. 

c. (inches water column) for natural gas and 11 in. w. c. for LP Gas.

Pipe Delivery Schedule

NOTE:  The following procedure and tables apply to Natural 
Gas 

only.

  1. Obtain from the gas company the heating value and specific 

gravity of the gas delivered.

  2. Determine the exact length of pipe needed.

  3. Read BTUH input nameplate on the furnace.

  4. Use the multiplier opposite the specific gravity of the gas given 

in Table 1 below and insert in the following formula:

  5. Using Table 2, select the pipe length nearest to calculated size.

Table 1

. Specific Gravity Multiplier

DEALER INSTALLED

GROUND UNION

1/8" N.P.T.PLUGGED

ACCESS FOR TEST

GAUGE CONNECTION

FROM

GAS SUPPLY

FIELD SUPPLIED MAIN

GAS VALVE, MUST BE

INSTALLED BY DEALER

OUTSIDE OF UNIT.

UNIT

TO MAIN

CONTROL

VALVE

6"

MIN

DRIP LEG
(6" MIN)

Figure 17. Gas Pipe

NOTE:  If this is an LP Gas application, consult your LP Gas 
supplier for pipe sizes and deliveries.

  6.  Follow this line vertically down to the exact CFH found in Step 4 

above or the next highest value.

  7. Read horizontally to the left of this column for the required pipe 

size diameter.

Furnace Input in BTUH

Gas Heat Contne in BTU/Cu. Ft. X Multiplier

CFH =

  1. Install a tapped, Style A (1/8-inch NPT tap) shut-off gas cock at 

the end of the gas supply line near the unit.  Be sure the tapped 
gas cock is downstream of the pressure regulator, if used.

  2. Install a ground union joint downstream of the shut-off cock.  

This joint must also be installed outside of the unit.

  3.  Install a drip leg at least six (6) inches in depth next to the union 

as shown in Figure 17.  This drip leg is required to collect any 
sediment that may be deposited in the line.

SPECIFIC 

GRAVITY

MULTIPLIER

MULTIPLIERS TO BE USED 

WHEN THE SPECIFIC GRAV-

ITY OF THE GAS IS OTHER 

THAN 0.60

.50

1.10

.55

1.04

.60

1.00

.65

.962

Содержание 4YCY4042C

Страница 1: ...out the evaporator fan or coil access panels in place Reinstall the access panels after performing maintenance proceedures on the fan Operating the unit without the access panels properly installed ma...

Страница 2: ...per service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and approved POE compres sor oil IMPORTANT W...

Страница 3: ...work to Roof Frame 16 Attaching Horizontal Ductwork to Unit 16 Condensate Drain Piping 16 Gas Piping Installation 16 Pipe Delivery Schedule natural gas only 17 Gas Pressure Set up Precautions 17 Gas S...

Страница 4: ...Guide Step 2 Determine Unit Clearances Figure 1 4YCZ6036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from u...

Страница 5: ...Page 5 Installer s Guide Figure 2 4YCZ6036 2 of 3...

Страница 6: ...Page 6 Installer s Guide Figure 3 4YCZ6036 3 of 3...

Страница 7: ...Page 7 Installer s Guide Figure 4 4YCZ6048 through 4YCZ6060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Страница 8: ...Page 8 Installer s Guide Figure 5 4YCZ6048 through 4YCZ6060 2 of 3...

Страница 9: ...Page 9 Installer s Guide Figure 6 4YCZ6048 through 4YCZ6060 3 of 3...

Страница 10: ...to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabricate...

Страница 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airfl...

Страница 12: ...abs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparing the unit for lifting check the unit dimension drawings for center of gravity for lifting safety Figur...

Страница 13: ...roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails are...

Страница 14: ...ible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars Base of unit rest on top of curb rails Dr...

Страница 15: ...rizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Ang...

Страница 16: ...ise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two...

Страница 17: ...making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local cod...

Страница 18: ...chonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the...

Страница 19: ...ns Models that require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1...

Страница 20: ...tioning systems been checked at the service ports for charge and leak tested if necessary Does the condenser fan and indoor blower turn free without rub bing and are they tight on the shafts Has the i...

Страница 21: ...Page 21 Installer s Guide Figure 22 4YCZ6 Field Wiring Diagram NOTE For economizer wiring instructions see the Installer s Guide that came with your economizer...

Страница 22: ...ating Cycle Theseunitsareequippedwithasolid stateignitioncontrolthatlights the burners each time the thermostat calls for heat The burners are extinguished during the OFF cycle The gas heating section...

Страница 23: ...nd postpurge The indoor blower motor will continue to operate at the current speed for 60 or 90 seconds after the flames are extinguished Sequence of Operation Safety Sequences This product is equippe...

Страница 24: ...stible materials gasoline or other flammable vapors or liquids near the unit WARNING Someoftheperiodicmaintenancefunctionsofthe4YCZ6unitcan beperformedbytheowner thisincludesreplacingthedisposable or...

Страница 25: ...Hood and Combustion Blower Cleaning Manifold Pressure Check and Adjust 1 Connect a manometer to the pressure tap at the outlet side of the unit s gas valve remove the Control Heat access panel Read th...

Страница 26: ...3 Flashes Pressure switch problem detected Fast Flash Rate Not used 4 Flashes High Limit switch protection device open Steady ON Normal No Call for Heat 5 Flashes Flame sensed and gas valve not energi...

Страница 27: ...Page 27 Installer s Guide...

Страница 28: ...ide Trane 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specification without n...

Отзывы: